5.1.2 The equipment used in refrigeration systems is to be provided with local control and
monitoring arrangements.
5.1.3 Where isolation of equipment or systems can be carried out, means of indicating the
status of isolation is to be provided at positions where the equipment and system
can be operated and monitored.
5.1.4 Instrumentation to indicate the operational status of running and any standby
equipment is to be provided locally and at any control station.
5.1.5 All pumps are to be provided with an indication of discharge pressure and a low
discharge pressure alarm at each control station.
5.1.7 Refrigeration compressors are to be provided with the following instrumentation and
automatic shutdowns:
- Indication of suction pressure (saturated temperature),
including intermediate stage when applicable.
- Indication of discharge pressure (saturated temperature),
including intermediate stage when applicable.
- Indication of lubricating oil pressure.
- Indication of cumulative running hours.
- Automatic shutdown in the event of low lubricating oil
pressure.
- Automatic shutdown in the event of high discharge pressure
which is to operate at a pressure in excess of normal operating pressure but not
greater than 0,9 of the maximum working pressure.
- Automatic shutdown in the event of a low suction pressure.
5.1.8 For refrigeration compressors greater than 25 kW, the following
instrumentation, additional to that required by Vol 2, Pt 11, Ch 4, 5.1 General 5.1.7 is to
be provided:
- Indication of lubricating oil temperature.
- Indication of cooling water outlet temperature.
- Indication of suction and discharge temperatures.
5.1.9 Alarms are to be initiated in the event of the following fault conditions with
refrigeration compressors:
- High discharge pressure.
- Low suction pressure.
- Low oil pressure.
- High discharge temperature.
- High oil temperature.
- Motor shutdown.
5.1.10 Refrigeration plants are to be provided with the following alarms:
- Failure of condenser cooling water pumps.
- High condenser cooling water outlet temperature.
- Failure of air cooler fans.
- High and low chilled water delivery temperatures.