Section
8 Electric cables, optical fibre cables and busbar trunking systems
(busways)
8.1 General
8.1.2 Electric
cables for fixed wiring are to be designed, manufactured and tested
in accordance with the IEC Standards specified in Table 3.8.1 Electric cables or a specified standard
acceptable to the Naval Administration. On application, LR may be
able to assess the acceptability of cables in accordance with specified
standards other than the relevant IEC Standards, see also
Vol 2, Pt 9, Ch 1, 1.2 Application 1.2.4.
Table 3.8.1 Electric cables
Application
|
IEC Standard
|
Title
|
General constructional and testing
requirements
|
60092–350
|
Electrical installations in ships –
Part 350: General construction and test methods of power, control and
instrumentation cables for shipboard and offshore applications
|
Fixed power and control
circuits
|
60092–353
|
Electrical installations in ships –
Part 353: Power cables for rated voltages 1 kV and 3 kV
|
Fixed power circuits
|
60092–354
|
Electrical installations in ships –
Part 354: Single and three-core power cables with extruded solid insulation
for rated voltages 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
|
Instrumentation, control
and communication circuits up to 60 V
|
60092-370
|
Electrical installations
in ships – Part 370: Guidance on the selection of cables for
telecommunication and data transfer including radio-frequency cables
|
Control and instrumentation
circuits up to 250 V
|
60092–376
|
Electrical installations in ships –
Part 376: Cables for control and instrumentation circuits 150/250 V (300
V)
|
Mineral insulated
|
60702 (all parts)
|
Mineral insulated cables and their terminations with a
rated voltage not exceeding 750 V
|
8.1.3 Details
of optical fibre cables for fixed installation are to be submitted
to assess compliance with applicable international or National Standards.
These are to include:
- Flame retardancy;
- Fire resistance (if applicable);
- Smoke density;
- Halogen content;
- Mechanical properties;
- Suitability for use in the marine environment.
8.1.4 Surveys of cables for electric propulsion systems during manufacture and
testing, see
Vol 2, Pt 9, Ch 1, 1.6 Surveys 1.6.3, are to assess compliance with the applicable
International, National or Naval Standards and the application of an acceptable quality
management system, see also
Vol 2, Pt 9, Ch 1, 1.6 Surveys 1.6.6.
8.1.5 Where
increased flexibility is required due to confines of space, cables
having Class 5 stranded conductors in accordance with IEC 60228 Conductors
of insulated cables may be accepted provided Vol 2, Pt 9, Ch 3, 8.1 General 8.1.2 is otherwise complied with.
Provided that the adequate flexibility of the finished cable is assured,
conductors of nominal cross-sectional area 2,5 mm2 and
less need not be stranded.
8.1.6 Electric
and optical fibre cables for non-fixed applications are to comply
with a relevant National or International Standard.
8.1.7 For
the purpose of this Section, pipes, conduits, trunking or any other
system for the additional mechanical protection of cables are hereinafter
referred to under the generic name ‘protective casings’.
8.1.8 Electrical
cables for telecommunications and data transfer are, whenever practicable,
to be selected in accordance with the recommendations of IEC TR 60092-370, Guidance on the selection of cables for telecommunication and data
transfer including radio-frequency cables.
8.2 Testing
8.2.1 Routine
tests, consisting of at least:
-
measurement of electrical resistance of conductors;
-
high voltage test, see also
Vol 2, Pt 9, Ch 12, 1.1 Testing 1.1.2;
-
insulation resistance measurement;
-
for high voltage cables, partial discharge tests are to be made in
accordance with the requirements of IEC 60885-2:Electrical test methods for
electric cables– Part 2: Partial discharge tests, or a relevant National
Standard, at the manufacturer’s works prior to despatch.
- for optical fibres, an attenuation loss (see
Vol 2, Pt 9, Ch 12, 1.5 Optical Fibre Communications Systems).
Evidence of successful completion of routine tests is to be
provided by the manufacturer, see also
Vol 2, Pt 9, Ch 1, 1.6 Surveys 1.6.3.
8.2.2 Particular,
special and type tests are to be made, when required, in accordance
with the requirements of the relevant publication or National Standard
referred to in Vol 2, Pt 9, Ch 3, 8.1 General 8.1.2, and
a test report issued by the manufacturer.
8.3 Voltage rating
8.3.1 The
rated voltage of any electric cable is to be not lower than the nominal
voltage of the circuit for which it is used. The maximum sustained
voltage of the circuit is not to exceed the maximum voltage for which
the cable has been designed.
8.3.2 Electric
cables used in unearthed systems are to be suitably rated to withstand
the additional stresses imposed on the insulation due to an earth
fault.
8.4 Operating temperature
8.4.1 The
maximum rated conductor temperature of the insulating material for
normal operation is to be at least 10ºC higher than the maximum
ambient temperature liable to be produced in the space where the cable
is installed.
