Section
2 System level requirements
2.1 Quality of power supplies (QPS)
2.1.1 All electrical equipment supplied from the main and emergency sources of
electrical power and electrical equipment for Mobility systems, Ship Type systems, and
emergency services supplied from d.c. sources of electrical power is to be so designed
and manufactured that it is capable of operating satisfactorily under normally occurring
variations of voltage and frequency.
2.1.2 Unless
specified otherwise, a.c. electrical equipment is to operate satisfactorily
with the following simultaneous variations, from their nominal value,
when measured at the consumer input terminals:
-
voltage:
permanent variations +6%, -10%
transient variations due to step changes in load ±20%
recovery time 1,5 seconds
-
frequency:
permanent variations ±5%
transient variations due to step changes in load ±10%
recovery time 5 seconds
A maximum rate of change of frequency not exceeding ±1,5
Hz per second during cyclic frequency fluctuations.
2.1.3 Unless specified otherwise, the total harmonic distortion (THD) of the
voltage waveform at any switchboard or section-board is not to exceed 8 per cent of the
fundamental for all frequencies up to 50 times the supply frequency and no voltage at a
frequency above 25 times supply frequency is to exceed 1,5 per cent of the fundamental
of the supply voltage. THD is the ratio of the rms value of the harmonic content to the
rms value of the fundamental, expressed in per cent and may be calculated using the
expression:
where
V
h
|
= |
rms amplitude of a harmonic voltage of order h
|
V
1
|
= |
rms amplitude of the fundamental voltage. |
2.1.4 Where a higher value of THD is specified, all installed equipment and systems are to be
designed for the higher specified limit. This relaxation on the limit is to be
documented in the harmonic distortion calculation report.
2.1.5 Unless
specified otherwise, d.c. electrical equipment is to operate satisfactorily
with the following simultaneous variations, from their nominal value,
when measured at the consumer input terminals:
-
When supplied
by d.c. generator(s) or a rectified a.c. supply:
|
Voltage tolerance
(continuous)
|
±10%
|
|
Voltage cyclic variation
deviation
|
5%
|
|
Voltage ripple
|
10%
|
|
(a.c. rms over steady state d.c. voltage)
|
-
When supplied
by batteries:
-
Equipment connected
to the batteries during charging: Voltage tolerance +30%, -25%;
-
Equipment
not connected to batteries during charging: Voltage tolerance +20%,
-25%.
Different voltage variations as determined by the charging/discharging
characteristics, including ripple voltage from the charging device,
may be considered. When battery chargers/battery combinations are
used as d.c. power supply systems, adequate measures are to be taken
to keep the voltage within the specified limits during charging, boost
charging and discharging of the battery.
2.1.7 Where
weapons or other combat systems may degrade the quality of power supplies,
relevant details are to be advised to LR and to the prime contractor
in order that the consequences may be established.
2.2 Design, construction and location
2.2.1 Electrical
propelling machinery and associated equipment together with equipment
for services essential for the propulsion and safety of the ship are
to be constructed in accordance with the relevant requirements of
this Chapter.
2.2.2 The
design and installation of all equipment is to be such that risk of
fire due to its failure is minimised. It is, as a minimum, to comply
with a National or International Standard revised where necessary
for ambient conditions.
2.2.3 Electrical
equipment is to be suitable for its intended purpose in all conditions
in which it is expected to operate. Equipment is to be designed and
constructed in accordance with agreed specified standards. The design
and construction is to take account of both functional and environmental
requirements. For details of marine environmental conditions, reference
should be made to Annex B of IEC 60092: Electrical installations
in ships - Part 101: Definitions and general requirements.
2.2.4 Laser light sources for optical fibre systems are to be constructed in accordance with
IEC 60825-1, Safety of laser products – Part 1: Equipment classification and
requirements. Acceptance of alternative standards will be subject to
consideration by LR.
2.2.5 Optical fibre communication systems are to be constructed in accordance with IEC
60825-2, Safety of laser products – Part 2: Safety of optical fibre communication
system. Acceptance of alternative standards will be subject to consideration by
LR.
