4.1.1 A fixed
refrigerant detection system is to be provided in the refrigerating
machinery compartment or space and ventilation outlet ducts when the
ventilation system is shared with other compartments.
4.1.2 The
alarm system is to comply with the requirements of Pt 6, Ch 1 Control Engineering Systems and, as a minimum requirement,
the system is to activate at a low-level concentration to give warning
of refrigerant leaks, and at a high-level concentration corresponding
to the refrigerant’s safe occupational level.
4.1.3 Detection
equipment is to be so designed that it may be readily tested and calibrated;
any failure of the equipment is to initiate an alarm.
4.1.4 The
location of the detectors is to be determined relative to the layouts
of the individual compartments and machinery spaces and are to be
indicated in the plan submission.
4.1.5 Audible
and visual alarms are to be activated, located both inside and outside
the affected space. The alarms are to be readily identifiable and
be visible and audible in all locations within the space housing the
refrigeration equipment.