8.4.2 The
maximum rated conductor temperatures for normal and short circuit
operation, for the insulating materials included within the standards
referred to in Vol 2, Pt 9, Ch 3, 8.1 General 8.1.2, is not
to exceed the values stated in Table 3.8.2 Maximum rated conductor
temperature
Table 3.8.2 Maximum rated conductor
temperature
Type of insulating compound
|
Maximum rated
conductor temperature, °C
|
Abbreviated designation
|
Abbreviated designation
|
Short-circuit
|
Elastomeric or
thermosetting, based upon:
|
|
|
|
Ethylene-propylene rubber or similar (EPM or
EPDM)
|
EPR
|
90
|
250
|
High modulus
or hard grade ethylene propylene rubber
|
HEPR
|
90
|
250
|
Cross-linked polyethylene
|
XLPE
|
90
|
250
|
Cross-linked polyolefin material for halogen-free cables
|
HF90
|
90
|
250
|
Silicone rubber
|
S95
|
95
|
350
|
8.5 Construction
8.5.1 Electric
and optical fibre cables are to be at least of a flame-retardant,
low smoke, halogen free type. Compliance with IEC 60332-1-2: Tests
on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulated
wire or cable - Procedure for 1kW pre-mixed flame, IEC 61034: Measurements of smoke density of electric cables burning under defined
conditions, IEC 60754: Tests on gases evolved during
combustion of materials from cables will be acceptable. Where
cables are installed in bunches, the requirements of Vol 2, Pt 9, Ch 3, 8.8 Installation of electric and optical fibre cables 8.8.13 are to be satisfied. Alternative
proposals for equipment cabling that demonstrate satisfactory smoke
and toxicity performance under fire conditions for identified areas
of a ship may be submitted for consideration.
8.5.2 Exemption
from the requirements of Vol 2, Pt 9, Ch 3, 8.5 Construction 8.5.1 for
applications such as radio frequency or digital communication systems,
which require the use of particular types of cable, will be subject
to special consideration.
8.5.3 Where
electric or optical fibre cables are required to be of a 'fire resistant
type', they are in addition to be easily distinguishable and comply
with the performance requirements of the appropriate part of IEC 60331: Tests for electric cables under fire conditions - Circuit integrity,
when tested with a minimum flame application time of 90 minutes, as
follows:
- IEC 60331-1: Tests for electric cables under fire conditions – Circuit integrity
– Part 1: Test method for fire with shock at a temperature of at least 830°C for
cables of rated voltage up to and including 0,6/1,0 kV and with an overall
diameter exceeding 20 mm;
- IEC 60331-2: Tests for electric cables under fire conditions – Circuit integrity
– Part 2: Test method for fire with shock at a temperature of at least 830 Degrees
C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall
diameter not exceeding 20 mm;
- IEC 60331-21: Tests for electric cables under fire conditions – Circuit integrity
– Part 21: Procedures and requirements - Cables of rated voltage up to and
including 0, 6/1, 0kV;;
- IEC 60331-23: Tests for electric cables under fire conditions – Circuit integrity
– Part 23: Procedures and requirements - Electric data cables; or;
- IEC 60331-25: Tests for electric cables under fire conditions – Circuit integrity
– Part 25: Procedures and requirements - Optical fibre cables..
8.5.4 Where
electric or optical fibre cables are installed in locations exposed
to the weather, in damp and in wet situations, in machinery compartments,
refrigerated spaces or exposed to harmful vapours including oil vapour,
they are to have the conductor insulating materials or optical fibres
enclosed in an impervious sheath of material appropriate to the expected
ambient conditions.
8.5.5 Where
electric or optical fibre cables are installed in locations which
are totally submerged for extended periods of time, they are to have
the conductor insulating materials or fibres enclosed in an impervious
sheath of material appropriate to the expected submerged conditions
and duration.
8.5.7 Where
cables are installed in an area where contamination by oil is likely
to occur, the oversheath is to be of an enhanced oil resistance grade.
8.5.8 Where
single core electric cables are used in circuits rated in excess of
20 Amps and are armoured, the armour is to be of a non-magnetic material.
8.5.9 Electric
cables are to be constructed such that they are capable of withstanding
the mechanical and thermal effects of the maximum short circuit current
which can flow in any part of the circuit in which they are installed,
taking into consideration not only the time/current characteristics
of the circuit protective device but also the peak value of the prospective
short circuit current. Where electric cables are to be used in circuits
with a maximum short circuit current in excess of 70 kA, evidence
is to be submitted for consideration when required demonstrating that
the cable construction can withstand the effects of the short circuit
current.
8.5.10 All
high voltage electric cables are to be readily identified by suitable
marking.
8.6 Conductor size
8.6.1 The
maximum continuous load carried by a cable is not to exceed its continuous
current rating. It is to be chosen such that the maximum rated conductor
temperature for normal operation for the insulation is not exceeded.
In assessing the current rating the correction factors in Vol 2, Pt 9, Ch 3, 8.7 Correction factors for cable current rating may be applied as required.
