Section
7 Batteries
7.1 General requirements
7.1.1 The requirements of this Section apply to aqueous and non-aqueous permanently installed
secondary batteries of the vented and valve-regulated sealed type.
- Goal
Safe energy storage and dependable supply of
power to consumers.
- Functional requirements
Reasonably foreseeable hazards
external to the battery shall be identified and managed.
Reasonably
foreseeable hazards internal to the battery shall be identified and
managed.
7.1.2 A vented
battery is one in which the cells have a cover provided with an opening
through which the products of electrolysis and evaporation are allowed
to escape freely from the cells to the atmosphere.
7.1.3 A valve-regulated
sealed battery is one in which the cells are closed but have an arrangement
(valve) which allows the escape of gas if the internal pressure exceeds
a predetermined value. The electrolyte cannot normally be replaced.
7.1.4 The following Sections apply to lead acid, nickel cadmium and lithium cell
chemistries. While some of the same mitigations would be applicable, fixed charging
stations for portable lithium batteries are not covered by these requirements due to
differences in both design and arrangements. Where other cell chemistries or
arrangements are to be used, then a Risk Assessment is to be carried out in accordance
with the requirements of Vol 2, Pt 1, Ch 3, 18 Risk Assessment (RA). The Risk
Assessment is to include, but is not limited to:
- cell type;
- battery construction;
- the battery management;
- location;
- ventilation requirements;
- installation; and
- fire.
7.1.5 Lithium battery systems are to be Type Approved in accordance with LR’s Type
Approval System Test Specification Number 5 (2019), or alternatively manufactured
and tested to assess compliance with the applicable International or National Standards,
and application of an acceptable quality management system, may be submitted for
consideration.
7.1.6 The battery management systems are to be Type Approved in accordance with LR’s Type
Approval System Test Specification Number 1 (2018), or alternatively manufactured and
tested to assess compliance with the applicable International or National Standards,
and application of an acceptable quality management system, may be submitted for
consideration.
7.1.7 Where the lithium battery total system installation is less than 20 kWh then it is to be
housed in a gastight steel enclosure with a gastight ventilation duct leading to a safe
space on open deck and is to be suitable for withstanding the temperatures and pressures
generated in the worst case thermal runaway condition. The battery system is to satisfy
the requirements of LR’s Type Approval System Test Specification Number 5 (2019),
or an equivalent and acceptable National or International Standard, amended where
necessary for a battery space ambient temperature of 45°C. Alternative arrangements are
subject to special consideration.
7.1.8 The following Sections apply to lithium battery system installations of a capacity 20
kWh or greater and are in addition to those applicable in other Parts of these
Rules:
- Vol 2, Pt 9, Ch 2, 7.1 General requirements 7.1.9;
- Vol 2, Pt 9, Ch 2, 7.2 Design and construction 7.2.2 to Vol 2, Pt 9, Ch 2, 7.2 Design and construction 7.2.6;
- Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.11;
- Vol 2, Pt 9, Ch 2, 7.4 Installation 7.4.5 to Vol 2, Pt 9, Ch 2, 7.4 Installation 7.4.9;
- Vol 2, Pt 9, Ch 2, 7.5 Thermal management and ventilation 7.5.7 and Vol 2, Pt 9, Ch 2, 7.5 Thermal management and ventilation 7.5.11;
- Vol 2, Pt 9, Ch 12, 1.1 Testing 1.1.6.
7.1.9 For lithium battery system installations of nominal voltages exceeding 1500
V d.c., a Risk Assessment is to be carried out in accordance with the requirements of
Vol 2, Pt 1, Ch 3, 18 Risk Assessment (RA).
7.2 Design and construction
7.2.1 Batteries are to be constructed so as to prevent spilling of the electrolyte
due to motion and to minimise the emission of electrolyte spray.
