Section 2 System design - General
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules and Regulations for the Classification of Inland Waterways Ships, July 2022 - Part 6 Control, Electrical and Fire - Chapter 2 Electrical Installations - Section 2 System design - General

Section 2 System design - General

2.1 Systems of distribution

2.1.1 The following systems of distribution may be used:

  1. Parallel systems with constant voltage

    1. d.c., two-wire

    2. a.c., single-phase, two-wire

    3. a.c., three-phase,

      three-wire

      four-wire with neutral earthed

    Systems employing hull return will be accepted except for final sub-circuits which are to be 2-pole insulated.

  2. Series systems with constant current (direct current only).

2.1.2 For parallel systems with constant voltage, system voltages for both alternating current and direct current shall not exceed:

  500 V for generation, power, cooking and heating equipment permanently connected to fixed wiring.
  250 V for lighting, heaters in cabins and public rooms, and other applications not mentioned above.

2.1.3 Generation and distribution at higher voltages may be submitted for special consideration.

2.2 Earth indication

2.2.1 Every insulated distribution system is to be provided with lamps or other means to indicate the state of insulation to earth.

2.2.2 A device(s) is to be installed for every insulated distribution system, whether primary or secondary, for power, heating and lighting circuits, to continuously monitor the insulation level to earth and to operate an alarm in the event of an abnormally low level of insulation resistance.

2.3 Number and rating of generating sets

2.3.1 The number and rating of the ship’s service generating sets and converting sets are to be sufficient to ensure the operation of services essential for the propulsion and safety of the ship.

2.3.2 On oil tankers, oil and chemical tankers, chemical tankers, cargo and passenger ships where electrical power is required for essential equipment, the generating plant and converting plant is to be of such capacity that this essential equipment can be operated satisfactorily even with one generating set or converting set out of action.

2.3.3 In alternating current systems requiring standby equipment, see Pt 6, Ch 2, 2.3 Number and rating of generating sets 2.3.1, with one generating set out of action, the remaining set(s) are to have sufficient reserve capacity to permit the starting of the largest motor in the ship without causing any motor to stall or any other device to fail due to excessive voltage drop on the system.

2.4 Emergency source of power in passenger ships

2.4.1 All passenger ships are to be provided with an emergency source of electrical power. Location is to be aft of collision bulkhead and A60 separated from main generators and in a watertight separated compartment when available.

2.4.2 Where emergency generating sets are fitted, they are to be capable of being started readily when cold.

2.4.3 If hand starting is demonstrated to be practicable, alternative means of starting are not required. Where hand starting is not practicable, other means are to be provided and, in general, should provide for not less than 12 starts in a period of 30 minutes without recourse to sources within the machinery space.

2.4.4 The power available is to be sufficient to supply all services necessary for the safety of passengers and crew in an emergency, due regard being paid to such services as may have to be operated simultaneously. Special consideration is to be given to emergency lighting in all alleyways, stairways and exits, in the machinery spaces and in the control stations (i.e. spaces in which radio, main navigating or central fire recording equipment or the emergency generator is located), to fire detection and alarm systems, to the emergency fire pump if electrically driven, automatic sprinkler systems, if fitted, and to navigation lights. The power is to be adequate for a period of three hours.

2.4.5 The emergency source of power is to be either:

  1. A generator driven by a suitable prime mover with an independent fuel supply and with satisfactory starting arrangements; the fuel used is to have a flash point of not less than 43°C; or

  2. An accumulator (storage) battery capable of carrying the emergency load without recharging or excessive voltage drop.

2.4.6 Where the emergency source of power is an accumulator battery, arrangements are to be such that emergency lighting will automatically come into operation on failure of the main lighting supply.

2.4.7 An indicator is to be mounted in the machinery space, or in the wheelhouse, to indicate when any accumulator battery fitted in accordance with Pt 6, Ch 2, 2.4 Emergency source of power in passenger ships 2.4.5 is being discharged.

2.4.8 The emergency switchboard is to be installed as near as is practicable to the emergency source of power.

2.4.9 The emergency switchboard may be supplied from the main switchboard during normal operation.

2.4.10 Emergency source/distribution is to be independent from main source/distribution and main source/distribution is to be independent of emergency source/distribution.