8.6.2 The
cross-sectional area of the conductors is to be sufficient to ensure
that, under short circuit conditions, the maximum rated conductor
temperature for short circuit operation is not exceeded, taking into
consideration the time current characteristics of the circuit protective
device and the peak value of the prospective short circuit current.
8.6.3 The
cable current ratings given in Table 3.8.3 Electric cable current ratings,
normal operation, based on ambient 45°C and Table 3.8.4 Electric cable current ratings,
r.m.s. short circuit current are
based on the maximum rated conductor temperatures given in Table 3.8.2 Maximum rated conductor
temperature. When cable sizes are
selected on the basis of precise evaluation of current rating based
upon experimental and calculated data, details are to be submitted
for consideration. Alternative short circuit temperature limits, other
than those given in Table 3.8.4 Electric cable current ratings,
r.m.s. short circuit current,
may be applied using the data provided in:
- IEC 60724:Short-circuit temperature limits of electric cables
with rated voltages of 1kV (Um=1,2kV) and 3kV (Um=3,6kV);or
- IEC 60986: Short-circuit temperature limits of electric
cables with rated voltages from 6kV (Um=7,2kV) and up to 30kV (Um=36kV).
Alternative short-circuit temperature limits provided in an
acceptable and relevant National Standard may also be considered.
Table 3.8.3 Electric cable current ratings,
normal operation, based on ambient 45°C
Nominal cross section (mm2)
|
Continuous r.m.s. current rating, in amperes
|
Elastomeric (90°C)
|
Elastomeric or thermosetting, based on silicone rubber
(95°C)
|
single core
|
2 core
|
3 or 4 core
|
single core
|
2 core
|
3 or 4 core
|
0,75
|
15
|
13
|
11
|
17
|
14
|
12
|
1
|
18
|
15
|
13
|
20
|
17
|
14
|
1,25
|
21
|
18
|
14
|
23
|
20
|
16
|
1,5
|
23
|
20
|
16
|
26
|
22
|
18
|
2
|
28
|
24
|
19
|
31
|
26
|
22
|
2,5
|
30
|
26
|
21
|
32
|
27
|
22
|
3,5
|
37
|
32
|
26
|
39
|
33
|
28
|
4
|
40
|
34
|
28
|
43
|
37
|
30
|
5,5
|
49
|
42
|
35
|
52
|
44
|
37
|
6
|
52
|
44
|
36
|
55
|
47
|
39
|
8
|
62
|
53
|
44
|
66
|
56
|
46
|
10
|
72
|
61
|
50
|
76
|
65
|
53
|
14
|
88
|
75
|
62
|
94
|
80
|
66
|
16
|
96
|
82
|
67
|
102
|
87
|
71
|
22
|
117
|
100
|
82
|
124
|
106
|
87
|
25
|
127
|
108
|
89
|
135
|
115
|
95
|
30
|
142
|
121
|
100
|
151
|
128
|
106
|
35
|
157
|
133
|
110
|
166
|
141
|
116
|
38
|
165
|
140
|
116
|
175
|
149
|
122
|
50
|
196
|
167
|
137
|
208
|
177
|
146
|
60
|
220
|
187
|
154
|
233
|
198
|
163
|
70
|
242
|
206
|
169
|
256
|
218
|
179
|
80
|
263
|
224
|
184
|
278
|
237
|
195
|
95
|
293
|
249
|
205
|
310
|
264
|
217
|
100
|
302
|
257
|
212
|
320
|
272
|
224
|
120
|
339
|
288
|
237
|
359
|
305
|
251
|
125
|
348
|
295
|
243
|
368
|
313
|
258
|
150
|
389
|
331
|
272
|
412
|
350
|
288
|
185
|
444
|
377
|
311
|
470
|
400
|
329
|
200
|
466
|
396
|
326
|
494
|
420
|
346
|
240
|
522
|
444
|
365
|
553
|
470
|
387
|
300
|
601
|
511
|
421
|
636
|
541
|
445
|
Table 3.8.4 Electric cable current ratings,
r.m.s. short circuit current
Nominal cross section (mm2)
|
Fault current (kA) at 250°C
|
Fault current (kA) at 350°C
|
1s duration
|
0,5s duration
|
0,1s duration
|
1s duration
|
0,5s
duration
|
0,1s duration
|
0,75
|
0,1
|
0,2
|
0,3
|
0,1
|
0,2
|
0,4
|
1
|
0,1
|
0,2
|
0,5
|
0,2
|
0,2
|
0,5
|
1,25
|
0,2
|
0,3
|
0,6
|
0,2
|
0,3
|
0,7
|
1,5
|
0,2
|
0,3
|
0,7
|
0,3
|
0,4
|
0,8
|
2
|
0,3
|
0,4
|
0,9
|
0,3
|
0,5
|
1,1
|
2,5
|
0,4
|
0,5
|
1,1
|
0,4
|
0,6
|
1,4
|
3,5
|
0,5
|
0,7
|
1,6
|
0,6
|
0,8
|
1,9
|
4
|
0,6
|
0,8
|
1,8
|
0,7
|
1,0
|
2,2
|
5,5
|
0,8
|
1,1
|
2,5
|
0,9
|
1,3
|
3,0
|
6
|
0,9
|
1,2
|
2,7
|
1,0
|
1,5
|
3,2
|
8
|
1,1
|
1,6
|
3,6
|
1,4
|
1,9
|
4,3
|
10
|
1,4
|
2,0
|
4,5
|
1,7
|
2,4
|
5,4
|
14
|
2,0
|
2,8
|
6,3
|
2,4
|
3,4
|
