Section
4 Electric propulsion systems
4.1 General
4.1.2 Where
the arrangements permit a propulsion motor to be connected to a generating
plant having a continuous rating greater than the motor rating, means
are to be provided to limit the continuous input to the motor to a
value not exceeding the continuous full load torque for which the
motor and shafts are approved.
4.1.3 The ventilation and cooling systems for electrical propulsion equipment are
to be provided with monitoring devices arranged to operate an alarm if the temperature
of the heated cooling medium exceeds a predetermined safe value. See also
Vol 2, Pt 9, Ch 3, 7.2 Semiconductor converters 7.2.5.
4.1.5 Propulsion
motors, generators and converters are to be provided with means to
prevent the accumulation of moisture and condensate when operating
at low power levels, or when idle.
4.2 System design and arrangement
4.2.1 In general,
for a ship to be assigned an unrestricted service notation, it is
to have two independently driven propellers or other propulsion devices,
each connected with at least one electric motor, where these form
the sole means of propulsion.
4.3 Power requirements
4.3.1 The
propulsion system is to have sufficient power for manoeuvring the
vessel and for going astern. With the ship travelling at her maximum
service speed the propulsion equipment is to be capable of stopping
and reversing the ship in an agreed time.
4.3.2 The
propulsion system is to have adequate torque and power margins for
all operating conditions including manoeuvring and rough weather with
due regard to propeller and ship characteristics.
4.3.3 The
electric power for the propulsion system may be derived from generating
sets dedicated to propulsion duty or from a central power generation
plant which serves both propulsion and ship service loads.
4.3.4 Where
propulsion power is derived from a central, common, power plant the
control system is to ensure a safe distribution of power between propulsion
and ship services, with tripping of non-essential loads and/or reduction
in propulsion power if necessary.
4.3.5 Where
a central power generation system is employed, the number and rating
of generator sets is to be such that with one set out of action the
remaining sets are capable of providing all essential and normal ship
service loads whilst maintaining an effective level of propulsion
power.
4.3.6 Where,
in a central power generation system, the electrical power requirements
are normally supplied by two or more generating sets operating in
parallel, on sudden loss of power from one set, the rating of the
remaining set(s) in service is to be sufficient to ensure uninterrupted
operation of essential services and an effective level of propulsion
power.
4.3.7 Where
a central power generation system is employed, means are to be provided
to connect available generator sets to meet the power requirement
of the electric propulsion system. Arrangements are to be in place
to prevent generator sets being automatically disconnected during
ship manoeuvres.
4.3.8 Where
forced cooling is used on propulsion motors, it is to be possible
to operate the motor at a defined reduced power level in the event
of failure of the forced cooling.
4.3.9 Total harmonic distortion of the a.c. voltage waveform up to 10 per cent on
electric propulsion circuits, not directly connected to the main source of electrical
power, may be considered where details are submitted which demonstrate that the
equipment and systems are capable of operating under such conditions. Where a higher
value of THD is specified, see
Vol 2, Pt 9, Ch 1, 2.1 Quality of power supplies (QPS) 2.1.4.
4.4 Propulsion control
4.4.1 Propulsion
control systems are to be stable throughout their normal operating
range and arranged to attenuate any effects of cyclic propeller load
fluctuations caused by wave action.
4.4.2 Control
of propeller speed, and/or pitch, from zero to full ahead or astern
is to be provided.
4.4.3 The
control system is to ensure that there is no dangerous overspeeding
of propulsion motors upon loss of load.
4.4.4 Interlocks
are to be provided in the control system to ensure that ahead and
astern circuits are not energised simultaneously.
4.4.5 Any
single fault in either the propulsion machine excitation or power
distribution systems is not to result in a total loss of propulsion
power.
4.4.7 Each
control station is to be provided with an emergency stop function
for the propulsion motor(s). The emergency stop function is to be
independent of the normal control system.
4.4.8 The
control system is to limit the propulsion power if the power available
from the generator(s) is not sufficient to supply the demand level
of propulsion power. In the event of a power limitation, there is
to be a visual indication at the control stations.