7.2.2 A Failure Mode and Effects Analysis (FMEA) is to be carried out for the lithium battery
system installation and is to consider the effects of failure upon safety and
dependability of the lithium battery system installation, taking account of reasonably
foreseeable internal and external failures such that the goal and functional
requirements of Vol 2, Pt 9, Ch 2, 7.1 General requirements 7.1.1 are achieved and
is to include but is not limited to the following:
- overpressure, fire and explosion;
- electrical short circuit due to leakage of cell electrolyte or
mechanical impact;
- venting out flammable and toxic gases;
- rupture of the casing of cell, battery module, battery pack or
battery system with exposure of internal components; and
- ingress of water into the battery space from cooling system
leak, fire suppression system release and/or adjacent areas.
7.2.3 The casing of a lithium cell and/or battery module is to incorporate pressure relief
functions that will prevent overpressure, rupture or explosion of the battery module
enclosure (see
Vol 2, Pt 9, Ch 12, 1 Testing and trials).
7.2.4 The lithium battery management system is to continuously monitor the
condition of cells, battery modules or battery packs and to maintain them within their
specified safe operating region. As a minimum the alarms and safeguards as indicated in
Table 2.7.1 Lithium battery system: alarms and safeguards are to
be provided:
Table 2.7.1 Lithium battery system: alarms and safeguards
Item
|
Alarm
|
Note
|
Cell
voltage*
|
High
|
Automatic termination
of the cell charge current. See Notes 1 and 5
|
Low
|
Per cell. Automatic
prevention of cell discharge. See Notes 2 and 5
|
Cell
temperature*
|
1st stage
high
|
Per sensor.
See Notes 4 and 5
|
2nd stage
high
|
Per sensor. Automatic
shutdown of battery system. See Notes 4 and 5
|
Low
|
Automatic charge and
discharge current limitation. See Notes 3 and 4
|
Charge current of the
battery cells
|
High
|
Automatic reduction
of charge/discharge current. See Note 3
|
Communication failure
between battery management system and external charge controller
system
|
Failure
|
Automatic shutdown of battery system
See Note 6
|
Battery management
system
|
Failure
|
Automatic shutdown of
battery system
|
Temperature
sensor
|
Failure
|
Automatic shutdown of
battery system
|
Voltage
sensor
|
Failure
|
Automatic shutdown of
battery system
|
Emergency
trip*
|
Active
|
Automatic shutdown of battery system
See Note 5
|
Insulation
resistance
|
Low
|
-
|
Note 1. Cell voltage is to be maintained below the cell manufacturer
specified upper limit charge voltage.
Note 2. Cell voltage is to be maintained above the cell manufacturer
specified lower limit discharge voltage.
Note 3. Cell charge/discharge current is to be controlled within cell
manufacturer specified current limits.
Note 4. Cell temperature is to be controlled within the cell manufacturer
specified temperature limits.
Note 5. For lithium batteries used for Mobility systems, Ship Type systems,
Ancillary systems or emergency services, only items marked * are to
initiate automatic shutdown.
Note 6. For lithium
batteries used as an emergency source of power, communication failure is
to automatically stop and prevent charging.
Footnote: Automatic shutdown of battery system includes termination of
battery charging and discharging and disconnection from electrical
distribution network.
|
7.2.5 A fully independent hard-wired means to disconnect the battery system in an emergency
from power distribution is to be provided. This emergency trip is to be located outside
of the battery space and situated such that it will remain accessible in the event of an
emergency inside the battery space and is to initiate an audible and visual alarm at the
relevant control stations to advise duty personnel of the emergency condition.
7.2.6 For lithium battery system installations the following is to be measured and displayed
at relevant manned control stations:
- State of charge (SOC) and state of health (SOH) are to be
displayed at relevant control stations and on the navigating bridge.
- System alarms are to be displayed at relevant
control stations and at least a common alarm displayed on the navigating bridge.
7.3 Location
7.3.1 Vented
batteries connected to a charging device with a power output of more
than 2 kW, calculated from the maximum obtainable charging current
and the nominal voltage of the battery, are to be housed in an adequately
ventilated compartment assigned to batteries only, or in an adequately
ventilated suitable box on open deck.
7.3.2 Vented
batteries connected to a charging device with a power output within
the range 0,2 kW to 2 kW, calculated from the maximum obtainable charging
current and the nominal voltage of the battery, are to be installed
in accordance with Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.1,
or may be installed in a box within a well ventilated machinery or
similar space.