7,6
|
16
|
2,3
|
3,2
|
7,2
|
2,7
|
3,9
|
8,7
|
22
|
3,1
|
4,5
|
10,0
|
3,8
|
5,3
|
11,9
|
25
|
3,6
|
5,1
|
11,3
|
4,3
|
6,0
|
13,5
|
30
|
4,3
|
6,1
|
13,6
|
5,1
|
7,3
|
16,2
|
35
|
5,0
|
7,1
|
15,8
|
6,0
|
8,5
|
18,9
|
38
|
5,4
|
7,7
|
17,2
|
6,5
|
9,2
|
20,6
|
50
|
7,2
|
10,1
|
22,6
|
8,6
|
12,1
|
27,1
|
60
|
8,6
|
12,1
|
27,1
|
10,3
|
14,5
|
32,5
|
70
|
10,0
|
14,2
|
31,7
|
12,0
|
16,9
|
37,9
|
80
|
11,4
|
16,2
|
36,2
|
13,7
|
19,4
|
43,3
|
95
|
13,6
|
19,2
|
43,0
|
16,3
|
23,0
|
51,4
|
100
|
14,3
|
20,2
|
45,2
|
17,1
|
24,2
|
54,1
|
120
|
17,2
|
24,3
|
54,3
|
20,5
|
29,0
|
64,9
|
125
|
17,9
|
25,3
|
56,6
|
21,4
|
30,2
|
67,6
|
150
|
21,5
|
30,4
|
67,9
|
25,7
|
36,3
|
81,2
|
185
|
26,5
|
37,4
|
83,7
|
31,7
|
44,8
|
100,1
|
200
|
28,6
|
40,5
|
90,5
|
34,2
|
48,4
|
108,2
|
240
|
34,3
|
48,6
|
108,6
|
41,1
|
58,1
|
129,9
|
300
|
42,9
|
60,7
|
135,7
|
51,3
|
72,6
|
162,3
|
8.6.4 The
cross-sectional area of the conductors is to be sufficient to ensure
that at no point in the installation will the voltage variations stated
in Vol 2, Pt 9, Ch 1, 2.1 Quality of power supplies (QPS) be exceeded when
the conductors are carrying the maximum current under their normal
conditions of service.
8.6.6 The
cross sectional area of conductors used in circuits supplying cyclic
or non-continuous loads is to be sufficient to ensure that the cables
maximum rated conductor temperature for normal operation is not exceeded
when the conductors are operating under their normal conditions of
service, see
Vol 2, Pt 9, Ch 3, 8.7 Correction factors for cable current rating 8.7.4.
8.7 Correction factors for cable current rating
8.7.2
Bunching
of cables. Where more than six electric cables, which may be
expected to operate simultaneously at their full rated capacity, are
laid close together in a cable bunch in such a way that there is an
absence of free air circulation around them, a correction factor of
0,85 is to be applied. Signal cables may be exempted from this requirement.
8.7.3
Ambient
temperature. The current ratings of Table 3.8.3 Electric cable current ratings,
normal operation, based on ambient 45°C are based on an ambient
temperature of 45ºC. For other values of ambient temperature
the correction factors shown in Table 3.8.5 Correction factors are to be applied.
Table 3.8.5 Correction factors
Insulation material
|
Correction factor for ambient air temperature of °C
|
35
|
40
|
45
|
50
|
55
|
60
|
65
|
70
|
75
|
80
|
85
|
Elastomeric or thermosetting (90°C)
|
1,10
|
1,05
|
1,00
|
0,94
|
0,88
|
0,82
|
0,74
|
0,67
|
0,58
|
0,47
|
–
|
Elastomeric or thermosetting, based on silicone rubber (95°C)
|
1,10
|
1,05
|
1,00
|
0,95
|
0,89
|
0,84
|
0,77
|
0,71
|
0,63
|
0,55
|
0,45
|
8.7.4
Short
time duty. When the load is not continuous i.e. operates for
periods of half an hour or one hour and the periods of no load are
longer than three times the cable’s time constant, T,
in minutes, the cable’s continuous rating may be increased by
a duty factor, calculated in accordance with:
When the load is not continuous, is repetitive and
has periods of no-load less than three times the cable’s time
constant, so that the cable has insufficient time to cool down between
the applications of load, the cable’s continuous rating may
be increased by an intermittent factor, calculated in accordance with:
where
t
p
|
= |
the intermittent period, in minutes, i.e. the total period of
load and no-load before the cycle is repeated |
T
|
= |
0,245d
1,35 where d is the overall diameter
of the cable, in mm
|
t
s
|
= |
the service time of the load current in minutes |
8.8 Installation of electric and optical fibre
cables
8.8.1 Electric
and optical fibre cable runs are to be, as far as practicable, fixed
in straight lines and in accessible positions.
