Section 
                     13 Testing, marking and surveys
                  
                  
                  
                  
                  
                  
                  
                     
                        
                         
                        13.1 Testing
                        
                        
                        
                        
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                           
                              
                              
                              13.1.4 The test procedure and test loads are to be submitted to the responsible LR plan
                                 appraisal office for approval.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.5 Testing and examination shall be carried out in accordance with the requirements of
                                 this sub-Section and the agreed Inspection and Test Plan (ITP).
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              13.1.7 For A-GU type systems (providing unrestricted access) the initial overload tests and
                                 subsequent periodical overload tests are to be carried out using the test loads as
                                 defined in the following:
                                  
                                    - A-GU gangway integrity test 
                                       
                                       
The test load shall be applied uniformly along the completely extended
                                          gangway with the test load per square metre defined as follows: 
                                        
                                       
                                       
                                       
                                       
                                       
                                       where 
                                       
                                       
                                       
                                       FT = 1,5 = test load
                                          factor
                                        
                                       
                                       
                                       UDLP = 360
                                          kg/m2 
                                       
                                       
                                       This integrity test is only required
                                          at the initial survey; the test may be carried out at the manufacturer's
                                          works and does not need to be repeated on board.
                                        
                                       
                                     
                                    - A-GU system test
                                       
                                          - For A-GU type systems which are not
                                             designed to carry personnel in the cantilevered position, the test
                                             load is to be applied uniformly along the completely extended
                                             gangway with the test load per square metre defined as follows:
                                             
                                             
                                             
                                             
                                             
where 
                                             
                                             
                                             TLA-GU.b.i.l = test load, in
                                                kg/m2 
                                             
                                             
                                             FT = 1,5 = test
                                                load factor
                                              
                                             
                                             
                                             g = 9,81
                                                kg/m2 
                                             
                                             
                                             Wgw =
                                                total dead load of the gangway, in kg 
                                              
                                             
                                             
                                             Lgw = length of gangway from heel to tip,
                                                in m
                                              
                                             
                                             
                                             Bgw = effective width
                                                of gangway (see
                                                Ch  1,  1.10 Terms and definitions 1.10.9 for a
                                                definition of the effective width), in m
                                              
                                             
                                             
                                             Alternatively, the test load may be applied at the gangway tip
                                                and is defined as follows:
                                              
                                             
                                             
                                             
                                             
                                             
                                             where 
                                             
                                             
                                             TLA-GU.b.i.2 = alternative test load, in
                                                kg
                                              
                                             
                                             
                                             The designer/manufacturer needs to
                                                evaluate whether it can be ensured that the gangway cannot be
                                                used in the cantilevered position. If this cannot be ensured the
                                                system needs to be designed and tested as a cantilevered system
                                                as defined in Ch  1,  13.1 Testing 13.1.7.(b).(i).
                                                
                                              
                                             
                                           
                                          - For A-GU type systems which are
                                             designed to carry personnel in the cantilevered position, the test
                                             loads are to be applied at the gangway tip and are defined as
                                             follows:
                                             
                                             
                                             
where 
                                             
                                             
                                             TLA-GU.b.ii.1 = test load, in kg
                                              
                                             
                                             
                                             Alternatively, the test loads may be applied
                                                uniformly along the completely extended gangway with the test
                                                load per square metre defined as follows:
                                                 
                                              
                                             
                                             
                                             where 
                                             
                                             
                                             TLA-GU.b.ii.2 = alternative test load, in
                                                kg/m2 
                                             
                                             
                                             If the test load
                                                TLA-GU.b.ii.2 is chosen to be applied
                                                along the completely extended gangway, the test as defined in
                                                Ch  1,  13.1 Testing 13.1.7.(a) may be
                                                omitted.
                                              
                                             
                                           
                                        
                                       
                                       
                                       The gangway shall be in the cantilevered position in
                                          both cases (i) and (ii) during the overload test.
                                        
                                       
                                     
                                  
                                 
                               
                              
                              
                              
                              
                                 
                                 
                                 
                                    Table 1.13.1 Test loads – Overview
                                    
                                       
                                          
                                             | Type of load test
                                                
                                              | 
                                             OPTS designed to carry personnel in cantilevered
                                                position
                                                
                                              | 
                                             A-GU
                                                
                                                  (Access - Gangway Unrestricted) 
                                                see Note
                                                1
                                                
                                              | 
                                             A-GR
                                                
                                                  (Access - Gangway Restricted) 
                                                see Note
                                                1
                                                