7.3.3 Vented
batteries connected to a charging device with a power output of less
than 0,2 kW, calculated from the maximum obtainable charging current
and the nominal voltage of the battery, may be installed in an open
position or in a battery box in any suitable space.
7.3.4 Where
more than one charging device is installed for any battery or group
of batteries in one location, the total power output is to be used
to determine the installation requirements of Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.1, Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.2 or Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.3.
7.3.5 Valve-regulated
sealed batteries may be located in compartments with standard marine
or industrial electrical equipment provided that the ventilation requirements
of Vol 2, Pt 9, Ch 2, 7.5 Thermal management and ventilation 7.5.10and the charging
requirements of Vol 2, Pt 9, Ch 2, 7.6 Charging facilities 7.6.4 and Vol 2, Pt 9, Ch 2, 7.6 Charging facilities 7.6.5 are complied with. Equipment
that may produce arcs, sparks or high temperatures in normal operation
is not to be in close proximity to battery vent plugs or pressure
relief valve outlets.
7.3.6 Where
lead-acid and nickel-cadmium batteries are installed in the same compartment,
precautions are to be taken, such as the provision of screens, to
prevent possible contamination of electrolytes.
7.3.7 Where
batteries may be exposed to the risk of mechanical damage or falling
objects, they are to be suitably protected.
7.3.8 A permanent
notice prohibiting naked lights and smoking is to be prominently displayed
in all compartments containing vented type batteries.
7.3.9 Only
electrical equipment necessary for operational reasons and for the
provision of lighting is to be installed in compartments provided
in compliance with Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.1,
the compartment ventilation exhaust ducts and zones within a 1,5 m
radius of the ventilation outlet(s). Such electrical equipment is
to be certified for group IIC gases and temperature Class T1 in accordance
with the applicable parts of IEC 60079: Explosive atmospheres,,
or an acceptable and relevant National Standard.
7.3.10 A
permanent notice is to be prominently displayed adjacent to battery
installations advising personnel that replacement batteries are to
be of an equivalent performance type. For valve-regulated sealed batteries,
the notice is to advise of the requirement for replacement batteries
to be suitable with respect to products of electrolysis and evaporation
being allowed to escape from cells to the atmosphere, see also
Vol 2, Pt 9, Ch 1, 1.7 Alterations and additions 1.7.6.
7.3.11 The lithium battery space is not to be located forward of the collision bulkhead and is
not to be contiguous to the boundaries of machinery spaces of Category A or those spaces
containing the main source of electrical power, associated transforming equipment (if
any) or the main switchboard. The boundaries of the lithium battery space are to be part
of a vessel structure or enclosures and provided with ‘A-60’ insulation of the bulkhead
unless the space is adjacent to spaces of negligible fire risk such as cofferdams, void
spaces, or similar in which case consideration can be made to reduce the insulation to
‘A-0’. Penetrations through these boundaries are to be protected to the same fire
protection standard. Special consideration will be made for a ship not built of steel or
equivalent material. All other safety systems within the lithium battery spaces are to
be in accordance with the requirements of this Part or, if not made explicit, at least
equivalent to those of a machinery space of Category A.
7.4 Installation
7.4.1 Batteries are to be arranged such that each cell or crate of cells is
accessible from the top and at least one side and it is to be ensured that they are
safely secured.
7.4.2 The materials used in the construction of a battery rack or stand are to be
resistant to the battery electrolyte or suitably protected by paint or a coating.
7.4.3 Measures are to be taken to minimise the effect of any electrolyte spillage
and leakage, for example the use of rubber capping around the top of the cells and the
provision of a tray of electrolyte-resistant material below the cells, unless the deck
is suitably protected with paint or a coating.
7.4.4 The interiors of all compartments for batteries, including crates, trays,
boxes, shelves and other structural parts therein, are to be of an electrolyte-resistant
material or suitably protected, for example with paint or a coating.
7.4.5 Battery systems are to be installed in accordance with manufacturer’s recommendations
taking account of the results of the risk assessment or FMEA, where applicable.
