Section 4 System design
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules for LNG Ships and Barges Equipped with Regasification Systems, July 2022 - Chapter 1 Rules for LNG Ships and Barges Equipped with Regasification Systems - Section 4 System design

Section 4 System design

4.1 General

4.1.1 Materials, components and equipment to be used in the construction of regasification systems shall be suitable for the intended service conditions and acceptable to LR. The materials, components and equipment shall also satisfy the requirements of this Section.

4.1.2 Materials shall comply with the requirements of the Rules for the Manufacture, Testing and Certification of Materials (hereinafter referred to as the Rules for Materials) and Chapter 6 of the Rules for Ships for Liquefied Gases.

4.1.3 The design, arrangements and selection of equipment shall be such as to minimise the risk of fire and explosion from flammable products.

4.1.4 Electrical components and equipment shall comply with Ch 1, 7 Electrical installation.

4.1.5 Any single failure of the regasification system shall not result in a hazard that affects safety.

4.1.6 The regasification ship or barge shall have adequate capability for managing the boil-off gas generated by heat ingress through headers, manifolds and loading arms during ship-to-ship transfer operations.

4.1.7 The regasification system shall include provision to pre-cool the product transfer piping system prior to ship-to-ship transfer operations commencing.

4.2 Vaporisers

4.2.1 The requirements of these Rules apply to various types of vaporiser, such as:

  • STV – Shell and tube heat-exchanger type.
  • ORV – Open rack type utilising sea-water or a circulating intermediate heated fluid.
  • SCV – Submerged combustion type utilising the heat of combustion of either oil or send-out gas.

4.2.2 Vaporising units of novel design, making use of materials not covered by the Rules, will be subject to special consideration and subject to the requirements of Pt 7, Ch 14 Requirements for Machinery and Engineering Systems of Unconventional Design of the Rules for Ships, ‘Requirements for machinery and engineering systems of unconventional design’.

4.2.3 The manufacture, installation and testing of vaporisers, including the intermediate heat transfer vessels and pumping systems, shall be undertaken in accordance with the requirements of the Rules for Ships for Liquefied Gases.

4.2.4 All LNG high pressure pumps supplying vaporisers, which are capable of developing a pressure exceeding the design pressure of the system into which they are pumping, are to be provided with relief valves in closed circuit.

4.2.5 For STVs and ORVs, sea-water may be used as a primary heat source for vaporisation. An intermediate heat transfer fluid may be proposed to reduce the chance of freezing and effects of corrosion.

4.2.6 Where sea-water is used as the source of heat to vaporise the LNG, the tubes shall be manufactured from a corrosion-resistant material, taking into consideration the type and temperature of media conveyed. Where the Lloyd’s RGP+ Notation is to be assigned, suitable redundancy of the sea-water circulation pump and LNG high pressure supply pumps shall be provided.

4.2.7 When an intermediate heat transfer fluid is used, and where the Lloyd’s RGP+ Notation is to be assigned, dual compressors or circulating pumps shall be provided. Where the heat transfer fluid goes through a phase change, the applicable Sections ofPt 6, Ch 3 Refrigerated Cargo Installations of the Rules for Ships shall be complied with.

4.2.8 Where potential risk of failure of a tube or passage could result in gas entering the sea-water side:

  1. the sea-water side shall be designed to accept the full gas pressure of the gas side;

  2. the sea-water side shall be protected with relief valves in readily visible positions; the discharge from these relief valves shall be taken to a suitable high-pressure venting arrangement and the number and position of valves shall be adequate to relieve the flow occurring due to failure of a single tube.

4.2.9 If steam is used in a heat exchanger containing either propane or other gas, the condensate shall not be passed directly back to the engine room. The condensate shall be passed through a degassing tank located in a gas-dangerous area. The vent outlet from the degassing tank shall be routed to a safe location and be fitted with a flame screen. The degassing tank shall be covered by the gas detection and alarm system, see Ch 1, 4.3 Gas detection system.

4.2.10 If the LNG ship is to operate in regions where insufficient natural sources of heat are available for vaporisation, e.g. low sea-water temperature, the design gas output conditions shall be maintained utilising alternative means.