8.8.2 Bends
in fixed electric and optical fibre cable runs are to be in accordance
with the cable manufacturer’s recommendations. The minimum internal
radius of bend for the installation of fixed electric cables is to
be chosen according to the construction and size of the cable and
is not to be less than the values given in Table 3.8.6 Minimum internal radii of bends in
cables for fixed wiring
Table 3.8.6 Minimum internal radii of bends in
cables for fixed wiring
Cable construction
|
Overall diameter of
cable
|
Minimum internal radius
of bend (times overall diameter of cable)
|
Insulation
|
Outer
covering
|
Elastomeric 600/1000 V
and below
|
Metal
sheathed Armoured and braided
|
Any
|
6D
|
Other
finishes
|
≤ 25
mm
> 25 mm
|
4D
6D
|
Mineral
|
Hard
metal sheathed
|
Any
|
6D
|
Elastomeric above
600/1000 V
|
|
|
|
– single
core
|
Any
|
Any
|
|
– multicore
|
Any
|
Any
|
12D
|
8.8.3 The manufacturer’s tensile load limit of the optical fibre is not to be exceeded during
installation.
8.8.4 The manufacturer’s minimum bend radii for optical fibres is not to be exceeded during
installation.
8.8.6 The
installation of electric and optical fibre cables across expansion
joints in any structure is to be avoided. Where this is not practicable,
a loop of electric cable of length sufficient to accommodate the expansion
of the joint is to be provided. For electric cables, the internal
radius of the loop is to be at least 12 times the external diameter
of the cable. For optical fibre cables, the internal radius of the
loop is to meet the manufacturers’ minimum recommendations.
8.8.7 Electric and optical fibre cables for Mobility systems, Ship Type systems,
and emergency services are to be arranged, so far as is practicable, to avoid galleys,
machinery spaces and other enclosed spaces and areas of high fire risk except as is
necessary for the service being supplied. Such cables are also, so far as reasonably
practicable, to be routed clear of bulkheads to preclude them being rendered
unserviceable by heating of the bulkheads that may be caused by a fire in an adjacent
space.
8.8.8 Electric
and optical fibre cables having insulating materials with different
maximum rated conductor temperatures are to be so installed that the
maximum rated conductor temperature for normal operation of each cable
is not exceeded.
8.8.9 Electric
and optical fibre cables having a protective covering which may damage
the covering of other cables are not to be bunched with those other
cables.
8.8.10 Cables
having an exposed metallic screen, braid or armour are to be installed
in such a manner that galvanic corrosion by contact with other metals
is prevented. Sufficient measures are also to be taken to prevent
damage to exposed galvanised coatings during installation.
8.8.11 Protection
is to be provided for cable oversheaths in areas where cables are
likely to be exposed to damaging substances under normal circumstances
or areas where the spillage or release of harmful substances is likely.
8.8.12 Electric
and optical fibre cables are to be, as far as practicable, installed
remote from sources of heat. Where installation of cables near sources
of heat cannot be avoided and where there is consequently a risk of
damage to the cables by heat, suitable shields, insulation or other
precautions are to be installed between the cables and the heat source.
The free air circulation around the cables is not to be impaired.
8.8.13 Where
cables are installed in bunches, provision is to be made to limit
the propagation of fire. This requirement is considered satisfied
when cables of the bunch have been tested in accordance with the requirements
of IEC 60332-3-22:Tests on electric and optical fibre cables
under fire conditions, Part 3-22, Test for vertical flame spread of
vertically mounted bunched wires or cables - Category A, provided
that, in addition, there is no shedding of flaming droplets of sheath
or insulation material and that they are installed in the same configuration(s)
as used in the test(s). If the cables are not so installed, information
is to be submitted in satisfactorily demonstrate that suitable measures
are taken to ensure that an equivalent limit of fire propagation will
be achieved for the configuration(s) used. Particular attention is
to be given to cables in vertical runs in trunks and other restricted
spaces. In addition, cables that comply with the requirements of IEC
60332-3-22 are also required to meet the requirements of IEC 60332-1-2: Tests on electric and optical fibre cables under fire conditions –
Part 1-2: Test for vertical flame propagation for a single insulated
wire or cable – Procedure for 1 kW pre-mixed flame.
8.8.14 Electric
and optical fibre cables are not to be coated or painted with materials
which may adversely affect their sheath or their fire performance.
