Section
2 Construction and installation
2.1 Materials
2.1.1 The
selection of materials for piping systems in provision store refrigeration
systems is to take account of the following:
-
The pressures
and temperatures of the refrigerant fluids.
-
Locations of
systems and equipment.
-
Compatibility
of materials.
-
Fluid flow rates
and static pressure conditions.
-
Minimising corrosion
and erosion through life of system.
-
Refrigerant flammability
and toxicity.
2.1.2 Pipes,
valves and fittings are in general to be made of steel, ductile cast
iron, copper, copper alloy, or other approved ductile material suitable
for the intended purpose. The use of plastics materials is also acceptable
subject to the restrictions in Pt 5, Ch 12, 5 Plastic pipes.
2.2 Equipment – Selection and installation
2.2.3 Pipes
in piping systems are to be permanent pipes made with approved pipe
connections to enable ready removal of valves, pumps, fittings and
equipment. The pipes are to be efficiently secured in position to
prevent chafing or lateral movement.
2.2.4 Suitable
means for expansion are to be made, where necessary, in each range
of pipes.
2.2.5 Suitable
protection is to be provided for all pipes and equipment situated
where they are liable to mechanical damage.
2.2.6 All
moving parts are to be provided with guards to minimise danger to
personnel.
2.3 Valves and relief devices
2.3.1 Valves
are to be fitted in places where they are readily accessible at all
times.
2.3.2 Relief
valves are to be adjusted and bursting discs so selected that they
relieve at a pressure not greater than the design pressure of the
system. When satisfactorily adjusted, relief valves are to be protected
against tampering or interference by a locking wire with a lead seal
or similar arrangement, see also
Pt 7, Ch 15, 2.4 Refrigerant systems 2.4.4.
2.4 Refrigerant systems
2.4.1 The
primary refrigerants ammonia, hydrocarbons or carbon dioxide shall
not be used in direct expansion FCUs located in accommodation spaces.
The use of these refrigerants in machinery spaces, such as a separate
AHU compartment, may be accepted subject to suitable safety arrangements
being provided to the satisfaction of Clasifications Register (hereinafter
referred to as LR).
2.4.3 The
design of refrigeration systems is to permit maintenance and repair
without unavoidable loss of refrigerant to atmosphere. To minimise
refrigerant release to the atmosphere, refrigerant recovery units
are to be provided to allow evacuation of a system prior to maintenance.
2.4.4 Refrigeration
systems are to be provided with relief devices which are arranged
with sufficient margins to avoid circumstances that would allow an
inadvertent discharge of refrigerant to the atmosphere. The system
is to be so designed that overpressure due to fire conditions can
be safely relieved.
2.4.5 A pressure
relief valve and/or bursting disc is to be fitted between each positive
displacement compressor and its gas delivery stop valve, the discharge
being led to the suction side of the compressor. The refrigerant flow
capacity of the valve or disc is to exceed the full load compressor
capacity for the particular refrigerant at the maximum potential suction
pressure. For these internal relief valves, servo-operated valves
will be accepted. Where the motive power for the compressor does not
exceed 10 kW, the pressure relief valve and/or bursting disc may be
omitted.
2.4.6 Each
pressure vessel which may contain liquid refrigerant and which is
capable of being isolated by means of a stop or automatic control
or check valve is to be protected by two pressure relief valves or
two bursting discs, or one of each, controlled by a changeover device.
Pressure vessels that are connected by pipework without valves, so
that they cannot be isolated from each other, may be regarded as a
single pressure vessel for this purpose, provided that the interconnecting
pipework does not prevent effective venting of any pressure vessel.
2.4.7 Omission
of one of the specified relief devices and changeover device, as required
by Pt 7, Ch 15, 2.4 Refrigerant systems 2.4.6, will be accepted
where:
-
vessels are of
less than 300 litres internal gross volume; or
-
vessels discharge
into the low pressure side of the system by means of a relief valve.
2.4.8 Sections
of systems and components that could become full of liquid between
closed valves are to be provided with pressure relief devices relieving
to a suitable point in the refrigerant circuit.
2.4.9 Where
any hermetic or semi-hermetic compressor has the electric motor cooled
by the circulating refrigerant, the following arrangements are to
be provided:
-
Refrigeration
circuits are to contain no more than one hermetic or semi-hermetic
compressors.
-
Each compressor
motor is to be fitted with a thermal cutout device to protect the
motor against overheating.
-
Each refrigerant
circuit is to contain a suitable arrangement to allow debris or contaminants
from a motor failure to be removed.
-
The pressure
envelope of any hermetic or semi-hermetic compressor exposed to the
refrigerant pressure is to be designed and constructed in accordance
with the requirements of Pt 5, Ch 11 Other Pressure Vessels and Pt 5, Ch 17 Requirements for Fusion Welding of Pressure Vessels and Piping as applicable. Plans are
to be submitted for consideration as required by Pt 5, Ch 11, 1.6 Plans.