4.2.11 Where alternative means of heating the LNG are required, an independent gas or oil supply system shall be provided to facilitate initial start-up.

4.2.12 The regasification system may operate with a dual heat source with, for example, a mixture of heat inputs from sea-water and a boiler.

4.2.13 Where aluminium alloy vertical tubes and horizontal headers are constantly covered with sea-water, adequate protection against corrosion shall be provided.

4.2.14 Commissioning and testing of vaporisers shall be undertaken by the manufacturer prior to units being installed on board.

4.2.15 Water supply pumps shall be fitted with suitable inlet filters. It shall be possible to remove and clean the filters whilst the regasification system remains operational. Any regasification system-related sea-water inlet shall be fitted with gratings and provision made to allow cleaning by low pressure steam or compressed air.

4.2.16 A water treatment system shall be incorporated for use with submerged combustion vaporisers to eliminate degradation of the tubes.

4.2.17 The submerged combustion vaporisers shall comply with the relevant Sections applicable to inert gas generators and steam boilers operating with boil-off gas, as applicable, stated in Chapter 7 of the Rules for Ships for Liquefied Gases and Part 5, Pt 5, Ch 10 Steam Raising Plant and Associated Pressure Vessels, Pt 5, Ch 14 Machinery Piping Systems and Pt 5, Ch 15 Piping Systems for Oil Tankers of the Rules for Ships.

4.3 Gas detection system

4.3.1 In addition to the gas detection system fitted to allow compliance with the Rules for Ships for Liquefied Gases, a permanently installed system of gas detection and audible and visual alarms is to be fitted in:

  1. all enclosed spaces containing gas piping, liquid piping or regasification equipment;

  2. other enclosed or semi-enclosed spaces where gas vapours may accumulate;

  3. air-locks;

  4. secondary fluid expansion tanks;

  5. the condensate degassing tank.

4.3.2 Gas detection equipment is to be designed, installed and tested in accordance with IEC 60079-29-1, and is to be suitable for the gases to be detected.

4.3.3 The number and the positions of detection heads or sampling heads is to be determined with due regard to the size and layout of the compartment, the air flow from compartment purging or ventilation and stagnant areas, and the manufacturer’s recommendations.

4.3.4 The gas detection system serving the regasification system may be either independent or combined with the gas detection system installed to allow compliance with the Rules for Ships for Liquefied Gases.

4.3.5 The gas detection is to be of the continuous monitoring type, capable of immediate response.

4.3.6 The gas detection system serving the regasification system is otherwise to comply with the construction and installation requirements of the Rules for Ships for Liquefied Gases.

4.4 Emergency shutdown (ESD) system

4.4.1 An emergency shutdown (ESD) system serving the regasification systems and equipment shall be fitted and shall comply with the cause and effect matrix shown in Table 1.4.1 ESD functional arrangements, as applicable.

Table 1.4.1 ESD functional arrangements

  Pumps Compressor systems Valves Link
Shutdown action Cargo pumps/ cargo booster pumps Spray/ stripping pumps Vapour return compressors Fuel gas compressors Reliquefaction plant, including condensate return pumps, if fitted Gas combustion unit ESD values Valves Signal to ship/ shore link***
Initiation
Emergency push buttons (See Ch 1, 4.4 Emergency shutdown (ESD) system 4.4.2) See Note 2
Fire detection on deck or in compressor house*
High level in cargo tank See Notes 1 and 2 See Notes 1 and 3 See Note 1 See Note 6
Signal from ship/shore link See Note 2 See Note 3 n/a n/a
Loss of motive power to ESD valves** See Note 2 See Note 3 n/a
Main electric power failure ('blackout') See Note 7 See Note 7 See Note 7 See Note 7 See Note 7 See Note 7
Cargo tank level alarm override (See Note 4) See Note 4 See Notes 4 and 5 See Note 1 See Note 1 See Note 1
KEY
* Fusible plugs, electronic point temperature monitoring or area fire detection may be used for this purpose on deck
** Failure of hydraulic, electric or pneumatic power for remotely operated ESD valve actuators
*** Signal need not indicate the event initiating ESD
Functional requirement
n/a Not applicable

Note 1. These items of equipment can be omitted from these specific automatic shutdown initiators provided the compressor inlets are protected against cargo liquid ingress.