                                              | 
                                           
                                          
                                             | Gangway integrity test (A-GU only) 
                                                
                                              | 
                                             ---
                                                
                                              | 
                                             TLA-GU.a =
                                                FTUDLP
                                                see Note 2
                                                
                                              | 
                                             ---
                                                
                                              | 
                                           
                                          
                                             | OPTS test
                                                
                                              | 
                                             No
                                                
                                              | 
                                              
                                                see Note 2
                                                
                                                or 
                                                
                                                
                                                 
                                                   see Note 3
                                                 
                                                
                                                
                                              | 
                                             ---
                                                
                                              | 
                                           
                                          
                                             | Yes
                                                
                                              | 
                                              
                                                see Note 4
                                                
                                                or 
                                                
                                                
                                                 
                                                   see Note 5
                                                 
                                                
                                                
                                              | 
                                              
                                                see Note 4
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             
                                                
                                                Note 1: 
                                                    
                                                      - Test load factor: FT = 1,25 for
                                                         A-GR systems and FT = 1,5 for A-GU
                                                         systems 
                                                      
 
                                                      - Uniformly Distributed Load – Personnel:
                                                         UDLP = 360 kg/m2
                                                         
                                                      
 
                                                      - Total dead load of the gangway, in kg:
                                                         Wgw
                                                         
                                                      
 
                                                      - Length of gangway from heel to tip, in m:
                                                         Lgw
                                                         
                                                      
 
                                                      - Effective width of gangway, in m:
                                                         Bgw: 
                                                      
 
                                                      - Safe Working Load – Personnel, in kg:
                                                         SWLP
                                                         
                                                      
 
                                                      - Safe Working Load – Cargo on Gangway,
                                                         in kg: SWLCG: 
                                                      
 
                                                    
                                                   
                                                 
                                                
                                                
                                                Note 2: The test load shall be applied uniformly along the
                                                   completely extended gangway.  
                                                 
                                                
                                                
                                                Note 3: Alternatively, the test load may be applied at the
                                                   gangway tip. 
                                                 
                                                
                                                
                                                Note 4: The test load shall be applied at the gangway tip. 
                                                 
                                                
                                                
                                                Note 5: Alternatively, the test load may be applied uniformly
                                                   along the completely extended gangway. 
                                                 
                                                
                                                
                                                
                                              | 
                                           
                                       
                                     
                                    
                                  
                                 
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.8 For A-GR type systems (providing restricted access) the initial overload test and
                                 subsequent periodical overload tests are to be carried out applying the overload
                                 test load as defined in the following at the gangway tip:
                                  
                               
                              
                              
                              
                              where
                                  
                                    
                                       
                                          | 
                                                   TLA-GR | 
                                          = | 
                                          test load, in kg | 
                                        
                                       
                                          | 
                                                   FT | 
                                          = | 
                                          1,25 = test load factor | 
                                        
                                       
                                          | 
                                                   Wgw | 
                                          = | 
                                          total dead load of the gangway, in kg  | 
                                        
                                       
                                          | 
                                                   SWLP | 
                                          = | 
                                          safe working load, personnel, in kg  | 
                                        
                                       
                                          | 
                                                   SWLCG | 
                                          = | 
                                          safe working load, cargo on gangway, in kg | 
                                        
                                     
                                  
                                 
                               
                              
                              
                              
                              The gangway shall be in the cantilevered position during the overload test. 
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              13.1.10 Overload test loads deviating from the above will be specially considered. 
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              13.1.12 During overload testing of the OPTS all its possible operating motions
                                 (e.g. slewing, telescoping) are to be carried out at low speed. The load test shall
                                 extend over all operational modes and configurations of the system. Any motion
                                 compensation system (MCS) is only to be engaged during overload testing in case the
                                 MCS of the OPTS has been designed to withstand the test loads as indicated in Ch  1,  13.1 Testing 13.1.7 and Ch  1,  13.1 Testing 13.1.8 in order to avoid overloading the
                                 MCS while being tested. The application duration of the test load shall be twice as
                                 long as the time required to move the OPTS from its stowage position to the target
                                 structure (considering a fully completed landing operation). Alternative durations
                                 of the application of test loads will be specially considered. The overload testing
                                 needs to be carried out on board the mothership. The overall displacement of the
                                 OPTS due to the applied overload shall be measured at the gangway tip and shall be
                                 less than the displacement limits as defined in Table 1.5.1 Displacements limits. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.13 The OPTS is further to be tested with its SWLP and/or
                                 UDLP and SWLCG being applied under all
                                 design working conditions at maximum related design speeds and with any motion
                                 compensation system activated and also de-activated. Both passive and active
                                 compensation modes (if any) shall be tested. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.14 The OPTS shall be subjected to a full functional testing regime for
                                 normal operation during the initial survey ( see
                                 Ch  1,  13.3 Initial survey of new installations), covering
                                 the following items as a minimum: 
                                  