7.4.6 The lithium battery space and the crates, trays, boxes, shelves and other structural
parts therein are to be designed and constructed such that the structural integrity of
the battery space will not be compromised in the event of a lithium fire.
7.4.7 The lithium battery space is to be fitted with suitable fixed detectors in accordance
with manufacturer’s recommendations and which are capable of providing early
identification of a fire or thermal runaway condition. Early identification is to
include high cell temperature or detection of electrolyte solvent vapours and a
combination of smoke and heat detectors. When activated, the fire detection system is to
initiate an alarm to the relevant control stations and on the navigating bridge and is
to initiate the automatic isolation of electric systems within the lithium battery
space, except as described below, and activate the fixed fire-fighting system.
7.4.8 In the event that a fire or thermal runaway condition is identified, the battery
monitoring system is to initiate protective features such as automatic safe isolation of
the batteries. Ventilation necessary for extraction of gasses, active cooling systems,
and thermal/safety monitoring and alarm are to be continued prior to, during and after
an overheating or fire event. Failure of the monitoring system is to be alarmed to the
ship’s safety system and is to result in the battery system automatically reverting to a
defined safe state.
7.4.9 An appropriate water-based fixed fire-fighting system in accordance with SOLAS II-2,
Part C, Regulation 10.4.1.1.3 and the manufacturer’s recommendation is to be provided
for the lithium battery space. The fixed fire-fighting system is to be suitable for heat
removal, boundary cooling and/or extinguishing for the duration that the heat and/or gas
release are present. Fixed fire-fighting systems using a medium other than water which
provide equivalent heat removal, boundary cooling and/or extinguishing for the duration
that the heat and/or gas release is present can be taken into consideration provided
that appropriate fire tests have been conducted. In particular, the fire-extinguishing
media are to be chosen as appropriate for the specific type and characteristics of fire
foreseen.
7.4.10 The fixed fire-fighting control system is to be located outside the battery space, be
activated automatically and be capable of manual activation. In addition to the fixed
fire-fighting system, the battery space is to be provided with a minimum of two (2)
portable and suitable fire-extinguishers located outside the space at or near the
entrance(s) and in agreement with the Naval administration/authority. The number and
position of hydrants are to be such that at least two jets of water not emanating from
the same hydrant, each from a single length of hose, can reach any part of the lithium
battery space. Such hydrants are to be positioned in close proximity to the lithium
battery space. Any part of the fire-fighting system which crosses through the lithium
battery space without serving it is to be avoided.
7.4.11 The fire detection and automatic water-based fire-fighting systems are to be in
accordance with the recommendations of the battery manufacturer and the following
sub-Sections of these Rules:
7.4.12 The technical description detailed in Vol 2, Pt 9, Ch 1, 1.4 Documentation required for design review 1.4.27 is to consider the actual battery system installation and its
integration into the ship, including but not limited to the following:
- arrangement of battery compartment (location, including fire
risk of adjacent spaces/compartments, fire burden from equipment other than
batteries, heat sources, etc.);
- temperature control arrangements for the battery space and their
contribution to system safety;
- ventilation arrangements to prevent concentrations of gasses
within the space in case of uncontrolled thermal runaway;
- hazardous area(s) requirements;
- reasonable gas tightness of ventilation ducting;
- fire integrity of the space;
- the use of fire extinguishing arrangements for cooling in the
case of uncontrolled thermal runaway.
The FMEA referenced in Vol 2, Pt 9, Ch 2, 7.2 Design and construction 7.2.2 should
address any additional failure modes identified during the preparation of this technical
description.
7.4.13 The lithium battery space is to be provided with two means of escape, at least one
independent of any watertight door and leading to a safe position outside the space. One
of the escapes is to be suitable for the passage of a stretcher. At each entrance/exit
an emergency escape breathing device (EEBD) is to be provided. Where the maximum travel
distance to the door within the lithium battery space is less than 5 m, a single means
of escape is acceptable. The lithium battery space is not to be considered as part of an
escape route (primary or secondary) from any other accommodation, control, service
space, machinery space of Category ‘A’ and high fire risk area such as a garage, paint
store, etc.