Note 2. If the fuel gas compressor is used to return cargo vapour to shore, it shall be included in the ESD system only when operating in this mode.

Note 3. If the reliquefaction plant compressors are used for vapour return/shore line clearing, they shall be included in the ESD system only when operating in that mode.

Note 4. An override of the overflow control system may be used at sea to prevent false alarms or shutdowns. The arrangements for the override system shall be such that inadvertent operation is prevented. When level alarms are overridden, operation of cargo pumps and the opening of manifold ESD valves shall be inhibited and continuous visual indication shall be given at the relevant control station(s) and the navigating bridge.

Note 5. Cargo spray or stripping pumps used to supply forcing vaporiser may be excluded from the ESD system only when operating in that mode.

Note 6. A sensor operating independently of the high liquid level alarm shall automatically actuate a shut-off valve in a manner that will both avoid excessive liquid pressure in the loading line and prevent the tank from becoming liquid full. These sensors may be used to close automatically the tank filling valve for the individual tank where the sensors are installed, as an alternative to closing the ESD valve provided at each manifold connection. If this option is adopted, activation of the full ESD system shall be initiated when the high-level sensors in all the tanks to be loaded have been activated.

Note 7. These items of equipment shall be designed not to restart automatically upon recovery of main electric power and without confirmation of safe conditions.

4.4.2 The ESD system shall be activated by the manual and automatic inputs listed in Table 1.4.1 ESD functional arrangements. Any additional inputs shall only be included in the ESD system if it can be shown that their inclusion does not reduce the integrity and reliability of the system overall.

4.4.3 The ESD system shall return the regasification system to a safe static condition, allowing remedial action to be taken. Due regard shall be given in the design of the ESD system to avoid the generation of surge pressures within the pipework.

4.4.4 The equipment to be shut down on ESD activation shall include manifold valves during loading or discharge, and pumps and compressors associated with transferring cargo in either liquid or gaseous state.

4.4.5 The emergency shutdown system associated with the regasification system shall be designed, manufactured and tested in accordance with the principles stated in Ch 5, 5.6 of the Rules for Ships for Liquefied Gases.

4.4.6 The number and location of additional shutdown positions shall be determined by the type, number, location and position of the regasification systems and equipment.

4.5 Process shutdown (PSD) system

4.5.1 A process shutdown (PSD) system for the regasification system shall be arranged in accordance with the requirements listed in Ch 1, 6 Instrumentation, control, alarm and monitoring systems.

4.5.2 The activation of the PSD shall stop the supply of LNG to the LNG suction drum, high pressure LNG pumps and gas discharge valve. Where the installation comprises a number of separate regasification systems the PSD may be system-specific as well as full shutdown. A PSD functional arrangement matrix commensurate with that shown in Table 1.4.1 ESD functional arrangements shall be provided.

4.5.3 Manual PSD points shall be arranged at the regasification system control station and at locations as determined by the type, number, location and position of the regasification systems and equipment. The process shutdown points shall be clearly visible.

4.5.4 Process shutdown valves in liquid piping shall close fully under all service conditions within 30 seconds of actuation. Information about the closing time of the valves and their operating characteristics shall be available on board and the closing time shall be verifiable and reproducible.

4.5.5 The closure time of 30 seconds for the shutdown valve referred to in Ch 1, 4.5 Process shutdown (PSD) system 4.5.4 shall be measured from the time of manual or automatic initiation to final closure. This is called the total shutdown time and is made up of a signal response time and a valve closure time. The valve closure time shall be such as to avoid surge pressure in pipelines. Valves shall close smoothly.

4.6 Depressurisation and blowdown system

4.6.1 A depressurisation and blowdown system shall be provided for depressurising the high pressure liquid and gas pumps, vessels and pipework.

4.6.2 Where a liquid depressurisation system is provided, adequate provision shall be made in the design and installation for the effects of back pressure in the system and vapour flash-off when the pressures of liquids in the blowdown system are reduced.