2.2.6 For
areas susceptible to deluge or submersion, cable entries are to prevent
water ingress. In general, cable entries are to be in accordance with
IEC 60092-101, Electrical Installations in Ships – Part
101: Definitions and General Requirements.
2.2.7 Where equipment intended for Mobility or Ship Type systems requires a
controlled environment, an alternative means is to be provided to maintain the required
environment in the event of a failure of the normal cooling system. Failure of the
cooling system is to initiate an alarm. Duplication of the equipment requiring cooling
can be provided instead of an alternative means of cooling, providing that the
duplicated equipment is fed from an alternative, independent cooling system.
2.2.8 Assessment
of performance parameters, such as accuracy, repeatability, etc. are
to be in accordance with an acceptable specialised naval standard,
national or international standard, e.g. IEC 60051, Direct acting
indicating analogue electrical measuring instruments and their accessories.
2.2.9 Special
consideration will be given to arrangements that comply with a relevant
and acceptable specialised Naval, National or International Standard,
such as IEC 60092-504, Electrical Installation on Ships –
Special Features: Control and Instrumentation.
2.2.10 All electrical equipment is to be constructed or selected and installed such
that:
-
live parts cannot be inadvertently touched, unless they are supplied
at the safety voltage specified in Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.2.(h);
-
it does not cause
injury when handled or touched in the normal manner; and
-
it is unaffected
by any water, steam or oil and oil vapour to which it is likely to
be exposed.
Where not exposed to direct liquid spray, electrical equipment having, as a
minimum, the degrees of protection as specified in IEC 60092-201 for the relevant
location will satisfy these requirements. For high voltage electrical equipment, the
degrees of protection as specified in IEC 60092-503 Electrical installations in ships
– Part 503: Special features AC supply systems with voltages in the range of above
1kV up to and including 36kV for the relevant location will satisfy these
requirements.Where the equipment may be exposed to direct liquid spray the
degree of protection is not to be less than IPX4. Where the equipment may be exposed to
possible liquid immersion, the degree of protection is not to be less than IPX7.
2.2.11 Switchboards, section boards and distribution boards supplying Mobility or
Ship Type systems, and emergency services, as well as cables from the respective
generators to and between these boards, are to be arranged to avoid areas of high fire
risk and elevated temperatures, for example, in close proximity to incinerators and
boilers.
2.2.12 Electrical
equipment, as far as is practicable, is to be located:
-
such that it
is accessible for the purpose of maintenance and survey;
-
clear of flammable
material;
-
in spaces adequately
ventilated to remove the waste heat liberated by the equipment under
full load conditions, at the ambient conditions specified in Vol 2, Pt 9, Ch 1, 2.3 Ambient reference and operating conditions;
-
where flammable
gases cannot accumulate. If this is not practicable, electrical equipment
is to be of the appropriate ‘safe type’, see
Vol 2, Pt 9, Ch 5, 4 Electrical equipment for use in explosive gas atmospheres or in the presence of combustible dusts;
-
where it is not
exposed to the risk of mechanical injury or damage from water, steam
or oil.
2.2.13 Equipment
design and the choice of materials are to reduce the likelihood of
fire, ensuring that:
-
where the electrical
energised part can cause ignition and fire, it is contained within
the bounds of the enclosure of the electrotechnical product;
-
the design, material(s)
and construction of the enclosure minimises, as far as is practicable,
any internal ignition causing ignition of adjacent materials; and
-
where surfaces
of the electrotechnical products can be exposed to external fire,
they do not, as far as practicable, contribute to the fire growth.
2.2.14 Insulating
materials and insulated windings are to be oil resistant to tracking,
moisture, sea air, oil and oil vapour unless special precautions are
taken to protect them.
2.2.15 The
minimum creepage and clearance distances provided for electrical connections,
terminals and similar bare live parts are to be in accordance with
a relevant International or National Standard for the equipment or
apparatus concerned. In cases where the rated voltage is outside that
given in the Standard or where no Standard is available, the minimum
creepage and clearance distances provided are to be in accordance
with Vol 2, Pt 9, Ch 3, 5.7 Creepage and clearance distances. Details of alternative
proposals including supporting design rationale and demonstration
may be submitted for consideration.
