8.1.1 All Class
I and II pipes and their associated fittings are to be tested by hydraulic
pressure to the Surveyor’s satisfaction. Further, all steam,
feed, compressed air and fuel oil pipes, together with their fittings,
are to be similarly tested where the design pressure is greater than
7,0 bar. The test is to be carried out after completion of manufacture
and before installation on board and where applicable, before insulating
and coating.
8.1.4 Valves
and fittings non-integral with the piping system, intended for Classes
I and II, are to be tested in accordance with Recognised Standards,
but to not less than 1,5 times the design pressure. Where design features
are such that modifications to the test requirements are necessary,
alternative proposals for hydraulic tests are to be submitted for
special consideration.
8.1.5 All valves
are to be tested for tightness at 1,1 times the maximum permissible
working pressure.
8.1.7 In no
case is the membrane stress to exceed 90 per cent of the yield stress
at the testing temperature.