                                    - electrical systems (including failure testing according to an
                                       approved test schedule derived from the FMEA); 
                                    
 
                                    - control systems (including failure testing according to an
                                       approved test schedule derived from the FMEA); 
                                    
 
                                    - communication systems; 
 
                                    - safety systems; 
 
                                    - limit switches; 
 
                                    - monitoring systems (if applicable); 
 
                                    - landing arrangements and systems; and 
 
                                    - slewing, telescoping and luffing arrangements and systems. 
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.15 The OPTS shall be subjected to a full functional testing regime for
                                 emergency events during the initial survey ( see
                                 Ch  1,  13.3 Initial survey of new installations), covering
                                 the following items as a minimum: 
                                  
                                    - overload protection systems; 
 
                                    - alarm systems; 
 
                                    - emergency disconnection (lift-off) systems; 
 
                                    - emergency retraction/disconnection systems; 
 
                                    - emergency systems; 
 
                                    - redundant and redundancy systems and arrangements; and 
 
                                    - emergency stop. 
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.16 The functional test during the initial survey ( see
                                 Ch  1,  13.3 Initial survey of new installations) shall
                                 extend to cover the motion compensation system either by: 
                                  
                                    - Testing by simulation, under the following conditions: 
                                       
                                          - The motion compensation system may be tested by
                                             factory-based simulation, if it can be demonstrated that the
                                             simulation will not fall short of the dynamic loading and behaviour
                                             of the OPTS supporting mothership. 
                                          
 
                                          - The whole range and location of possible loads
                                             (UDLP, SWLP,
                                             SWLCG) shall be taken into consideration in
                                             the simulation. 
                                          
 
                                          - It shall further be demonstrated that the motion
                                             compensation performance can also be properly tested. 
                                          
 
                                          - The system shall be tested taking account of the
                                             maximum significant wave height the OPTS is required to perform
                                             under.
                                          
 
                                        
                                       
                                       
                                     
                                    - Testing in open sea conditions: 
                                       
                                          - The motion compensation system may be tested in open
                                             sea conditions. 
                                          
 
                                          - The whole range and location of possible loads
                                             (UDLP, SWLP,
                                             SWLCG) shall be taken into consideration in
                                             the open sea testing. 
                                          
 
                                          - The system shall be tested taking account of the maximum
                                             significant wave height the OPTS is required to perform under. 
                                          
 
                                        
                                       
                                     
                                  
                                 
                               
                              
                              
                              
                               The test results are required to be recorded and documented. Alternative testing
                                 methods will be specially considered.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.17 Load testing (including any SWLP and/or
                                 UDLP and SWLCG tests) and functional testing
                                 shall be carried out without persons on the OPTS and/or gangway. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.18 No persons shall be in the hazardous zone around the OPTS which will be affected by a
                                 failure of the OPTS during the load and functional testing. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.19 After functional, SWLP and/or UDLP
                                 and SWLCG (as applicable) and overload testing, the OPTS is to be
                                 thoroughly examined for deformations or other defects. 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.1.20 The load testing of the OPTS is to be repeated in the following circumstances using
                                 the approved test loads and procedures as defined in the above: 
                                  
                                    - Following any structural repair, alteration or re-erection of the
                                       appliances; 
                                    
 
                                    - at every fifth Annual Thorough Examination; and 
 
                                    - in accordance with the requirements of the National Administration.
 
                                  
                                 
                               
                              
                              
                            
                           
                           
                           
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.2 Marking
                        
                        
                        
                        
                           
                           
                           
                           
                           
                              
                              
                              13.2.2 Each OPTS is to be clearly and permanently marked at the Operator's
                                 control station with a minimum of the following information:
                               
                              
                              
                              
                                 - designer/manufacturer;
 
                                 - product name;
 
                                 - SWLP and/or UDLP and
                                    SWLCG, ideally with a pictogram showing the location of
                                    application of the operational loads;
                                 
 
                                 - access type (unrestricted/uncontrolled or restricted/controlled);
 
                                 - maximum number of persons on the waiting platform (if any);
 
                                 - maximum number of persons simultaneously allowed anywhere on the gangway (for
                                    restricted access);
                                 
 
                                 - any restrictions or limitations of safe operation;
 
                                 - minimum and maximum operational design luffing/inclination angles;
 
                                 - minimum and maximum length considering the telescopic extension;
 
                                 - stowage configuration and arrangement;
 
                                 - manufacturing date;
 
                                 - an identification mark to enable the system to be readily related to its
                                    appropriate test and certification or classification certificate; and
                                 
 
                                 - with the mark of the Surveyor who witnessed the load and functional
                                    testing.
                                 
