Section
1 General requirements
1.1 General
1.1.3 The
refrigeration system is to include the refrigeration compressor(s),
condenser(s), evaporator(s), direct expansion air handling and fan
coil units, interconnecting primary refrigerant piping system and
fittings.
Note For the purpose of these Rules, the term primary refrigerant
system, unless otherwise stated, applies to primary refrigerant systems
and secondary refrigerant systems containing volatile refrigerants.
1.1.4 These
requirements are intended to mitigate risks associated with the safety
of refrigeration and air-conditioning machinery, and do not cover
air distribution ductwork, chilled water systems or the calculation
and verification of air flow rates and cooling loads within the air
conditioned or refrigerated spaces. The method used to calculate the
capacity of the air-conditioning refrigeration equipment is the responsibility
of the Shipbuilder and Owner and should be in accordance with a recognised
code or standard such as ISO 7547:2002 Ships and marine technology
– Air-conditioning and ventilation of accommodation spaces –
Design conditions and basis of calculations or, ASHRAE 26-1996(RA2006) Mechanical Refrigeration and Air-Conditioning Installations Aboard
Ship.
1.1.5 Ships
complying with the applicable requirements of this Chapter will be
eligible for the optional machinery class notation RPA (Refrigeration
Machinery for Provision Stores and Air-conditioning).
1.2 Plans and information
1.2.1 The
following plans and particulars, as applicable, and any others which
may be specially requested for the refrigerating plant and systems,
are to be submitted in triplicate for approval, before construction
is commenced:
-
Schematic plans,
including full particulars of piping and instrumentations, for:
-
primary and
secondary refrigerant systems containing a volatile fluid;
-
air cooler
defrosting arrangements; and
-
condenser
cooling water systems.
-
Detailed dimensioned
plans and material specifications for:
-
reciprocating
compressor crankshaft and crankcase, where exposed to refrigerant
pressure;
-
rotary-type
compressor rotors and casing;
-
condensers,
both shell and tube, and plate type;
-
evaporators,
both shell and tube, and plate type;
-
air coolers
or arrangement of air cooling pipe grids and construction method;
-
liquid receivers;
-
oil separators;
and
-
any other
pressure vessels or heat exchangers containing primary refrigerants, see
Pt 5, Ch 11, 6.1 General.
-
General arrangement
of refrigerating machinery compartments in elevation and plan, showing
location and arrangement of the plant, ventilation details and location
of temperature sensors and refrigerant vapour detectors.
-
Details of automatic
controls, alarms and safety systems, see
Pt 6, Ch 1, 1 General requirements.
-
Details of primary
refrigerant level indicators.
-
Capacity calculations
for pressure relief valves and/or bursting discs, and inlet and discharge
pipework pressure drop calculations.
-
Programme of
tests to be conducted on completion of the installation, see
Pt 7, Ch 15, 7 Testing and trials.
1.2.2 In
addition to the applicable requirements detailed in Pt 7, Ch 15, 1.2 Plans and information 1.2.1, the following information
is also to be submitted for air-conditioning refrigeration equipment:
-
Details of direct
expansion fan coil units (FCUs).
-
Details of cooling
coils, fitted to air handling units (AHUs) that contain primary refrigerant.
-
General arrangement
drawing showing the location of the air-conditioning refrigeration
equipment, direct expansion FCUs and AHUs throughout the ship.
-
Details of pressure
testing procedures for the refrigeration equipment.
1.2.3 Plans
showing the general arrangement of refrigeration plant compartments,
together with a description of the equipment and arrangements installed
for isolation and distribution of ventilation air and the electrical
power supply systems. The plans are to indicate segregation and access
arrangements for compartments and associated control rooms and control
stations.
1.2.4 A statement
of the intended design system capacity for the intended operating
conditions for verification purposes at the trials required by Pt 7, Ch 15, 7.2 Trials 7.2.1.
1.2.6 Operating
manuals are to be submitted for information. The manuals are to include
the following information:
-
Particulars and
a description of the systems.
-
Operating instructions
for the equipment and systems.
-
Maintenance instructions
for the installed arrangements.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
 |
|