2.5 Diversity factor

2.5.1 Circuits supplying two or more final sub-circuits are to be rated in accordance with the total connected load subject, where justified, to the application of a diversity factor. Where spare ways are provided on a section or distribution board, an allowance for future increase of load is to be added to the total connected load before application of any diversity factor.

2.5.2 The diversity factor may be applied to the calculation for size of cable and rating of switchgear and fusegear.

2.6 Motor circuits

2.6.1 A separate final sub-circuit is to be provided for every motor required for essential services.

2.7 Lighting circuits

2.7.1 Lighting circuits are to be supplied by final sub-circuits separate from those for heating and power. (This does not apply to cabin fans and wardrobe heaters).

2.7.2 A final sub-circuit of rating exceeding 15 A is not to supply more than one point. The number of lighting points supplied by a final sub-circuit of rating 15 A or less is not to exceed:

10 for 24 55 V circuits,
14 for 110 127 V circuits,
18 for 220 250 V circuits,

except that in final sub-circuits for cornice lighting, panel lighting and electric signs where lampholders are closely grouped, the number of points supplied is unrestricted, provided the maximum operating current in the sub-circuit does not exceed 10 A.

2.7.3 Lighting of cargo spaces is to be controlled by multi-pole linked switches situated outside these spaces. Provision is to be made for the complete isolation of these circuits and locking in the off position of the means of control.

2.7.4 Emergency lighting is to be fitted in accordance with Pt 6, Ch 2, 2.4 Emergency source of power in passenger ships 2.4.4.

2.8 Steering gear

2.8.1 Where electrical control of the steering system is fitted, an independent alternative control system is to be installed. This may be a duplicate electrical control system or control by other means.

2.8.2 Provision should be made on the bridge to effectively transfer the steering control instantaneously to the alternative means of control.

2.8.3 Indicators for running indication of steering gear motors are to be installed on the bridge.

2.8.4 Audible and visual alarms are to operate at the steering position(s) for the following fault conditions:

  1. Failure of steering gear power system(s).

  2. Failure of steering gear control system(s).

2.9 Fire detection, alarm and extinguishing systems on passenger ships

2.9.1 Where electrically driven emergency fire pumps are installed in accordance with Pt 6, Ch 2, 17.4 Emergency services 17.4.1, the supply to such pumps is not to pass through the main machinery spaces.

2.9.2 Any fire-alarm system is to operate both audible and visual signals at the fire detection control station(s).

2.10 Navigation lights

2.10.1 Each navigation light is to be controlled and protected in each insulated pole by a switch and fuse or circuit-breaker mounted in the distribution board.

2.10.2 Automatic indication of failure is to be provided unless lights are visible from the bridge.

2.10.3 Any Statutory Requirements of the country of registration are to be complied with and may be accepted as an alternative to the above.

2.11 Remote stops for ventilating fans and pumps

2.11.1 Means are to be provided for stopping ventilating fans serving machinery and cargo spaces. These means are to be capable of being operated from outside such spaces in case of fire.

2.11.2 Machinery driving boiler fans, independently driven pumps delivering oil to main propulsion machinery for bearing lubrication and piston cooling, fuel oil transfer pumps and other similar fuel pumps are to be fitted with remote controls situated outside the space concerned so that they may be stopped in the event of fire arising in the space in which they are located.

2.11.3 In passenger ships, all power ventilation systems, except cargo and machinery space ventilation, which is to be in accordance with Pt 6, Ch 2, 2.11 Remote stops for ventilating fans and pumps 2.11.1, are to be fitted with master controls so that all fans may be stopped from either of two separate positions which are to be situated as far apart as practicable.

2.12 Motor control

2.12.1 Every electric motor is to be provided with efficient means of starting and stopping so placed as to be easily operated by the person controlling the motor. Every motor above 0,5 kW is to be provided with control apparatus as given in Pt 6, Ch 2, 2.12 Motor control 2.12.2 .

2.12.2 Means are to be provided to prevent undesired restarting after a stoppage due to low volts or complete loss of volts. This does not apply to motors, the continuous availability of which is essential to the safety of the ship.