 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.2.3 Limits of telescopic, slewing, luffing motion are to be marked on the OPTS structure
                                 (e.g. maximum and minimum gangway length, range of gangway inclination, etc.).
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.2.4 Each OPTS shall be clearly and permanently marked with at least the following
                                 information at the waiting area and on each end of the gangway:
                               
                              
                              
                              
                                 - maximum number of persons on the waiting platform (if any);
 
                                 - maximum number of persons simultaneously allowed anywhere on the gangway (for
                                    restricted access);
                                 
 
                                 - any restrictions or limitations of safe operation;
 
                                 - emergency procedures;
 
                                 - alarms; and
 
                                 - access limitations.
 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.2.5 The marking language shall preferably be the English language.
                                 Alternatively, and depending on the requirements of the Flag or Coastal State
                                 Authorities, the language may, in addition, be that of the mothership’s crew.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.2.6 Any interface areas between moving parts shall be marked with a warning pattern in
                                 black and reflecting yellow.
                               
                              
                              
                            
                           
                           
                           
                           
                           
                           
                              
                              
                              13.2.8 The OPTS parts, components, machinery items, shall be marked with visual
                                 danger signs in accordance with a recognised National or International Standard
                                 (e.g. EN 842 Safety of machinery – Visual danger signals – General requirements,
                                    design and testing or ISO 7010 Graphical symbols – Safety colours and
                                    safety signs – Registered safety signs as considered appropriate), as
                                 applicable.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.3 Initial survey of new installations
                        
                        
                        
                        
                           
                           
                           
                           
                           
                           
                           
                           
                              
                              
                              13.3.3 The definition of critical, primary and secondary welds as given in Ch  12 Testing, Marking and Surveys, Table 12.3.1 Minimum requirements for
                                    NDE of the Code for Lifting Appliances in a Marine Environment, July 2022 are redefined as follows for the application in an OPTS:
                               
                              
                              
                              
                                 - Critical welds
                                    
 are defined as welds where the failure of which may or
                                       will result in harm to persons using the OPTS or in the partial or complete
                                       loss of the OPTS, e.g. foundation/deck welds, slewing bearing/pedestal
                                       welds, base frame welds, main gangway structural welds, walkway support
                                       structural welds, waiting platform support structural welds, etc.
                                     
                                    
                                  
                                 - Primary welds
                                    
 are defined as welds directly applicable to floorings,
                                       ladders, walkways, waiting platforms, handrails, suspended baskets,
                                       personnel containments, etc.
                                     
                                    
                                  
                                 - Secondary welds
                                    
 are defined as non-critical and non-primary load-path
                                       member welds (as defined under (a) and (b)) and/or which are not involved in
                                       the prevention of harm to persons using the OPTS, e.g. service fittings
                                       (e.g. electrical, lighting), maintenance equipment, etc.
                                     
                                    
                                  
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.3.4 If the OPTS includes a slewing bearing in its design, initial bearing clearances
                                 shall be recorded by means of a rocking test after the initial proof load test. The
                                 rocking test shall be repeated annually in accordance with the slewing bearing
                                 manufacturer’s recommendations. Acceptable tolerances shall be as per slewing
                                 bearing manufacturer’s recommendations.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.3.5 The control system shall be subjected to failure testing according to an approved
                                 test schedule derived from an approved FMECA.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.4 Initial Survey of existing installations
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.5 Periodical thorough examinations
                        
                        
                        
                        
                           
                           
                           
                           
                           
                           
                           
                           
                              
                              
                              13.5.3 The interval for the thorough examination required for the OPTS and all associated
                                 gear and machinery engaged in personnel transfer operations is six months.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.5.4 The periodical thorough examination of the electrical arrangements shall be carried
                                 out at the following intervals:
                               
                              
                              
                              
                                 - annual visual inspection of cabling and equipment;
 
                                 - annual examination of the earthing arrangements;
 
                                 - annual visual examination of motors;
 