2.2.16 Studs,
screw-type of spring-type clamp terminations, satisfactory for the
normal operating currents and voltages, are to be provided in electrical
equipment for the connection of external cable, or bus-bar conductors,
as appropriate, see also
Vol 2, Pt 9, Ch 3, 8.15 Electric cable ends. There is to be adequate space and access for the terminations.
2.2.17 The
design of equipment is to enable ease of access to all parts requiring
inspection or replacement in service.
2.2.18 Equipment
is not to remain live through the control circuits and/or pilot lamps
when switched off by the control switch. This does not apply to synchronising
switches and/or plugs. Where equipment such as anti-condensation heaters
is fed from a supply separate from the main supply, isolation arrangements
are to be provided.
2.2.19 The
operation of all electrical equipment and the lubrication arrangements
are to be efficient under such conditions of vibration and shock as
arise in normal practice. This requirement excludes military aspects
that are required to be defined by Vol 2, Pt 1, Ch 3, 4.9 Military requirements
2.2.20 All
nuts and screws and clamping devices used in connection with current-carrying,
supporting and working parts are to be provided with means to ensure
that they cannot work loose by vibration and shock as arise in normal
practice.
2.2.21 To
allow ease of access, connectors are to be spaced far enough apart
to permit connection and disconnection. At test points, adequate clearance
is to be provided between connection points and controls to provide
access for testing.
2.2.22 Conductors
and equipment are to be placed at such a distance from the magnetic
compasses, or are to be so disposed, that the interfering magnetic
field is negligible when circuits are switched on and off.
2.2.23 Where electrical power is used for propulsion, the equipment is to be so
arranged that it will operate satisfactorily in the event of partial flooding by bilge
water above the tank top up to the bottom floor plate level under the normal angles of
inclination given in Vol 2, Pt 9, Ch 1, 2.3 Ambient reference and operating conditions for Mobility systems, see
Vol 2, Pt 7, Ch 2, 4 Drainage of machinery spaces. This requirement excludes military aspects that are
required to be defined by Vol 2, Pt 1, Ch 3, 4.9 Military requirements.
2.2.25 Electrical
equipment and cables for emergency alarms are to be so arranged that
the loss of alarms in any one area due to localised fire, collision,
flooding or similar damage is minimised, see
Vol 2, Pt 9, Ch 1, 2.8 Labels, signs and noticesand Vol 2, Pt 9, Ch 1, 2.5 Operation under fire conditions.
2.3 Ambient reference and operating conditions
2.3.1 Reference is to be made toVol 2, Pt 1, Ch 3, 4.4 Ambient reference conditions, Vol 2, Pt 1, Ch 3, 4.5 Ambient operating conditions and
Vol 2, Pt 1, Ch 3, 4.6 Inclination of ship for the requirements concerning: Ambient reference conditions and
Ambient operating conditions, with regards to the rating of Mobility and/or Ship Type
electrical equipment for classification of restricted and unrestricted service
conditions, and satisfactory operating conditions of machinery Mobility and/or Ship Type
systems.
2.3.2 Where
electrical equipment is installed within environmentally controlled
spaces, the ambient temperature for which the equipment is suitable
for operation at its rated capacity may be reduced to a value not
less than 35°C provided:
- the equipment is not for use for emergency services and is located
outside of machinery space(s);
- temperature control is achieved by at least two cooling units
so arranged that in the event of loss of one cooling unit, for any
reason, the remaining unit(s) is (are) capable of satisfactorily maintaining
the design temperature;
- the equipment is able to be initially set to work safety within
a 45°C ambient temperature until such a time that the lesser ambient
temperature may be achieved; the cooling equipment is to be rated
for a 45°C ambient temperature;
- alarms are provided, at a continually attended control station,
to indicate any malfunction of the cooling units.
2.4 Earthing and bonding
2.4.1 Except
where exempted by Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.2, all
non-current carrying exposed metal parts of electrical equipment and
cables are to be earthed for personnel protection against electric
shock. Bonding is to give a substantially equal potential and a sufficiently
low earth fault loop impedance to ensure correct operation of protective
devices.