2.12.3 Efficient means of isolation are to be provided so that all voltage may be cut off from the motor and any associated apparatus including any automatic circuit-breaker.

2.12.4 Where the primary means of isolation (that provided at the switchboard, section board or distribution fuse board) is remote from a motor, one of the following is to be provided:

  1. An additional means of isolation fitted adjacent to the motor; or

  2. provision made for locking the primary means of isolation in the OFF position; or

  3. provision made so that the fuses in each line can be readily removed and retained by authorized personnel.

2.12.5 Means are to be provided for automatic disconnection of the supply in the event of excess current due to mechanical overloading of the motor.

2.12.6 Where fuses are used to protect polyphase motor circuits, means are to be provided to protect the motor against unacceptable overload in the case of single phasing.

2.12.7 When motor controlgear is being selected, the maximum current of a motor is to be taken as the full load rated current of the motor.

2.13 Size of batteries and charging facilities

2.13.1 Where batteries are used for starting main engines, they are to be of adequate capacity to meet the requirements of Pt 5, Ch 2, 9 Starting arrangements, air compressors and batteries.

2.13.2 Adequate charging facilities are to be provided, and where batteries are charged from line voltage, by means of a series resistor, protection against reversal of current is to be provided when the charging voltage is 20 per cent of line voltage or higher.

2.13.3 In direct current systems, means are to be provided to isolate the batteries from the low voltage system when being charged from a higher voltage system.

2.14 Communications

2.14.1 For the requirements of the provision of a communication system on board passenger ships, see Pt 6, Ch 2, 17.5 Passenger and crew warning system and Pt 6, Ch 2, 17.6 General emergency alarm system.

2.15 Heating and cooking equipment

2.15.1 Each item of heating or cooking equipment is to be controlled as a complete unit by a multi-pole linked switch mounted in the vicinity of the equipment. In the case of cabin heaters a single-pole switch will be acceptable.

2.16 Shore supply

2.16.1 Where arrangements are made for the supply of electricity from a source on shore or elsewhere, a suitable connection box is to be installed in a position in the ship suitable for the convenient connection of flexible cables from the external source and containing a circuit-breaker or isolating switch and fuses and terminals of ample size and suitable shape to facilitate a satisfactory connection. Suitable cables, permanently fixed, are to be provided connecting the terminals to a linked switch and/or a circuit-breaker at the main switchboard.

2.16.2 An earth terminal is to be provided for connecting the hull to the shore earth.The shore connection is to be provided with an indicator at the main switchboard in order to show when the cable is energized.

2.16.3 The shore connection is to be provided with an indicator at the main switchboard in order to show when the cable is energized.

2.16.4 Means are to be provided for checking the polarity (for direct current) or the phase sequence (for three – phase alternating current) of the incoming supply in relation to the ship’s system.

2.16.5 At the connection box, a notice is to be provided giving full information on the system of supply and the normal voltage (and frequency, if alternating current) of the ship’s system and the procedure for carrying out the connection.

2.16.6 Alternative arrangements may be submitted for consideration.

2.17 Choice of cables

2.17.1 Cables are to be in accordance with an acceptable National or International Standard, due regard being given to the ambient conditions stated in Pt 6, Ch 2, 1.5 Ambient temperatures 1.5.1.

2.17.2 The rated voltage of any cable is to be not lower than the nominal voltage of the circuit for which it is used.

2.18 Choice of insulating material

2.18.1 The rated operating temperature of the insulating material is to be at least 10°C higher than the maximum ambient temperature liable to be produced in the space where the cable is installed.

2.19 Choice of protective covering

2.19.1 Cables fitted in the following locations:

  Decks exposed to the weather
  Bathrooms
  Cargo holds
  Machinery spaces

or in any other location where water condensation or harmful vapour (e.g. oil vapour) may be present are to have an impervious sheath. In permanently wet situations, metallic sheaths are to be used for cables with hygroscopic insulation.

2.19.2 All cables are to be of flame-retardant or of fire-resisting type, except that flame-extending cables may be used for final circuits where cables are installed in metallic conduits having an internal diameter not exceeding 25 mm and provided the conduits are mechanically and electrically continuous.