                                 - five-yearly insulation tests of cabling and motors; and
 
                                 - five-yearly testing of main circuit breakers (power supply).
 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.5.5 The periodical thorough examination of the control arrangements shall be carried out
                                 at the following intervals:
                               
                              
                              
                              
                                 - annual simulation testing of highly critical failures (as identified in the
                                    FMECA);
                                 
 
                                 - five-yearly testing of the approved test schedule derived from the approved
                                    FMECA;
                                 
 
                                 - five-yearly testing of safety systems (e.g. emergency stop);
 
                                 - five-yearly testing of alarms;
 
                                 - five-yearly testing of sensors related to operational limits; and
 
                                 - five-yearly overload testing of the OPTS.
 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.5.6 The detailed requirements for the thorough examination of the OPTS and
                                 associated loose gear are given in Table 1.13.2 6-Monthly thorough examination of OPTS.
                               
                              
                              
                              
                              
                                 
                                 
                                 
                                    Table 1.13.2 6-Monthly thorough examination of OPTS
                                    
                                       
                                          
                                             | Item
                                                 | 
                                             Survey
                                                 | 
                                           
                                          
                                             | 0.
                                                General
                                                
                                              | 
                                             (a) The
                                                following requirements for the 6-monthly thorough examination of
                                                the OPTS shall be applied as applicable and as far as possible
                                                depending on the actual design of the OPTS.
                                                
                                                 (b) If the design
                                                   is novel or deviating from the requirements in this Code the
                                                   scope of the thorough examination might need to be extended
                                                   to cover the essential items of the actual OPTS.
                                                 
                                                
                                                
                                                (c)
                                                   The thorough examination shall take into account
                                                   designer’s/manufacturer’s maintenance and inspection
                                                   instructions and recommendations.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 1.
                                                Certification
                                                
                                              | 
                                             (a) Check
                                                that certification issued by a competent body, exists for the
                                                OPTS to be examined.
                                                
                                                 (b) Check the Register and/or the OPTS
                                                   initial and periodical thorough examination documentation
                                                   for any outstanding endorsements, recurring problems,
                                                   down-ratings, etc. 
                                                 
                                                
                                                
                                                If there is no evidence that the
                                                   OPTS has ever been certified, the thorough examination is to
                                                   be declined and LR’s certification services for existing
                                                   OPTS may be offered.
                                                 
                                                
                                                
                                                (c) Check the Register for any
                                                   repairs or modifications.
                                                 
                                                
                                                
                                                 (d) Check the maintenance
                                                   records.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 2.
                                                Arrangements
                                                
                                              | 
                                             Check reeving arrangement are as shown in Rigging
                                                Plan or designer’s/manufacturer’s manual. Check that the
                                                arrangement of hydraulic cylinders (if applicable) is as shown
                                                on the reeving diagram or appropriate plans.
                                                
                                              | 
                                           
                                          
                                             | 3. Fixed
                                                sheaves, axle pins and housings
                                                
                                              | 
                                             (a)
                                                Determine that the sheaves are free from cracks. The extent of
                                                the examination is to be such that a reliable judgement can be
                                                made. Depending on access, it may be necessary to dismantle the
                                                item.
                                                
                                                 (b) Survey rope groove for scoring or uneven
                                                   wear.
                                                 
                                                
                                                
                                                (c) Check that lubrication arrangements are in
                                                   working order.
                                                 
                                                
                                                
                                                (d) Check security (keep plates, cotter
                                                   pins, etc.) of fixed axle pins.
                                                 
                                                
                                                
                                                (e) Check for free
                                                   rotation of sheave on axle pin.
                                                 
                                                
                                                
                                                (f) Check for
                                                   excessive wear of axle pin and sheave bush.
                                                 
                                                
                                                
                                                (g) Check
                                                   condition of housing and separation plates and for signs of
                                                   ovality in the pin holes.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 4. Gangway heel pins and other pins in the main
                                                load-path
                                                
                                              | 
                                             (a) Check
                                                lubrication for detrimental wear.
                                                
                                                 (b) Check security (keep
                                                   plates, cotter pins, castle nuts, etc.) of heel
                                                   pins.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 5. Slewing
                                                rings for OPTS 
                                                
                                              | 
                                             (a) Listen to the bearing during slewing motion for
                                                any untoward noises. Also note the age of the bearing or its
                                                operational hours (if possible) and check against guidance in
                                                designer’s/manufacturer’s maintenance manual. Older bearings
                                                will be more prone to problems.
                                                
                                                 (b) Check any
                                                   maintenance records for evidence of regular routine
                                                   maintenance.
                                                 
