18.2.1 Insulation
resistance is to be measured using a self-contained instrument such
as a direct reading ohm-meter of the generator type applying a voltage
of at least 500 V. Where a circuit incorporates capacitors of more
than 2 μF total capacitance, a constant-voltage type instrument
is to be used to ensure accurate test readings.
18.2.2
Power
and lighting circuits. The insulation resistance between all
insulated poles and earth and where practicable, between poles, is
to be at least 1 MΩ. The installation may be subdivided and appliances
may be disconnected if initial tests produce results less than this
figure.
18.2.3
Low
voltage circuits. Circuits operating at less than 50 V are
to have an insulation resistance of at least 0,33 MΩ.
18.2.4
Switchboards,
section boards and distribution boards. The insulation resistance
is to be at least 1 MΩ when measured between each busbar and
earth and between busbars. This test may be made with all circuit-breakers
and switches open, all fuse links for pilot lamps, earth fault-indicating
lamps, voltmeters, etc. removed and voltage coils temporarily disconnected,
where otherwise damage may result.
18.2.5
Generators
and motors. The insulation resistance of generators and motors,
in normal working condition and with all parts in place, is to be
measured and recorded. The test should be carried out with the machine
hot, if possible. The insulation resistance of generator and motor
cables, field windings and controlgear is to be at least 1 MΩ.