4.4.9 Means
are to be provided to identify the cause of propulsion motor power
limitation or automatic reduction (e.g. excessive load torque, cooling
failure, high temperature, power availability).
4.4.10 Alternative
means of operation, independent of any remote system, are to be provided
to permit effective control of the propulsion equipment for all intended
functional requirements. The alternative control facility is to include
all necessary protection and power limitation features.
4.4.12 The factory acceptance test (FAT) of the propulsion control and power management system
is to be carried out according to a FAT programme acceptable to LR. A reduced FAT
programme for subsequent vessels in a series is subject to agreement by LR.
4.5 Harmonic filtering for propulsion
4.5.2 In the event of filter circuit failure, continued safe operation of the
propulsion system is to be possible by following appropriate procedures specified by
the manufacturer and/or system integrator. These procedures are to include any
operational limitations, and they are to be kept on board and made available to the
Surveyor on request.
4.6 Protection of propulsion system
4.6.1 Provision
is to be made for protection against severe overloads, and electrical
faults likely to result in damage to plant.
4.6.2 Propulsion
motors are to be capable of withstanding, without damage, the thermal
and mechanical effects of a short-circuit at the terminals.
4.6.3 Propulsion
converters are to be capable of withstanding, without damage, the
thermal and mechanical effects of a short-circuit at the terminals
or connection to a propulsion motor with a stalled or locked rotor.
4.6.4 Electric
motors of podded propulsion units, and/or propulsion motors having
permanent magnet excitation, are to be provided with a protective
device which, in the event of a short-circuit in the motor or in the
cables between the motor and its circuit breaker, will instantaneously
open the circuit breaker and, in motors with electromagnetic excitation,
de-excite the motor. Motors with permanent magnet main excitation
are to be provided with means to prevent further damage as a result
of continued rotation after disconnection (e.g. shaft brake).
4.6.5 Safeguards
for protecting propulsion equipment against damage resulting from
earth faults are to be as specified by the equipment manufacturer.
Where the fault current flowing is liable to cause damage to the electrical
equipment, there are to be arrangements for interrupting the current
automatically.
4.6.6 For
the protection of electrical equipment and cables against overvoltages,
means are to be provided for limiting the induced voltage when field
windings and other inductive circuits are opened. Protective resistors
and devices are to be sized to cater for the likely extreme operating
conditions.
4.6.7 An alarm
is to be initiated when the excitation system of electric generators
providing propulsion power is overloaded such that damage due to heating
could occur in the generator or its cabling.
4.6.8 Where,
on stopping or reversing the propeller, regenerated energy is produced
by the propulsion motor, this is not to cause a dangerous increase
of speed in the prime mover or a dangerous overvoltage condition on
the supply system. Where a central power generation system is used,
then the voltage and frequency fluctuations are not to exceed the
limits given in Vol 2, Pt 9, Ch 1, 2 System level requirements.
4.6.9 Dynamic
braking resistors are to be suitably rated for their expected operation.
4.6.10 Loss
of flow of air or liquid cooling of propulsion converters, where used,
is to initiate an alarm at an attended control position. Loss of flow
of air or liquid cooling is not to result in immediate damage to the
propulsion converter, see
Vol 2, Pt 9, Ch 3, 7.2 Semiconductor converters 7.2.4.
4.6.11 The system integrator is to determine the protection co-ordination required for high
voltage propulsion transformers. Where primary protection is to be the only means of
protection, evidence demonstrating that this is sufficient is to be submitted for
consideration, see also
Vol 2, Pt 9, Ch 4, 4.12 Protection of transformers 4.12.1.
4.6.12 Alarms
and safeguards for electric propulsion equipment are indicated in Table 5.4.1 Electric propulsion equipment:
Alarms and safeguards.