                                                
                                                
                                                (c) Check condition and
                                                   tightness (using a method recommended by the manufacturer)
                                                   of inner and outer bearing bolts, removing any protective
                                                   caps if fitted. Sample bolts may be removed at the
                                                   discretion of the Surveyor to check for the possibility of
                                                   stress corrosion cracking.
                                                 
                                                
                                                
                                                (d) Review the
                                                   results of the latest rocking test measurements and grease
                                                   sample analysis carried out in accordance with the
                                                   designer’s/manufacturer’s recommendations and check the
                                                   recommended limits for either wear or metallic particle
                                                   content are not being exceeded. This will give an indication
                                                   of the wear in the bearing.
                                                 
                                                
                                                
                                                These tests
                                                   are usually carried out annually.
                                                 
                                                
                                                
                                                (e)
                                                   Check the effectiveness of lubrication of the bearing.
                                                 
                                                
                                                
                                                (f) Additional inspections are to be carried
                                                   out where these are specified by the OPTS or slew ring
                                                   manufacturer.
                                                 
                                                
                                                
                                                (g) In case the OPTS is
                                                   also designed and used as a conventional offshore crane the
                                                   requirements of Ch  12 Testing, Marking and Surveys, Table 12.3.6 Annual Thorough Examination of
                                                      cranes (incuding derrick cranes) and launch and recovery systems for diving
                                                      operations, clause 6
                                                   of the Code for Lifting Appliances in a Marine Environment, July 2022 are
                                                   required to be complied with.
                                                 
                                                
                                                
                                                (h) Any
                                                   requirements of National Authority (i.e. Flag State) and/or
                                                   Coastal State Authorities are required to be complied
                                                   with.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 6. Wire
                                                ropes
                                                
                                              | 
                                             (a) Confirm that appropriate wire ropes
                                                certificates are on board (LA.4 or equivalent).
                                                
                                                 (b) Check the general condition of ropes by examining as
                                                   much of their length as is possible.
                                                 
                                                
                                                
                                                (c)
                                                   Check for broken or worn wires. Check for any signs of
                                                   internal and external corrosion. Check for changes in rope
                                                   diameter. Check for signs of damage and deformation (e.g.
                                                   kinks, birdcaging, etc.), or of thermal damage. In general,
                                                   the rope is to be replaced immediately, if any of the
                                                   discard criteria in ISO 4309 Cranes – Wire ropes – Care
                                                      and maintenance, inspection and discard are
                                                   exceeded.
                                                 
                                                
                                                
                                                (d) Inspect rope terminations,
                                                   splices, end fittings, etc. with particular attention to
                                                   broken wires at ferrule connections. Any serving on splices
                                                   is to be removed for the examination.
                                                 
                                                
                                                
                                                (e)
                                                   Liverpool splices are to be rejected on any rope where the
                                                   ends are not secured against rotation.
                                                 
                                                
                                                
                                                (f)
                                                   Before re-rigging ensure that the wire rope has been
                                                   lubricated.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 7.
                                                Structure and general
                                                
                                              | 
                                             (a) Check structural bolts for tightness. Where
                                                bolts have been replaced, they are to be of the same type, size
                                                and quality as previously fitted.
                                                
                                                 (b) Check
                                                   pedestal and foundation bolts for signs of corrosion and
                                                   flange distortion.
                                                 
                                                
                                                
                                                (c) Check main welds
                                                   for cracks. Initially by visual examination but NDE can be
                                                   used at the Surveyor’s discretion.
                                                 
                                                
                                                
                                                (d)
                                                   Check welds between pedestal/foundation and the mothership.
                                                   Initially by visual examination but NDE can be used at the
                                                   Surveyor's discretion.
                                                 
                                                
                                                
                                                (e) Inspect the
                                                   structure for condition of coating. Inspect the structure
                                                   for corrosion, removing paint and carrying out hammer tests
                                                   as necessary. If considered necessary, the thickness of
                                                   structural items is to be checked by ultrasonic testing or
                                                   other suitable methods that do not affect the material or
                                                   condition of the structure.
                                                 
                                                
                                                
                                                (f) Check
                                                   base frame, gangway, walkways, guard rails, handrails,
                                                   stanchions, supporting pedestal (or foundation), for any
                                                   signs of damages, local indentations, buckling, cracks or
                                                   unfairness. Particular attention is to be given to
                                                   connections of chords and lattices, hydraulic cylinder
                                                   connections, sheave housing attachments, gangway tip, and
                                                   other areas where there is significant load input.
                                                 