8.8.15 Where
electric and optical fibre cables are installed in refrigerated spaces,
they are not to be covered with thermal insulation but may be placed
directly on the face of the refrigeration chamber, provided that precautions
are taken to prevent the electric cables being used as casual means
of suspension.
8.8.17 High
voltage cables may be installed as follows:
-
in the open,
e.g. on carrier plating, when they are to be provided with a continuous
metallic sheath or armour which is effectively bonded to earth to
reduce danger to personnel. The metallic sheath or armour may be omitted
provided that the cable sheathing material has a longitudinal electric
resistance high enough to prevent sheath currents which may be hazardous
to personnel;
-
contained in
earthed metallic protective casings when the cables may be as in (a)
or the armour or metal sheath may be omitted. In the latter case care
is to be taken to ensure that protective casings are electrically
continuous and that short lengths of cable are not left unprotected.
8.8.18 High
voltage electric cables are not to be run in the open through accommodation
spaces.
8.8.19 High-voltage
electric cables are to be segregated from electric cables operating
at lower voltages.
8.8.20 Electric
and optical fibre cables are to be, so far as reasonably practicable,
installed remote from sources of mechanical damage. Where necessary,
the cables are to be protected in accordance with the requirements
of Vol 2, Pt 9, Ch 3, 8.9 Mechanical protection of cables
8.8.21 Electric
and optical fibre cables, with the exception of those for portable
appliances and those installed in protective casings, are to be fixed
securely in accordance with the requirements of Vol 2, Pt 9, Ch 3, 8.10 Cable support systems
8.8.22 Electric and optical fibre cables serving any Mobility or Ship Type system,
and any glands through which they pass must be able to withstand flooding for a period
of 18 hours, based on the water pressure that may occur at the location.
8.9 Mechanical protection of cables
8.9.1 Electric
or optical fibre cables exposed to risk of mechanical damage are to
be protected by suitable protective casings unless the protective
covering (e.g. armour or sheath) is sufficient to withstand the possible
cause of damage.
8.9.2 Electric
or optical fibre cables installed in spaces where there is exceptional
risk of mechanical damage such as hangers, storage spaces, etc. are
to be suitably protected by metallic protective casings, even when
armoured, unless the ship’s structure affords adequate protection.
8.10 Cable support systems
8.10.2 Cable
support systems, which may be in the form of trays or plates, separate
support brackets, hangers or ladder racks, together with their fixings
and accessories, are to be robust and are to be of corrosion-resistant
material or suitably corrosion inhibited before erection. The cable
support system is to be effectively secured to the ships’ structure,
the spacing of the fixings taking account of the probability of vibration
and any heavy external forces, e.g. where located in areas subject
to impact by sea-water. In addition, where applicable, military aspects
for shock are to be defined as required by Vol 2, Pt 1, Ch 3, 4.8 Astern power
8.10.3 The
distances between the points at which the cable is supported (e.g.
distances between ladder rungs, support brackets, hangers, etc.) are
to be chosen according to the construction of cable (i.e. size and
rigidity) and the probability of vibration and are to be generally
in accordance with those given in Table 3.8.7 Maximum spacing of supports or
fixings for securing cables
Table 3.8.7 Maximum spacing of supports or
fixings for securing cables
External diameter of cable
|
Non-armoured cables
|
Armoured cables
|
exceeding
|
not
exceeding
|
mm
|
mm
|
mm
|
mm
|
—
|
8
|
200
|
250
|
8
|
13
|
250
|
300
|
13
|
20
|
300
|
350
|
20
|
30
|
350
|
400
|
30
|
—
|
400
|
450
|
8.10.4 Where
the cables are laid on top of their support system, the spacing of
the clips, straps, etc. securing the cables may be increased beyond
the spacing given in Table 3.8.7 Maximum spacing of supports or
fixings for securing cables,
but should take account of movement and vibration and in general is
not to exceed 900 mm. This relaxation is not to be applied where cables
can be subjected to heavy external forces, e.g. where they are run
on, or above, open deck or in areas subject to sea-water impingement.
8.10.5 Single
core electric cables are to be firmly fixed, using supports of strength
adequate to withstand forces corresponding to the values of the peak
prospective short circuit current.
8.11 Penetration of bulkheads and decks by cables
8.11.1 Where
electric or optical fibre cables pass through watertight, fire insulated
or gastight bulkheads or decks separating hazardous zones or spaces
from non-hazardous zones or spaces, the arrangements are to be such
as to ensure the integrity of the bulkhead or deck is not impaired.
The arrangements chosen are to ensure that the cables are not adversely
affected.
8.11.2 Where
cables pass through non-watertight bulkheads or structural steel,
the holes are to be bushed with suitable material. If the steel is
at least 6 mm thick, adequately rounded edges may be accepted as the
equivalent of bushing.
8.11.3 Electric
and optical fibre cables passing through decks are to be protected
by deck tubes or ducts.
