10.2.1 An electrical
                                 insulation resistance test is to be made on the electrical equipment
                                 and cables. The installation may be sub-divided, or equipment which
                                 may be damaged disconnected, for the purpose of this test.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.2 The fittings
                                 on the main and emergency switchboards, section boards and distribution
                                 boards are to be examined and over-current protective devices and
                                 fuses inspected to verify that they provide suitable protection for
                                 their respective circuits.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.3 Generator
                                 circuit-breakers are to be tested, so far as is practicable, to verify
                                 that protective devices including preference tripping relays, if fitted,
                                 operate satisfactorily.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.4 Air circuit-breakers
                                 for essential or emergency services and rated at 800 A and above are
                                 to be surveyed to ensure that the manufacturer’s recommended
                                 number of switching options has not been exceeded. See Vol
                                 7, Pt  16, Ch  2,  7.3 Circuit-breakers 7.3.6. Where a
                                 breaker is not fitted with an automatic counter, a written record
                                 is to be kept.
                                 
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.5 The electric
                                 cables and their securing arrangements are to be examined, so far
                                 as is practicable, without undue disturbance of fixtures or casings
                                 unless opening up is considered necessary as a result of observation
                                 or of the tests required by Pt  1, Ch  3,  10.2 Complete Surveys 10.2.1.
                                 
                              
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              10.2.7 Where
                                 transformers or electrical apparatus associated with supplies to essential
                                 services are liquid-immersed, the Owner is to arrange for samples
                                 of the liquid to be taken and tested for dissolved gases, breakdown
                                 voltage, acidity and moisture by a competent authority, in accordance
                                 with the equipment manufacturer's requirements, and a certificate
                                 giving the test results is to be made available  to the Surveyor on
                                 request.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.8 Navigation
                                 light indicators are to be tried under working conditions, and correct
                                 operation on the failure of supply or failure of navigation lights
                                 verified.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.9 The emergency
                                 sources of electrical power, where fitted, together with their automatic
                                 arrangements and associated circuits are to be tested.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.10 Emergency
                                 lighting, transitional emergency lighting, supplementary emergency
                                 lighting, general emergency alarm and public address systems are to
                                 be tested as far as practicable.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.11 Where
                                 the craft is electrically propelled, the propulsion motors, generators,
                                 propulsion transformers, propulsion conversion equipment, cables,
                                 harmonic filters, neutral earthing resistors, dynamic braking resistors
                                 and all ancillary electrical equipment that forms part of the propulsion
                                 drive and control system, exciters and ventilating plant (including
                                 coolers) associated therewith are to be surveyed, and the insulation
                                 resistance to earth is to be tested. Special attention is to be given
                                 to windings, commutators and slip-rings. Where practicable, the low
                                 voltage and high voltage windings of resin cast propulsion transformers
                                 are to be subjected to boroscopic inspection, to assess the physical
                                 condition of their insulation and for signs of mechanical and thermal
                                 damage. The operation of protective gear and alarm devices is to be
                                 checked, so far as is practicable. Insulating oil, if used, is to
                                 be tested in accordance with Pt  1, Ch  3,  10.2 Complete Surveys 10.2.7.
                                 Interlocks intended to prevent unsafe operations or unauthorised access
                                 are to be checked to verify that they are functioning correctly. Emergency
                                 overspeed governors are to be tested.
                                 
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.12 Where batteries with charging power higher than 2kW provide the source of
                                 power for any essential services, their installation, including charging and ventilation
                                 arrangements, is to be examined.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.13 Sufficient battery capacity shall be verified for Lithium-Ion battery
                                 system installations used as the primary power source for emergency systems.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.14 Where Lithium-Ion batteries with total system capacity exceeding 20 kWh are
                                 used as the primary power source for essential or emergency systems, a test of all
                                 required monitoring and safety functions shall be carried out.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.15 A test of the safety functions in spaces or compartments containing
                                 Lithium-Ion batteries with total system capacity exceeding 20 kWh used as power source
                                 for essential and emergency services shall be carried out, i.e., fire detection and
                                 extinguishing, gas detection, ventilation etc. as applicable to the installation.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              10.2.16 The safety aspects of spaces or compartments containing Lithium-Ion
                                 batteries used as a power source for essential or emergency systems are to be examined
                                 as applicable to the installation. This could include examinations of:
                                 
                                    - structural fire protection;
 
                                    - fixed fire detection;
 
                                    - fixed firefighting system(s);
 
                                    - ventilation and associated dampers;
 
                                    - off-gas detection, exhaust and/or extraction arrangement;
 
                                    - integrity of battery crates, trays, boxes, shelves and other structural
                                       parts;
                                    
 
                                    - battery cooling arrangement;
 
                                    - electrical power cabling, switchgear and converters; and
 
                                    - EEBD (emergency escape breathing device) and means of escape.