                                                
                                                
                                                (g) Check connection between gangway, guard
                                                   rails, handrails and stanchions.
                                                 
                                                
                                                
                                                (h)
                                                   Check connection of flooring elements with the supporting
                                                   structure. Flooring elements and other parts in way of the
                                                   walking area shall not pose a tripping hazard.
                                                 
                                                
                                                
                                                (i) Check whether the gaps between moving parts
                                                   are not excessive posing a crushing hazard.
                                                 
                                                
                                                
                                                (j) Check sea-fastening/stowage arrangements
                                                   (if applicable).
                                                 
                                                
                                                
                                                (k) Check other items
                                                   reflecting the intension of the above list or similar to the
                                                   above consideration the actual design of the
                                                   OPTS.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 8.
                                                Shackles, links, rings, etc.
                                                
                                              | 
                                             (a) Check loose gear items, can be identified
                                                against appropriate certificates (LA.3 or equivalent).
                                                
                                                 (b) Examine under proper conditions and check
                                                   for cracks, deformation, wear, wastage or other defects.
                                                   Items are to be free from paint, grease, scale, etc.
                                                 
                                                
                                                
                                                (c) Confirm that the material is recorded on the
                                                   test certificate. The certificate should distinguish between
                                                   mild steel, higher tensile steel and alloy steel.
                                                 
                                                
                                                
                                                (d) Deformed shackles or shackle pins shall be
                                                   replaced.
                                                 
                                                
                                                
                                                (e) If the shackle pin is
                                                   renewed, the whole shackle is to be re-tested and
                                                   certified.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 9.
                                                Chains
                                                
                                              | 
                                             (a) Confirm appropriate chain certificates on board
                                                (LA.3 or equivalent).
                                                
                                                 (b) The chain is to be
                                                   taken to a suitably equipped workshop for examination and
                                                   examined after removal of paint, grease, scale, etc. and
                                                   wire brushing.
                                                 
                                                
                                                
                                                (c) Check for deformation,
                                                   wear or other defects. If links require renewal, the chain
                                                   is to be suitably heat treated and re-tested. Replacement
                                                   links are to be of equivalent material and strength to the
                                                   original.
                                                 
                                                
                                                
                                                (d) Confirm that material is
                                                   recorded on test certificate. The certificate should
                                                   distinguish between mild steel, higher tensile steel and
                                                   alloy steel.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 10. Rope
                                                drums
                                                
                                              | 
                                             (a) At
                                                least three turns of wire rope are to remain on the drum. 
                                                
                                                 (b)
                                                   Check the effectiveness of wire rope anchorages.
                                                 
                                                
                                                
                                                (c)
                                                   Check drum for cracks and for defects liable to damage the
                                                   rope.
                                                 
                                                
                                                
                                                (d) Check the effective working of any fleeting
                                                   device fitted.
                                                 
                                                
                                                
                                                (e) Check drum flanges for bending or
                                                   distortion. This is particularly appropriate for multi-layer
                                                   spooling drums.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 11.
                                                Hydraulic arrangements
                                                
                                              | 
                                             (a) Check hydraulic hoses, pipes, couplings,
                                                actuators, filters, valves, measuring devices, control blocks
                                                and other hydraulic components for leakage and/or damage.
                                                
                                                 (b) Check hydraulic pumps and motors for
                                                   leakage and/or damage.
                                                 
                                                
                                                
                                                (c) Check hydraulic
                                                   accumulators for leakage, deformation and/or other
                                                   damage.
                                                 
                                                
                                                
                                                (d) Check pre-fill pressure of
                                                   the hydrogen bottles, as applicable.
                                                 
                                                
                                                
                                                (e)
                                                   Check for correct oil levels.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 12.
                                                Hydraulic cylinders, winches, etc. and attachments
                                                
                                              | 
                                             (a) Check condition of machinery systems.
                                                
                                                 (b) Check for leaks and condition of hydraulic
                                                   pipes and couplings.
                                                 
                                                
                                                
                                                (c) Check piston rod
                                                   for scoring and signs of deformation.
                                                 
                                                
                                                
                                                (d)
                                                   Check end pivot pins and bearings for any excessive wear and
                                                   deformation, and the security of the pins.
                                                 
                                                
                                                
                                                (e) Check that mounting brackets are free from deformation,
                                                   cracks or damage.
                                                 
                                                
                                                
                                                (f) Check safety
                                                   systems, such as limit switches and slack rope detection
                                                   systems.
                                                 
                                                
                                                