8.11.4 Where
cables pass through thermal insulation they are to do so at right
angles, in tubes sealed at both ends.
8.12 Installation of electric and optical fibre cables in protective
casings
8.12.1 Protective
casings are to be mechanically continuous across joints and effectively
supported and secured to prevent damage to the electric or optical
fibre cables.
8.12.2 Protective
casings are to be suitably smooth on the interior and have their ends
shaped or bushed in such a manner as not to damage the cables.
8.12.4 The
space factor (ratio of the sum of the cross sectional areas corresponding
to the external diameters of the cables to the internal cross sectional
area of the protective casings) is not to exceed 0,4.
8.12.5 Where
necessary, ventilation openings are to be provided at the highest
and lowest points of protective casings to permit air circulation
and to prevent accumulation of water.
8.12.6 Expansion
joints are to be provided in protective casings where necessary.
8.12.7 Protective
casings containing high voltage electric cables are not to contain
other electric or optical fibre cables and are to be clearly identified,
defining their function and voltage.
8.13 Non-metallic cable support systems, protective casings and fixings
8.13.2 Non-metallic
cable support systems and protective casings are to be installed in
accordance with the manufacturer’s recommendations. The support
systems and protective casings are to have been tested in accordance
with an acceptable test procedure for:
-
ambient operating
temperatures;
-
safe working
load;
-
impact resistance;
-
flame retardancy;
-
smoke and toxicity;
and
-
use in explosive
gas atmospheres or in the presence of combustible dusts, electrical
conductivity;
with satisfactory results.
8.13.3 Non-metallic
cable support systems, protective casings and fixings installed on
the open deck are to be protected from degradation caused by exposure
to solar radiation.
8.13.4 Where
the cable support system, protective casing or fixings are manufactured
from a material other than metal, suitable supplementary metallic
fixings or straps spaced at regular distances are to be provided such
that, in the event of a fire or failure, the cable support system,
protective casing and the affixed cables are prevented from falling
and causing an injury to personnel and/or an obstruction to any escape
route. Alternatively, the cables may be routed away from such areas.
8.13.5 The
load on non-metallic cable support systems or protective casings is
not to exceed the tested safe working load.
8.13.6 When
a cable support system or protective casing is secured by means of
clips or straps manufactured from a material other than metal, the
fixings are to be supplemented by suitable metal clips or straps spaced
at regular distances each not exceeding 2 m and, for non metallic
cable support systems or protective casings, that used during safe
working load testing.
8.13.7 Non-metallic
fixings are to be flame retardant in accordance with the requirements
of IEC 60092- 101: Electrical installations in ships –
Part 101: Definitions and general requirements, or an alternative,
relevant National or International Standard.
8.14 Single core electric cables for alternating current
8.14.1 When
installed in protective casings, electric cables belonging to the
same circuit are to be installed in the same casing, unless the casing
is of non-magnetic material.
8.14.2 Cable
clips are to include electric cables of all phases of a circuit unless
the clips are of non-magnetic material.
8.14.3 Single-core
cables of the same circuit are to be in contact with one another,
as far as possible. In any event the distance between adjacent electric
cables is not to be greater than one cable diameter.
8.14.4 If
single-core cables of current rating greater than 250 A are installed
near a steel bulkhead, the clearance between the cables and the bulkhead
is to be at least 50 mm unless the cables belonging to the same a.c.
circuit are installed in trefoil formation.
8.14.5 Magnetic
material is not to be used between single core cables of a group.
Where cables pass through steel plates, all the conductors of the
same circuit are to pass through a plate or gland, so made that there
is no magnetic material between the cables, and the clearance between
the cables and the magnetic material is not to be less than 75 mm,
unless the cables belonging to the same a.c. circuit are installed
in trefoil formation.
8.14.6 Electric
cables are to be installed such that the induced voltages, and any
circulating currents, in the sheath or armour are limited to safe
values.
8.15 Electric cable ends
8.15.1 Where
screw-clamp or spring-clamp type terminations are used in electrical
apparatus for external cable connections (see
Vol 2, Pt 9, Ch 1, 2.2 Design, construction and location 2.2.14), cable conductors
of the solid or stranded type may be inserted directly into the terminals.
Where flexible conductors are used, a suitable termination is to be
fitted to the cable conductor to prevent ‘whiskering’
of the strands.
8.15.2 If
compression type conductor terminations are used on the cable ends,
they are to be of a size to match the conductor and to be made with
a compression type tool with the dies selected to suit the termination
and conductor sizes and having a ratchet action to ensure completion
of the compression action.
8.15.3 Soldered
sockets may be used in conjunction with non-corrosive fluxes provided
that the maximum conductor temperature at the joint, under short circuit
conditions, does not exceed 160ºC.
8.15.4 High
voltage cables of the radial field type, i.e. having a conducting
layer to control the electric field within the insulation, are to
have terminations which provide electrical stress control.