2.5 Air handling unit(s) (AHUs) for air-conditioning systems
2.5.1 Evaporator
coils as fitted to direct expansion AHUs are to be considered for
approval and plans are to be submitted, see also
Pt 7, Ch 15, 1.2 Plans and information 1.2.2. All other equipment fitted
to an AHU, such as air filtration, dehumidification, heating and humidification
systems are outside the scope of these Rules and are the responsibility
of the Shipyard and Owner.
2.5.2 Each
AHU is to be provided with suitable drip trays and drainage arrangements
to remove any condensate which may form.
2.5.3 The
installation arrangements of AHUs are to be such as to allow sufficient
space for the withdrawal and replacement of the refrigerant cooling
coil.
2.6 Air coolers and cooling grids for provision store refrigeration
systems
2.6.1 Air
cooler fan motors are to be suitably enclosed to withstand the effects
of moisture.
2.6.2 Means
are to be provided for effectively defrosting air coolers. Air coolers
are to be provided with trays of suitable depth arranged to collect
all condensate. The trays are to be provided with drains at their
lowest points to enable the condensate to be drained away when the
refrigerated spaces are in service. When a store operates at temperatures
at, or lower than 0°C, provision is to be made for the prevention
of freezing of the condensate.
2.6.3 The
installation arrangements of air coolers are to be such that when
the refrigerated spaces are loaded with provisions, adequate space
is provided for the inspection, servicing and renewal of controls,
valves, fans and fan motors.
2.6.4 Steel
air cooler circuits and cooling grids are to be suitably protected
against external corrosion.
2.7 Design pressures
2.7.2 The
maximum working pressure is the maximum permissible pressure within
the system (or part system) in operation or at rest. No pressure relief
valve or other protective device is to be set to a pressure higher
than the maximum working pressure.
2.7.3 The
design pressure of the low pressure side of the system is to be the
saturated vapour pressure of the refrigerant at plus 46°C. Due
regard is to be taken of defrosting arrangements which may cause a
higher pressure to be imposed on the low pressure side of the system.
For carbon dioxide design pressures, see
Pt 7, Ch 15, 2.7 Design pressures 2.7.6.
2.7.4 The
minimum design pressure of the high pressure side of the system (P
dh), is to be determined from 1,11 × P
b,
where P
b is an allowance for the compressor
high pressure cut-out. P
b is to be not less
than to 1,11 × P
a, where P
a is the condenser working pressure, when operating in tropical
zones and equates to the saturation pressure of the refrigerant at
plus 46°C.
2.7.5 Design
pressures applicable to refrigerants are to be not less than the values
given in Table 15.2.1 Design pressure limits when
condensers are sea-water cooled. The design pressure for other refrigerants
and condensing arrangements is to be agreed with LR.
Table 15.2.1 Design pressure limits
Refrigerant
|
Pressure, (MPa)
|
High
|
Low
|
R-717
|
|
1,72
|
R-22
|
2,06
|
1,67
|
R-290
|
1,81
|
1,47
|
R-600a
|
0,64
|
0,52
|
R-134a
|
1,34
|
1,09
|
R-407C
|
2,35
|
1,9
|
R-410A
|
3,45
|
2,8
|
R-507A
|
2,53
|
2,05
|
R-404A
|
2,48
|
2,01
|
R-744
|
See
Pt 7, Ch 15, 2.7 Design pressures 2.7.6
|
Note In view of increasing world-wide restrictive legislation
and phasing out of the HCFC refrigerant R-22, it is recommended that
this refrigerant should not be used in new installations.
|
2.7.6 The
proposed design pressure for a carbon dioxide system is to be stated,
taking account of the maximum working pressure and the maximum pressure
at rest conditions. Where the maximum pressure at rest condition is
maintained by the fitting of a supplementary refrigeration unit, condensing
the vapour in a holding vessel, supporting calculation is to be provided
to show that this can be undertaken with a local ambient temperature
of 45°C. The holding vessel is to be thermally insulated to prevent
the operation of the relief devices within a 24 hour period after
stopping the supplementary refrigeration unit at an ambient temperature
of 45°C and an initial pressure equal to the starting pressure
of the refrigeration unit.
2.7.7 Where
a carbon dioxide system is designed for hot gas defrosting, due regard
is to be given to the possibility of a higher pressure being imposed
on the low pressure system. The design pressure for the hot gas defrosting
section of the system is to be 10 per cent greater than the maximum
pressure experienced during defrosting.
2.8 Insulation materials
2.8.1 Where
applicable, having regard to their location and environmental conditions,
insulation arrangements are to have:
-
materials suitably
resistant to fire;
-
insulation lining
suitably resistant to flame spread;
-
effective protection
against penetration of water vapour; and
-
adequate protection
against mechanical damage.
2.8.3 Where
the in situ foam type of insulation is proposed, full
details of the process are to be submitted.
2.8.4 Prefabricated
panel systems are to be fitted with suitable pressure equalising devices.
2.9 Manufacture and certification
2.9.2 Other
equipment, apart from applicable pressure vessels and heat exchangers,
used for air-conditioning or provision stores refrigeration systems
are not required to be constructed under survey.
2.9.3 All
major items of equipment, containing refrigerant, such as compressors,
condensers, AHU cooling coils and FCUs shall be supplied with a manufacturer’s
works certificate providing details of the design and test pressures.
|