2.20 Current rating

2.20.1 The highest continuous load carried by a cable is not to exceed its current rating. The diversity factor of the individual loads and the duration of the maximum demand may be allowed for in estimating the maximum continuous load and is to be shown on plans submitted for approval.

2.20.2 The voltage drop from the main switchboard busbars to any point in the installation when the cables are carrying maximum current under normal conditions of service, is not to exceed six per cent of the nominal voltage.

2.20.3 In assessing the current rating of lighting circuits, every lampholder is to be assessed at the maximum load likely to be connected to it, with a minimum of 60 W, unless the fitting is so connected as to take only a lamp rated at less than 60 W.

2.20.4 Cables supplying cargo winches, cranes, windlasses and capstans are to be suitably rated for their duty. Unless the duty is such as to require a longer time rating, cables for winch or crane motors may be half hour rated on the basis of the half hour kW rating of the motors. Cables for windlass and capstan motors are to be not less than one hour rated on the basis of the one hour kW rating of the motor. In all cases the rating is to be subject to the voltage drop being within the specified limits.

2.20.5 The current ratings given in Table 2.2.2 General purpose rubber and PVC are based on maximum operating conductor temperatures given in Table 2.2.1 Maximum operating conductor. Alternatively, current rating in accordance with an acceptable National or International Standard may be applied, see Pt 6, Ch 2, 2.17 Choice of cables 2.17.1.

Table 2.2.1 Maximum operating conductor

Insulating material Maximum rated conductor temperature, °C
ELASTOMERIC COMPOUNDS  
Natural or synthetic rubber (general purpose) 60
Butyl rubber 80
Ethylene propylene rubber 85
Cross-linked polyethylene 85
Silicone rubber 95
THERMOPLASTIC COMPOUNDS  
Polyvinyl chloride (general purpose) 60
Polyvinyl chloride (heat resisting quality) 75
OTHER MATERIALS  
Mineral 95

Note 1. Silicone rubber and mineral insulation may be used for higher temperatures (to 150°C for silicone rubber, unlimited for mineral insulation) when installed where they are not liable to be touched by ship's personnel. Proposals to employ these higher temperatures will be specially considered.

Note 2. The temperature of the conductor is the combination of ambient temperature and temperature rise due to load.

Table 2.2.2 General purpose rubber and PVC

Nominal Current rating
cross-section (Based on ambient temp. 40°C)
  Single core 2 core 3 or 4 core
mm2 amperes amperes amperes
1 9 8 7
1,5 14 12 9
2,5 20 16 14
       
4 25 22 17
6 33 29 23
10 46 39 32
       
16 62 53 43
25 82 69 56
35 100 85 70
       
50 121 102 84
60 138 115 97
70 155 132 108
       
95 190 161 132
120 219 185 153
150 253 215 177
       
185 288 244 201
240 336 283 234
300 385 328 269
       
  d.c. a.c. d.c. a.c. d.c. a.c.
400 449 437 380 374 316 311
500 518 495 437 420 363 345
625 598 541 506 432 414 380

Table 2.2.3 Heat resisting PVC

Nominal Current rating
cross-section (Based on ambient temp. 40°C)
  Single core 2 core 3 or 4 core
mm2 amperes amperes amperes
1 14 12 10
1,5 18 15 13
2,5 26 22 18
       
4 35 29 24
6 44 38 31
10 62 53 43
       
16 82 69 57
25 108 93 77
35 135 113 95
       
50 162 137 113
60 189 162 135
70 205 174 144
       
95 248 211 174
120 292 248 205
150 335 286 232
       
185 378 324 265
240 448 383 313
300 513 436 359
       
  d.c. a.c. d.c. a.c. d.c. a.c.
400 616 605 524 513 432 421
500 702 670 594 572 491 470
625 799 724 680 616 562 508

Table 2.2.4 Butyl

Nominal Current rating
cross-section (Based on ambient temp. 40°C)
  Single core 2 core 3 or 4 core
mm2 amperes amperes amperes
1 16 13 11
1,5 20 17 14
2,5 28 24 19
       
