10.2.1 Three
or more HPSW pumps are to be provided of sufficient capacity to supply
the total pumping capacity defined in Vol 2, Pt 7, Ch 5, 10.2 Pump units 10.2.3 with any one pump out of action. At least one of the pumps
is to be capable of supplying HPSW in a dead ship condition.
10.2.2 The
pumps are to be located in separate compartments and zones such that
the loss of one compartment or zone or failure in equipment will not
render the other pumps inoperative.
10.2.3 The
total pumping capacity of the HPSW pumps with one pump out of action
shall provide for the greatest of the following:
-
The amount required for pre-wetting.
-
The amount required for a fire in the largest space protected by a
fixed spray system plus 40 m3/hr boundary cooling from hoses.
-
The amount required for a major fire outside the spaces protected by
fixed spray systems, using 100 m3/hr boundary cooling for each fire.
The minimum number of fires to be considered is as follows:
-
Displacement at deep draught of under 4,000 tonnes – one
fire
-
Between 4,000 and 10,000 tonnes – two fires
-
Between 10,000 and 20,000 tonnes – three fires
-
Over 20,000 tonnes – four fires
Reference is also to be made to the System Design Description required
by Vol 2, Pt 7, Ch 5, 1.3 Documentation required for design review 1.3.2 where the number of fires to be considered may
also reference amongst other items, the type of ship, number of personnel on board
and number of fire zones.
-
The largest single magazine or ammunition transfer space spray
requirement plus 40 m3/hr boundary cooling.
-
The hangar spray requirement in the largest area contained by a fire
curtain.
-
A flight deck fire requiring one third of the total foam branch pipes
fitted in multi-aircraft landing (multi-spot) ships or two foam branch pipes in
single aircraft landing (single spot) ships.
- The amount required for any specific fire-fighting scenarios
defined by the System Design Description.
If the factor determining the total pumping capacity is (b),
then any pumps located in the space are to be added to the overall
number of pumps required.
10.2.5 The
sea suctions to HPSW pumps are to be provided with an air elimination
arrangement to ensure that the running and standby pumps do not become
air-locked.
10.2.6 HPSW
pumps are to be arranged to operate continuously with automatic and
switched means of starting of standby pumps on sea-water demand. Automatic
starting of standby pumps may be achieved by sensing when the system
pressure falls below a pre-set level. The continuous and minimum supply
pressures in the HPSW distribution system are to be in accordance
with the System Design Description required by Vol 2, Pt 7, Ch 5, 1.3 Documentation required for design review 1.3.2.
10.2.7 HPSW
pumps are to be provided with high temperature alarms for components
that may become overheated when the pump is running in low or no flow
demand conditions.
10.2.8 Where
HPSW pumps can develop a pressure greater than the design pressure
of the system, they are to be provided with pressure relief/control
devices on the pump discharge to effectively limit the pump discharge
pressure to the design pressure of the system.
10.2.9 Strainers
capable of being cleaned without interruption of water flow to the
pumps are to be provided in the suction pipes.