7.5 Thermal management and ventilation
7.5.1 Battery
compartments and boxes are to be ventilated to avoid accumulation
of dangerous concentrations of flammable gas.
7.5.2 Ducted
natural ventilation may be employed for battery installations connected
to a charging device with a power output of 2 kW or less, provided
the exhaust duct can be run directly from the top of the compartment
or box to the open air above, with no part of the duct more than 45º
from the vertical. A suitable opening is also to be provided below
the level of the top of the batteries, so as to ensure a free ventilation
air flow. The ventilation duct is to have an area not less than 50
cm2 for every 1 m3 of battery compartment or
box volume.
7.5.3 Where
natural ventilation is impracticable or insufficient, mechanical ventilation
is to be provided, with the air inlet located near the floor and the
exhaust at the top of the compartment.
7.5.4 Mechanical
exhaust ventilation complying with Vol 2, Pt 9, Ch 2, 7.5 Thermal management and ventilation 7.5.9 is to be provided for battery installations connected to a
charging device with a total maximum power output of more than 2 kW.
Also, to minimise the possibility of oxygen enrichment, compartments
and spaces containing batteries with boost charging facilities are
to be provided with mechanical exhaust ventilation irrespective of
the charging device power output.
7.5.5 The
ventilation system for battery compartments and boxes, other than
boxes located on open deck or in spaces to which Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.2, Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.3 and Vol 2, Pt 9, Ch 2, 7.3 Location 7.3.5 refer,
is to be separate from other ventilation systems. The exhaust ducting
is to be led to a location in the open air, where any gases can be
safely diluted, away from possible sources of ignition and openings
into spaces where gases may accumulate.
7.5.6 Fan
motors associated with exhaust ducts from battery compartments are
to be placed external to the ducts and the compartments.
7.5.7 Ventilating fans for battery compartments are to be so constructed and be of
material such as to minimise risk of sparking in the event of the impeller touching the
casing, and are to be suitable for the potentially hazardous and corrosive gases
produced in a thermal runaway condition. Non-metallic impellers are to be of an
anti-static material.
7.5.8 Battery
boxes are to be provided with sufficient ventilation openings located
so as to avoid accumulation of flammable gas whilst preventing the
entrance of rain or spray.
7.5.9 The
ventilation arrangements for all installations of vented type batteries
are to be such that the quantity of air expelled is at least equal
to:
Q
|
= |
110 n
|
where
n
|
= |
number
of cells in series |
I
|
= |
maximum
current delivered by the charging equipment during gas formation,
but not less than 25 per cent of the maximum obtainable charging current
in amperes |
Q
|
= |
quantity
of air expelled in litres/hr. |
7.6 Charging facilities
7.6.1 Charging
facilities are to be provided for all secondary batteries such that
they may be completely charged from the completely discharged state
in a reasonable time having regard to the service requirements.
7.6.2 Suitable
means, including an ammeter and a voltmeter, are to be provided for
controlling and monitoring charging of batteries, and to protect them
against discharge into the charging circuits.
7.6.3 For
floating circuits or any other conditions where the load is connected
to the battery whilst it is on charge, the maximum battery voltage
is not to exceed the safe value for any connected apparatus.
7.6.4 Arrangements
are to be fitted to automatically control the charging rate of valve
regulated sealed batteries so as to prevent overcharging which may
lead to an excessive evolution of gas. These arrangements are to take
account of any requirements for prolonged operation under close down
conditions.
7.6.5 Boost
charge facilities, where provided, are to be arranged such that they
are automatically disconnected should the battery compartment ventilation
system fail.
7.7 Recording of batteries for emergency and essential services
7.7.1 A schedule of batteries fitted for use for Mobility systems, Ship Type
systems, and emergency services is to be compiled and maintained.
7.7.3 When additions or alterations are proposed to the existing batteries for
Mobility systems, Ship Type systems, and emergency services, the schedule and
replacement procedure documentation are to be updated to reflect the proposed
installation and submitted in accordance with Vol 2, Pt 9, Ch 1, 1.7 Alterations and additions 1.7.1.
7.7.4 The
schedule and replacement procedure documentation are to be made available
to the LR Surveyor on request.
|