4 37 32 27
6 48 41 34
10 67 57 47
       
16 90 76 63
25 118 96 82
35 150 127 105
       
50 177 150 123
60 198 171 139
70 230 196 161
       
95 278 235 195
120 321 273 225
150 364 310 255
       
185 417 355 292
240 492 417 345
300 567 482 396
       
  d.c. a.c. d.c. a.c. d.c. a.c.
400 653 631 556 535 455 444
500 739 685 631 589 519 482
625 845 739 728 621 589 514

Table 2.2.5 Ethylene propylene rubber, crosslinked

Nominal Current rating
cross-section (Based on ambient temp. 40°C)
  Single core 2 core 3 or 4 core
mm2 amperes amperes amperes
1 17 14 12
1,5 21 18 15
2,5 30 24 20
       
4 40 34 28
6 51 42 35
10 71 60 50
       
16 95 81 67
25 127 108 89
35 154 127 106
       
50 191 164 133
60 212 180 148
70 239 202 166
       
95 292 248 205
120 339 294 237
150 387 329 270
       
185 440 373 307
240 519 441 364
300 594 505 416
       
  d.c. a.c. d.c. a.c. d.c. a.c.
400 689 668 583 572 482 466
500 784 731 668 625 551 509
625 901 774 763 657 625 541

Table 2.2.6 Silicone rubber, mineral

Nominal Current rating
cross-section (Based on ambient temp. 40°C)
  Single core 2 core 3 or 4 core
mm2 amperes amperes amperes
1 21 18 15
1,5 25 21 18
2,5 34 38 23
       
4 44 38 30
6 58 49 36
10 79 67 55
       
16 105 89 74
25 142 121 99
35 173 147 121
       
50 210 184 152
60 242 205 168
70 268 228 188
       
95 325 278 226
120 378 320 263
150 431 368 301
       
185 494 420 345
240 599 509 420
300 693 588 483

2.21 Correction factors for current rating

2.21.1  Ambient temperature. When it is known that the ambient temperature is different from that given in Pt 6, Ch 2, 1.5 Ambient temperatures, correction factors shown in Table 2.2.7 Correction factors for ambient are to be applied.

Table 2.2.7 Correction factors for ambient

Insulation Correction factor for ambient temperature
40°C 45°C 50°C 55°C
Rubber or PVC (general purpose) 1,00 0,87 0,71
PVC (heat-resisting quality) 1,00 0,93 0,84 0,76
Butyl rubber 1,00 0,93 0,84 0,80
Ethylene propylene rubber, cross linked polyethylene 1,00 0,94 0,89 0,82
Mineral, silicone rubber 1,00 0,95 0,90 0,85

2.21.2  Intermittent service. Where the load is intermittent, the correction factors in Table 2.2.8 Correction factors for intermettent may be applied for half hour and one hour ratings. In no case is a shorter rating than one half hour rating to be used, whatever the degree of intermittency.

Table 2.2.8 Correction factors for intermettent

Correction factor Half-hour rating One hour rating
With metallic sheath Without metallic sheath With metallic sheath Without metallic sheath
  mm2 mm2 mm2 mm2
1,0 Up to 20 Up to 75 Up to 67 Up to 230
1,1 21 – 40 76 – 125 68 – 170 231 – 400
1,15 41 – 65 126 – 180 171 – 290 401 – 600
1,2 66 – 95 181 – 250 291 – 430
1,25 96 – 130 251 – 320 431 – 600
1,3 131 – 170 321 – 400
1,35 171 – 220 401 – 500
1,4 221 – 270

2.22 Arrangement of cables

2.22.1 Cables having insulating materials with different maximum-rated conductor temperatures are not to be bunched together, or where this is not practicable, the cables are to be so operated that no cable reaches a temperature higher than that permitted for the lowest temperature-rated cable in the group.

2.23 Connections between entrained ships

2.23.1 Cables are to be suitable for use in the connections between entrained ships, i.e. are to be flexible, robust and of commensurate cross-section area.

2.23.2 The connection is to include provisions for the continuity of out-of-balance or earth-fault current return. The connecting device is to include provisions to ensure that this circuit is closed before, and opened after, the live circuits.

2.23.3 Terminal plugs and sockets, if used, are to be so arranged that any exposed pins cannot be energized, see Pt 6, Ch 2, 10.3 Socket outlets and plugsfor additional requirements.

2.23.4 Where hull-return systems are used, hull polarity is to be compatible.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.