                                                (g) Check fasteners, pins, gear
                                                   boxes, shafts, bearings, lubrication, etc.
                                                 
                                                
                                                
                                                (h) Check condition of brake (e.g. pads, brake
                                                   linings).
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 13.
                                                Electrical and control arrangements
                                                
                                              | 
                                             (a) Check the Operator station and other operating
                                                arrangements for suitable condition.
                                                
                                                 (b) Check
                                                   operation of audible and visual warnings.
                                                 
                                                
                                                
                                                (c) Check electrical arrangements in general and cabling
                                                   for state and secure connection.
                                                 
                                                
                                                
                                                (d)
                                                   Check effectiveness of limit switches.
                                                 
                                                
                                                
                                                (e) Check condition of electric motors. 
                                                
                                                
                                                (f) Check OPTS for safe operational behaviour as required
                                                   by the instructions for use.
                                                 
                                                
                                                
                                                (g) Conduct
                                                   earthing test, e.g. megger test.
                                                 
                                                
                                                
                                              | 
                                           
                                          
                                             | 14.
                                                Re-testing
                                                
                                              | 
                                             (a) Loose
                                                gear is to be proof tested if repairs have been carried out
                                                which affect its strength or if certificates are not
                                                available.
                                                
                                                 (b) Re-testing of the OPTS is necessary at
                                                   five-yearly intervals and after repairs or modifications
                                                   have been carried out affecting the strength or otherwise as
                                                   required by the Surveyors. The test is to demonstrate
                                                   satisfactory operation, efficiency of overload and weight
                                                   load indicators, effectiveness of limit switches,
                                                   etc.
                                                 
                                                
                                                
                                                (c) It is essential that the OPTS is operated at
                                                   each thorough examination to check gangway luffing, slewing,
                                                   telescoping and other motions as applicable, and the correct
                                                   operation of associated limit switches for such motions. In
                                                   case an overload protection system is installed such system
                                                   shall also be checked.
                                                 
                                                
                                                
                                              | 
                                           
                                       
                                     
                                    
                                  
                                 
                                 
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.6 Deferment and range of surveys
                        
                        
                        
                        
                           
                           
                           
                           
                           
                              
                              
                              13.6.2 If permitted by the Administration (Flag State) the six-monthly thorough examination
                                 date can be held within a time frame of ±3 months.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.7 Damage surveys
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.8 Design changes or modifications of existing OPTS
                        
                        
                        
                        
                           
                           
                              
                              
                              13.8.1 Design changes or modifications of an already certified or classed OPTS are required
                                 to be submitted for appraisal in order to maintain the validity of the certification
                                 or classification.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.8.2 The application of the design changes or modifications are in principle
                                 to be carried out in compliance with Ch  1,  13.3 Initial survey of new installations.
                                 The extent of the survey is to be agreed with the attending Surveyor.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.9 Classification surveys
                        
                        
                        
                        
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.10 Thorough examinations after emergency situations
                        
                        
                        
                        
                           
                           
                              
                              
                              13.10.1 Emergency situations are to be clearly defined in the instructions for use and are to
                                 be derived from the risk assessment. Emergency situations may result in loads which
                                 are beyond the certified SWLP and/or UDLP or
                                 other applicable SWL depending on the design and associated intended use.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.10.2 In case the OPTS has experienced an emergency situation a thorough examination is to
                                 be carried out in order to ensure that there are no damages or defects and that it
                                 is safe to resume normal operation.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.11 Non-permanently installed OPTS
                        
                        
                        
                        
                           
                           
                              
                              
                              13.11.1 OPTS which are not permanently installed on the mothership are required to be treated
                                 as new installations for the project phase where the OPTS is installed on the new
                                 mothership. All on-board testing related to the integration of the OPTS with the new
                                 mothership (as required by this Code, including load testing) are to be
                                 repeated.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                     
                        
                         
                        13.12 Maintenance requirements
                        
                        
                        
                        
                           
                           
                              
                              
                              13.12.1 The designer/manufacturer shall provide a detailed maintenance manual covering all
                                 components, parts and aspects of the OPTS.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.12.2 The OPTS and their components (including associated winches, hydraulic cylinders,
                                 loose gear, ropes, etc.) shall be properly maintained as per the requirements of the
                                 designer/manufacturer as stated in the maintenance manual at required intervals.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.12.3 Every OPTS is to be visually inspected once a week by the crew or Operator to ensure
                                 they are at all times ready for immediate use.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                              13.12.4 A record of maintenance should be kept for each OPTS.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                
             |