2.4.2 The
following parts may be exempted from the requirements of Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.1:
-
lamp-caps, where
suitably shrouded;
-
shades, reflectors
and guards supported on lampholders or light fittings constructed
of, or shrouded in, non-conducting material;
-
metal parts on,
or screws in or through, non-conducting materials, which are separated
by such material from current-carrying parts and from earthed non-current
carrying parts in such a way that in normal use they cannot become
live or come into contact with earthed parts;
-
apparatus which
is constructed in accordance with the principle of double insulation;
-
bearing housings
which are insulated in order to prevent circulation of current in
the bearings;
-
clips for fluorescent
lamps;
-
cable clips and
short lengths of pipes for cable protection;
-
apparatus supplied
at a safety voltage not exceeding 55 V direct current or 55 V, root
mean square, between conductors, or between any conductor and earth
in a circuit isolated from the supply. Autotransformers are not to
be used for the purpose of achieving the alternating current voltage;
-
apparatus or parts
of apparatus which although not shrouded in insulating material is
nevertheless otherwise so guarded that it cannot be touched and cannot
come in contact with exposed metal.
2.4.3 Where
extraneous-conductive parts (i.e. parts not forming part of the electrical
installation and liable to introduce an electric potential) are not
bonded by separate earthing conductors, details are to be submitted
that demonstrate that a permanent, metal-to-metal connection of negligible
impedance, which will not degrade due to corrosion or vibration, will
be achieved.
2.4.4 Armouring,
braiding and other metal coverings are to be effectively earthed.
Where the armouring, braiding and other metal coverings are earthed
at one end only, they are to be adequately protected and insulated
at the unearthed end with the insulation being suitable for the maximum
voltage that may be induced. See
Vol 2, Pt 9, Ch 5, 4.9 Cable and cable installation 4.9.2 for earthing of cables
in hazardous zones or spaces.
2.4.5 The
electrical continuity of all metal coverings of cables throughout
the length of the cable, particularly at joints and tappings, is to
be ensured.
2.4.6 Earthing
conductors are to be of copper or other corrosion-resistant material
and be securely installed and protected where necessary against damage
and also, where necessary, against electrolytic corrosion. Connections
are to be so secured that they cannot work loose under vibration.
It is recommended that earthing conductors carrying RF currents should
be solid strip, not braid, to minimise the impedance.
2.4.7 The
nominal cross-section areas of copper earthing conductors for electrical
equipment are, in general to be equal to the cross-section of the
current-carrying conductor up to 16 mm2, with a minimum
of 1,5 mm2. Above this figure they are to be equal to at
least half the cross-section of the current-carrying conductor with
a minimum of 16 mm2.
2.4.8 The
nominal cross-sectional areas of copper earthing conductors for amouring,
braiding and other metal coverings of cables are, in general, to be
equal to the equivalent cross-section of the armouring, braiding and
other metal coverings with a minimum of 1,5 mm2.
2.4.9 Earthing
conductors of materials other than copper are to have a conductance
not less than that specified for an equivalent copper earthing conductor.
2.4.10 The
connection of the earthing conductor to the hull of the ship is to
be made in an accessible position, and is to be secured by a screw
or stud of a diameter appropriate for the size of the earthing conductor,
but not less than 6 mm which is to be used for this purpose only.
Bright metallic surfaces at the contact areas are to be ensured immediately
before the nut or screw is tightened and, where necessary, the joint
is to be protected against electrolytic corrosion. The connection
is to remain unpainted.
2.4.11 Bonding
straps for the control of static electricity are required for refuelling
tanks and piping systems, for flammable products and solids liable
to release flammable gas and/or combustible dust, which are not permanently
connected to the hull of the ship either directly or via their bolted
or welded supports and where the resistance between them and the hull
exceeds 1MΩ.
2.4.12 Where
bonding straps are required for the control of static electricity,
they are to be robust, that is, having a cross-sectional area of at
least 10 mm2, and are to comply with Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.6 and Vol 2, Pt 9, Ch 1, 2.4 Earthing and bonding 2.4.10.