Table 5.4.1 Electric propulsion equipment:
Alarms and safeguards
Item
|
Alarm
|
Note
|
Electric propulsion equipment
ventilation and cooling medium temperature
|
High
|
See
Vol 2, Pt 4, Ch 5, 4.1 General 4.1.3 and Vol 2, Pt 4, Ch 5, 4.3 Power requirements 4.3.8
|
Electric propulsion transformer
winding temperature
|
High
|
See
Vol 2, Pt 9, Ch 3, 7.1 Transformers 7.1.1
|
Electric propulsion generator
excitation
|
Overload
|
See
Vol 2, Pt 4, Ch 5, 4.6 Protection of propulsion system 4.6.7
|
Electric propulsion generators and
motors winding temperature
|
High
|
See
Vol 2, Pt 4, Ch 5, 4.1 General 4.1.4
Actions to prevent damage to propulsion motor are to be
instigated.
|
Electric propulsion generator and
motor bearing temperature
|
1st stage high
|
See
Vol 2, Pt 4, Ch 5, 4.8 Propulsion motors – general 4.8.5
Safe shutdown to prevent damage.
|
|
2nd stage high
|
Actions to prevent damage to propulsion motor are to be
instigated.
|
Electric propulsion generator and
motor lubricating oil temperature
|
1st stage high
|
See
Vol 2, Pt 4, Ch 5, 4.8 Propulsion motors – general 4.8.7 and Vol 2, Pt 9, Ch 2, 6.1 General requirements 6.1.4 Safe shutdown to prevent
damage
|
|
2nd stage high
|
Actions to prevent damage to propulsion motor are to be
instigated.
|
Electric propulsion generator and
motor lubricating oil supply pressure
|
Low
|
See
Vol 2, Pt 4, Ch 5, 4.8 Propulsion motors – general 4.8.6 and Vol 2, Pt 9, Ch 2, 6.1 General requirements 6.1.5
|
Power limitation
|
—
|
Indication, see
Vol 2, Pt 4, Ch 5, 4.4 Propulsion control 4.4.8 and Vol 2, Pt 4, Ch 5, 4.4 Propulsion control 4.4.9
|
Note
See also IEC 60092-501:2013 Annex A.
|
4.7 Instruments
4.7.1 The
main control station is to be provided with indicating instruments
or other means of continuously monitoring the following:
-
a.c. systems
-
The line current
and excitation current of each generator, propulsion motor and propulsion
transformer primary; and for each generator, the voltage, power and
frequency.
-
The winding,
bearings and cooling system temperature of each generator, propulsion
transformer and propulsion motor.
-
d.c. systems
-
The armature
voltage and current for each generator and propulsion motor and the
current in each excitation circuit.
4.7.2 Each
control station is to be provided with instruments to indicate:
-
propeller speed;
-
direction of rotation
for a fixed pitch propeller or pitch position for a controllable pitch
propeller;
-
visual indication
of power limitation; and
-
the station in
control.
4.8 Propulsion motors – general
4.8.2 Shaft
materials for electric propulsion motors are to comply with the Rules
for Manufacture, Testing and Certification of Materials (hereinafter
referred to as the Rules for Materials) and are to be manufactured
under LR survey.
4.8.3 Propulsion
motors that form part of the electrical propulsion systems are to
have at least one embedded temperature detector (ETD) in each phase
of the machine winding in locations which may be subjected to the
highest temperature. Where there are two coil sides per slot the ETD’s
are to be located between the insulated coil sides in the slot, see
Vol 2, Pt 4, Ch 5, 4.1 General 4.1.4.
4.8.4 The
adverse effect of voltage stresses on the winding insulation caused
by the operation of switching devices is to be taken into account
in the specification, design and installation of inverter fed induction
motors.
4.8.5 A high
bearing temperature alarm is to be provided where the electric propulsion
motors are supplied with forced lubrication.
4.8.6 A low
lubricating oil pressure alarm is to be provided for electric propulsion
motors that are supplied with forced lubrication.
4.9 Propulsion motor ratings
4.9.2 Synchronous
propulsion motors are to be capable of an overload power of not less
than 10 per cent at their rated power factor for a period of 15 minutes
without injurious heating.
4.10 Propulsion motor temperature rise
4.11 Propulsion motor overloads
4.11.1 Machines
are to withstand on test, without injury, the following momentary
overloads:
-
The overload tests for propulsion machines will be specially
considered for each installation.
4.12 Propulsion motor enclosure
4.13 Survey and testing
|