8.15.5 Electric
cables having hygroscopic insulation (e.g. mineral insulated) are
to have their ends sealed against ingress of moisture.
8.15.6 Cable
terminations are to be of such a design and dimensions that the maximum
current likely to flow through them will not result in degradation
of the contacts or damage to insulation as the result of overheating
or corrosion.
8.15.7 The
fixing of conductors in terminals at joints and at tappings is to
be capable of withstanding the thermal and mechanical effects of short
circuit currents.
8.15.8 Cable
terminations are to be suitable for the operating voltages and currents
and may be of the screw-clamp or spring-clamp type or plug and socket
connectors.
8.16 Joints and branch circuits in cable systems
8.16.1 If
a joint is necessary it is to be carried out so that all conductors
or fibres are adequately secured, insulated and protected from atmospheric
action. The flame retardant properties or fire-resisting properties
of the cable are to be retained, the continuity of metallic sheath,
braid or armour is to be maintained and the current-carrying capacity
or transmission of data through the cable is not to be impaired.
8.16.2 Tappings
(branch circuits) are to be made in suitable boxes of such a design
that the conductors remain suitably insulated, protected from atmospheric
action and fitted with terminals or busbars of dimensions appropriate
to the current rating.
8.16.3 Tappings
and splices of optical fibre cables are to be made in accordance with
the manufacturers’ recommendations and are to be provided with
appropriate fittings. In addition they are to be located within suitably
designed enclosures to ensure that the protection of the optical fibres
is maintained.
8.17 Busbar trunking systems (bustrunks)
8.17.2 The
busbar trunking, or enclosure system, is to have a minimum ingress
protection of IP54, according to IEC60529: Degrees of protection
provided by enclosures (IP Code).
8.17.3 The
internal and external arrangements of the busbar trunking, or enclosure
system, are to ensure that the fire and/or watertight integrity of
any structure through which it passes is not impaired.
8.17.5 Supports
and accessories are to be robust and are to be of corrosion-resistant
material or suitably corrosion inhibited before erection. The support
system is to effectively secure the busbar trunking system to the
ship’s structure.
8.17.6 When
accessories are fixed to the busbar system by means of clips or straps
manufactured from a material other than metal, the fixings are to
be supplemented by suitable metal clips or straps, such that, in the
event of a fire or failure, the accessories are prevented from falling
and causing injury to personnel and/or an obstruction to any escape
route. Alternatively, the busbar system may be routed away from such
areas.
8.18 Cable segregation
8.18.1 To
reduce mutual interference, cables with different signal levels are
to be grouped in accordance with Table 3.8.8 Cable segregation groups and installed with the separation distances as shown
in Table 3.8.9 Separation distances, mm
Table 3.8.8 Cable segregation groups
Criteria
|
Signal level
|
Group
|
Application
|
LF/DC
|
HF
Pulse
|
Very
sensitive
|
1
mV
|
1
μV
|
A
|
Receiver antenna cables Television antenna cables
(RX) Infrared receiver cables Sonar/sounder
receiver cables Radio MF receiver cables Radar
MF receiver cables Dynamic microphone
input Servo amplifier input (asymmetric and high
impedance)
|
Sensitive
|
100 mV
|
10 μV
|
B
|
Voltage, frequency
and phase dependent signal cables Reference voltage and
synchro system cables (400/1100Hz) Servo amplifier input
cables (symmetric) Analogue and digital cables (symmetric and
low voltage signal) M and P lines, sound powered telephone
cables
|
Low sensitivity,
low interference
|
24 V
|
10 μV
|
C
|
Power supply
cables High power cables Telephone, telex,
loudspeaker and signal key cables Press to talk
cables Start/stop signalling cables
|
Interference
|
440 V
|
3 V
|
D
|
Synchronisation
cables Video cables Strobe
cables Marker cables Pulse cables (low
power) Control cables from wide band
amplifiers Digital signal cables (low level or asymmetrical
and high level) High power synchro cables
|
High
interference
|
440 V
|
30 V
|
E
|
Transmit antenna
cables Main electromotor cables Modulator
pulsed cables Pulse cables for high power Echo
sounder transmit and receiver cables
|
Very sensitive
with high interference
|
1000 V
|
1000 V
|
F
|
Radio transmit and
receive cables Transducer cables Echo sounder
transmit and receiver cables
|
Immune, no
interference
|
Z
|
Fibre optic cables
|
Table 3.8.9 Separation distances, mm
Group
|
A
|
B
|
C
|
D
|
E
|
F
|
A
|
—
|
50
|
100
|
150
|
200
|
200
|
B
|
50
|
—
|
50
|
100
|
150
|
100
|
C
|
100
|
50
|
—
|
50
|
100
|
100
|
D
|
150
|
100
|
50
|
—
|
50
|
100
|
E
|
200
|
150
|
100
|
50
|
—
|
200
|
F
|
200
|
100
|
100
|
100
|
200
|
—
|
|