2.5 Operation under fire conditions
2.5.1 As a
minimum, the following emergency services and their emergency power
supplies are required to be capable of being operated under fire conditions:
2.5.2 Where
cables for the emergency services listed in Vol 2, Pt 9, Ch 1, 2.5 Operation under fire conditions 2.5.1 pass through high fire risk
areas, main vertical or horizontal fire zones other than those which
they serve, they are to be so arranged that a fire in any of these
areas or zones does not affect the operation of the emergency service
in any other area or zone. This may be achieved either by:
- cables being of a fire-resistant type complying with Vol 2, Pt 9, Ch 3, 8.5 Construction 8.5.3, and at least extending
from the main control/monitoring panel to the nearest local distribution
panel serving the relevant area or zone; or
- there being at least two-loops/radial distributions run as widely
apart as is practicable and so arranged that in the event of damage
by fire at least one of the loops/radial distributions remains operational.
Areas of high fire risk include:
-
Machinery spaces including generator compartments and gas turbine
compartments but excluding those spaces which do not contain machinery having a
pressure lubrication system and where the storage of combustibles is prohibited.
-
Galleys.
-
Compartments with
tanks containing flammable liquids with a flash point lower than 60°C
or with a temperature above 32°C.
-
Compartments containing
liquid oxygen.
-
Fuel, petrol,
oil or lubricant pump spaces.
-
Magazines for
munitions and armaments.
2.5.4 Fire-resistant
electrical cables for the emergency services listed in Vol 2, Pt 9, Ch 1, 2.5 Operation under fire conditions 2.5.1, including their power supplies,
are to be run as directly as is practicable, having regard to any
special installation requirements, for example those concerning minimum
bend radii.
2.6 Operation under flooding conditions
2.6.1 Flooding
of spaces along the ship bottom that are not fitted with a double
bottom is not to result in the loss of the ability to provide electrically
operated fire, ship, crew and embarked personnel emergency safety
systems outside of the spaces.
2.6.2 Installation
of electrical equipment necessary to provide fire, ship, crew and
embarked personnel emergency safety systems in spaces along the ship
bottom not fitted with a double bottom is to be avoided, wherever
practical. Where it is proposed to install electrical equipment, including
cabling, necessary to provide fire, ship, crew and embarked personnel
emergency safety systems in such spaces, evidence is to be submitted
to demonstrate that required emergency services will be available
in other spaces in the event of flooding of the space not fitted with
a double bottom.
2.7 Electrical supplies to systems fulfilling military requirement
2.7.1 With
the exception of dedicated electrical supplies to systems fulfilling
military requirements, all other electrical supplies are to comply
with these Rules. The Rules are applicable to electrical equipment
and systems to the point of isolation of the military system or equipment.
The point of isolation is the supply side of the isolating switch,
MCCB panel, fuse panel or distribution panel dedicated to the military
system or equipment.
2.7.2 Dedicated
electrical supply arrangements to military systems are to be in accordance
with recognised International/National/specialised naval standards.
2.7.3 Where
isolating equipment is used for both military and other services,
the Rule requirements are to be applied.
2.7.4 Automatic,
hand and emergency changeover switches to military systems on the
ship’s supply system are to comply with these Rules.
2.8 Labels, signs and notices
2.8.1 Labels,
signs and notices required by this Chapter are to be positioned in
clearly visible locations which will not be obscured.
2.8.2 Labels,
signs and notices are to be easy to read under the expected operating
conditions. Character height in accordance with Table 1.2.1 Character height and viewing
distance will be considered to
satisfy this requirement.
Table 1.2.1 Character height and viewing
distance
Viewing distance (mm)
|
Minimum character height (mm)
|
Less than 500
|
2,3
|
500–1000
|
4,7
|
1000–2000
|
9,4
|
2000–4000
|
19
|
2.8.3 Controls,
indicators and displays required by this Chapter are to be labelled
to indicate their function. Labels are to be positioned in a manner
that associates the label with the item being labelled.
2.8.4 Labels,
signs and notices are to use short, clear messages. In general, warning
signs and notices are to comprise:
- a word signalling the gravity of the risk (e.g. Danger, Warning
or Caution)
- a statement of the nature and/or consequence of the hazard, and
wherever practical, an instruction giving appropriate behaviour to
avoid the hazard.
|