Section
4 Refrigerant charge limits, machinery room, and storage arrangements
4.1 Refrigerant classification
4.1.1 The design of the system and safety arrangements are to be implemented
based on the class of refrigerant selected for use in the system. The refrigerant
classification scheme, ISO 817 Refrigerants — Designation and safety
classification, is to be considered regarding the flammability and toxicity
class of the refrigerant. Flammable (Class 2L, 2, and 3) and toxic (Class B)
refrigerants are not to be used in systems designed for non-flammable, non-toxic
refrigerants.
4.1.2 The ‘practical limit’ of a refrigerant represents the highest acceptable
concentration level of refrigerant in an occupied space which will not result in any
impairment of crew (i.e. acute effects) or create a risk of ignition of the
refrigerant. Values for the practical limit for different refrigerants are listed in
ISO 5149-1 Refrigerating systems and heat pumps — Safety and environmental
requirements.
4.2 Refrigerating machinery in accommodation spaces
4.2.1 In accommodation spaces the amount of refrigerant charge is to be restricted to the
practical limit.
4.2.2 Accommodation spaces containing refrigerating machinery are to be provided with
natural or mechanical ventilation and suitable clearance for ventilation is to be
retained around the refrigerating machinery.
4.3 Refrigerating machinery in machinery spaces
4.4 Charge limits due to flammability
4.4.1 There is no restriction due to flammability on the charge size of
flammability Class 1 refrigerants.
4.4.2 Machinery using flammability Class 2L, 2 and 3 refrigerants may be
installed in machinery spaces providing the following controls are complied with:
- The total mass of refrigerant in the space is limited to the
values listed in Table 4.4.1 Refrigerant charge limits .
- A mechanical ventilation system capable of 30 air changes
per hour which is separate from ventilation systems serving other compartments
is provided. The ventilation system is to be arranged to ensure a good flow of
air around the refrigerating machinery. A lower flow may be used in normal
operation provided the system can increase the flow in the event of a leak being
detected, but is not to be below a minimum of ten air changes per hour.
- The space shall be provided with fire protection equivalent
to a category A machinery space.
4.4.3 If the refrigerant has the potential to produce toxic or corrosive products from
combustion, these are to be considered in the fire-fighting design and appropriate
warning signage provided adjacent to the machinery.
4.5 Charge limits due to toxicity
4.5.1 There is no restriction due to toxicity on the charge size of toxicity
class A refrigerants.
4.5.2 Refrigeration machinery and storage vessels containing toxicity class B
refrigerants may be installed in machinery spaces providing the total mass of
refrigerant is limited to the values listed in Table 4.4.1 Refrigerant charge limits .
Table 4.4.1 Refrigerant charge limits
Refrigerant Properties
|
Maximum allowable total refrigerant
charge
|
Toxicity
|
Flammability
|
Machinery
spaces
|
Accommodation
spaces
|
A
|
1
|
No charge
restriction
|
PL x
V
|
2L
|
20% x
LFL x V
|
2
|
3
|
B
|
1
|
≤10 kg
|
2L
|
20% x
LFL x V
but no greater than 10 kg
|
2
|
3
|
LFL = Lower flammability limit (kg/m3)
PL = Practical limit (kg/m3)
V = volume of compartment (m3) (see
Note 1)
|
Note 1. Permeability
of a compartment does not need to be considered for the
calculation (permeability =1) however, large enclosed volumes
such as gas turbine acoustic enclosures should be deducted from
the total compartment volume.
|
4.6 Refrigeration machinery space
4.6.1 A refrigeration machinery space is to be a normally unattended, gastight space.
4.6.2 The compartment access door is to open outwards and is to be fitted with an easily
operated opening mechanism to facilitate rapid escape in an emergency.
4.6.3 Where the refrigerating machinery space contains refrigerant of toxicity
Class B the space is to be fitted with the following features:
- Independent mechanical exhaust ventilation, ensuring at
least ten air changes per hour in empty space.
- Natural or mechanical supply ventilation independent of the
ventilation of other spaces.
- The ventilation system shall ensure under-pressure inside
the refrigerating machinery space.
- Clear signage indicating the potential hazard and warning
not to enter when a leak has been detected.
- Where the charge is greater than 50 kg, emergency body
shower and eye wash facilities shall be installed locally outside the
compartment.
4.6.4 Where the refrigerating machinery space contains refrigerant of
flammability Class 2L, 2 or 3 the space is to be fitted with the following features:
- A non-sparking mechanical exhaust ventilation system, with a
capacity of at least 30 air changes per hour, which is arranged to avoid areas
where gas may accumulate taking into account the density of the vapour and
potential ignition sources. The ventilation system shall be separated from those
serving other spaces.
- All machinery and electrical equipment within the space is
to be of a type suitable for a zone 2 hazardous area in accordance with Vol 2, Pt 9, Ch 5, 4 Electrical equipment for use in explosive gas atmospheres or in the presence of combustible dusts.
- The leak detection is to be set to alarm at gas
concentrations above 30 per cent lower flammable limit (LFL).
- All spaces containing these refrigerants, including exhaust
vents, are to be indicated on a hazardous area plan as described in Vol 2, Pt 9, Ch 1, 1 General requirements.
4.6.6 If the refrigerant has the potential to produce toxic or corrosive products from
combustion these are to be considered in the fire-fighting design and appropriate
warning signs provided at the entrance to the space.
4.6.7 The ventilation design is to consider the density of the refrigerant and draw from
the appropriate location to ensure good air distribution and effective exhaust from
the compartment.
4.6.8 The refrigerating machinery space shall have two means of escape
arranged as far apart as practicable. Spaces with automated unattended refrigerating
machinery, operating on Group A1 and B1 refrigerants, need not be provided with a
second means of escape.
4.6.9 The starting and stopping arrangements for the ventilation shall be
arranged both inside the refrigerating machinery space and outside, in the vicinity
of the exit.
4.6.10 Drain pipes from the refrigerated machinery space are to be fitted with liquid sealed
traps. Non-return valves are to be fitted in drain pipes from spaces located on the
tank tops.
4.7 Refrigerant storage compartments
4.7.1 Portable cylinders containing reserve supplies of refrigerant are to be stored in the
same compartment as the refrigeration machinery and included within the charge
limit, or in a well-ventilated compartment reserved solely for this purpose.
4.7.2 Compartments for storage of toxic (Class B) or flammable (Class 2L, 2 or
3) refrigerants are to include the following features:
- A mechanical ventilation system providing ten air changes
per hour.
- At least one door opening outwards giving direct access to
open deck.
- Clear signage indicating the potential hazard and warning
not to enter when a leak has been detected.
- Liquid sealed traps fitted to drain pipes. Non-return valves
are to be fitted in drain pipes from spaces located on the tank tops.
4.7.4 Bulk storage tanks holding more than 150 kg of replacement carbon dioxide (class A1)
are to be located in a dedicated compartment. The compartment is to be provided with
the following features:
- A mechanical ventilation system providing ten air changes
per hour.
- Ventilation system exhaust ducting positioned to remove air
from the base of the compartment.
- A gastight access door opening outward.
4.7.6 Storage cylinders are to be of an approved type, and are to be filled to a level
suitable for an ambient temperature of + 55°C.
4.7.7 The compartment is to be provided with racks to facilitate secure stowage of the
cylinders.
4.7.8 The Naval Administration may require protection of flammable gasses from military
attack.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
|
|