6.4.1 Each
alternating current generator, unless of the self-regulating type,
is to be provided with automatic means of voltage regulation; voltage
build-up is not to require an external source of power. Provision
is to be made to safeguard the distribution system should there be
a failure of the voltage regulating system resulting in a high voltage.
6.4.2 The
voltage regulation of any alternating current generator with its regulating
equipment is to be such that at all loads, from zero to full load
at rated power factor, the rated voltage is maintained within ±2,5
per cent under steady conditions. There is to be provision at the
voltage regulator to adjust the generator no-load voltage.
6.4.3 Generators
and their excitation systems, when operating at rated speed and voltage
on no-load, are to be capable of absorbing the suddenly switched,
balanced, current demand of the largest motor or load at a power factor
not greater than 0,4 with a transient voltage dip which does not exceed
15 per cent of rated voltage. The voltage is to recover to rated voltage
within a time not exceeding 1,5 seconds. In the absence of precise
data, the applied load is to be not less than 50 per cent of rated
kVA at a power factor not greater than 0,4.
6.4.4 The
transient voltage rise at the terminals of a generator is not to exceed
20 per cent of rated voltage when rated kVA at a power factor not
greater than 0,8 is thrown off. When a generator is supplying any
load between 25 per cent and 100 per cent of rated load, and a load
equal to 25 per cent rated load at a power factor of 0,8 is suddenly
removed, the transient voltage rise at the terminals of the generator
is not to exceed 7,5 per cent.
6.4.5 Generators
and their voltage regulation systems are to be capable of maintaining,
without damage, under steady state short circuit conditions a current
of at least three times the full load rated current for a duration
of at least two seconds or where precise data is available for the
duration of any time delay which may be provided by a tripping device
for discrimination purposes. The generator terminal voltage is not
to exceed 130 per cent of the rated voltage when the short circuit
is removed.
6.4.6 Generators
required to run in parallel are to be stable from no load (kW) up
to the total combined full load (kW) of the group, and load sharing
is to be such that the load on any generator does not normally differ
from its proportionate share of the total load by more than 15 per
cent of the rated output (kW) of the largest machine or 25 per cent
of the rated output (kW) of the individual machine, whichever is less.
6.4.7 When
generators are operated in parallel, the kVA loads of the individual
generating sets are not to differ from the proportionate share of
the total kVA load by more than five per cent of the rated kVA output
of the largest machines.