4.6.3 Manual and automatic activation of the depressurisation system shall be provided.

4.6.4 Manual activation shall be possible from the regasification control station, at the send-out manifold, and from other locations as determined by the type, number, location and position of the regasification systems and equipment.

4.6.5 Automatic activation shall be part of the emergency shutdown arrangements.

4.7 Pressure relief and venting system

4.7.1 Each regasification unit shall be provided with dedicated high pressure safety relief valves and venting arrangements. The arrangements shall be independent from the venting arrangements serving the cargo tanks. High pressure safety relief valves, headers, knock-out/drain drum and vent masts shall be located within the cargo deck area.

4.7.2 High pressure safety relief valves and venting arrangements for liquid and gas phases shall be provided for each regasification system. The safety relief valve support arrangements shall withstand the loads imposed by discharges.

4.7.3 Where multiple regasification systems are installed, the design of pressure safety relief and venting arrangements shall consider the maximum combined release rate.

4.7.4 The gaseous phase safety relief valves shall be led to the dedicated high pressure vent mast for the regasification system required by Ch 1, 4.7 Pressure relief and venting system 4.7.1. The high pressure vent mast shall be sized to handle the maximum regasification capacity and to ensure safe dispersal of the gas.

4.7.5 The liquid phase safety relief valves shall be led to a knock-out/drain drum having adequate capacity for the maximum LNG inflow anticipated within the design of the regasification unit. The knock-out drum shall be fitted with a level switch to stop all high pressure LNG pumps. Any LNG from the vent knock-out drum shall be safely drained or be allowed to boil off and vapour to be returned to the ship’s vapour header.

4.7.6 LNG suction and LNG knock-out/drain drums shall be fitted with pressure safety relief valves in accordance with the Rules for Ships for Liquefied Gases.

4.7.7 Pressure safety relief valves and venting arrangements and locations shall comply with Ch 8 Vent Systems for Cargo Containment of the Rules for Ships for Liquefied Gases.

4.8 Fire protection and fire extinction

4.8.1 The regasification system shall be protected with both a water spray deluge system plus a dry chemical powder system and a fire detection system. The systems shall meet the requirements of Chapter 11 of the Rules for Ships for Liquefied Gases.

4.8.2 The water spray deluge system and dry chemical powder system installed on board the ship shall be capable of providing coverage for the areas defined in Chapter 11 of the Rules for Ships for Liquefied Gases and the regasification system simultaneously.

4.8.3 The ship’s water spray deluge system shall be designed to cover the regasification equipment, ship-to-ship LNG loading arms and export manifold.

4.8.4 Protection from fire and heat shall be provided as necessary for the safe escape of personnel in case of an emergency. Details shall be submitted for appraisal as indicated in Ch 1, 2 Submission of plans and documentation.

4.8.5 Fire protection arrangements shall be such as to prevent possible jet fires propagating from the regasification unit to the adjacent cargo tank areas. Proposed arrangements shall be evaluated in the risk based studies in Ch 1, 3 Risk based analysis.

4.9 Location and arrangement of equipment

4.9.1 The location of the regasification unit shall be considered part of the cargo area as defined in Ch 1,1.3.6 of the Rules for Ships for Liquefied Gases. The regasification unit and all its associated equipment shall be located as far as is reasonably possible from the accommodation spaces.

4.9.2 The regasification system machinery may be located on the open deck or in cargo pump and cargo compressor rooms. Arrangements of such spaces shall be in accordance with the requirements of Chapter 3 of the Rules for Ships for Liquefied Gases.

4.9.3 When the regasification units are located on open deck they shall be placed in a sheltered location protected from green water.

4.9.4 The locations of the system arrangements, including vaporisers, high pressure pumps, suction drums, heaters, liquid pumps and ancillary piping systems, shall be defined and evaluated in the system safety risk assessment, (see Ch 1, 3 Risk based analysis), and shall be acceptable to LR.

4.9.5 The ship structure shall be protected from possible cryogenic spills at the regasification unit and suction drum in way of fittings, fixtures and demountable joints except in those locations where the structure material can withstand cryogenic temperatures.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.