1.2.2 Sprinklers
are to be grouped into separate sections, each of which is to contain
not more than 200 sprinklers. Any section of sprinklers is not to
serve more than two decks nor be situated in more than one main vertical
zone, except where it is satisfactorily shown that the protection
of the yacht against fire will not thereby be reduced.
1.2.3 Each section
of sprinklers is to be capable of being isolated by one stop valve
only. The stop valve in each section is to be readily accessible and
its location is to be clearly and permanently indicated. Means are
to be provided to prevent the operation of the stop valves by any
unauthorised person.
1.2.4 A gauge
indicating the pressure in the system is to be provided at each section
stop valve and at a central station.
1.2.5 The sprinklers
are to be resistant to corrosion by marine atmosphere. In accommodation
and service spaces the sprinklers are to come into operation within
the temperature ranges from 68°C to 79°C, except that in locations
such as drying rooms, where high ambient temperatures might be expected,
the operating temperature may be increased by not more than 30°C
above the maximum deck head temperature.
1.2.6 A list
or plan is to be displayed at each indicating unit showing the spaces
covered and the location of the zone in respect of each section. Suitable
instructions for testing and maintenance are to be available.
1.2.7 Sprinklers
are to be placed in an overhead position and spaced in a suitable
pattern to maintain an average application rate of not less than 5
litres per square metre per minute over the nominal area covered by
the sprinklers. For this purpose, the nominal area shall be taken
as the gross horizontal projection of the area to be covered. The
use of sprinklers providing other amounts of water suitably distributed,
will be considered provided they are shown to be not less effective.
1.2.9 The tank
is to contain a standing charge of fresh water, equivalent to the
amount of water which would be discharged in one minute by the pump
referred to in Pt 17, Ch 4, 1.2 Wet pipe type 1.2.12, and
the arrangements are to provide for maintaining such air pressure
in the tank to ensure that where the standing charge of fresh water
in the tank has been used the pressure will be not less than the working
pressure of the sprinkler, plus the pressure exerted by a head of
water measured from the bottom of the tank to the highest sprinkler
in the system. Suitable means of replenishing the air under pressure
and of replenishing the fresh water charge in the tank are to be provided.
A glass gauge suitably protected is to be provided to indicate the
correct level of the water in the tank.
1.2.10 Means
are to be provided to prevent the passage of sea water into the tank.
1.2.11 An independent
power pump is to be provided solely for the purpose of automatically
continuing the discharge of water from the sprinklers. The pump is
to be brought into action automatically by the pressure drop in the
system before the standing fresh water charge in the pressure tank
is completely exhausted.
1.2.12 The
pump and the piping system are to be capable of maintaining the necessary
pressure at the level of the highest sprinkler to ensure a continuous
output of water sufficient for the simultaneous coverage of a minimum
area of the maximum width of the craft squared or 280 m2 whichever
is less, at the application rate specified in Pt 17, Ch 4, 1.2 Wet pipe type 1.2.7.
1.2.13 The
pump is to have fitted on the delivery side a test valve with a short
open-ended discharge pipe. The effective area through the valve and
pipe is to be adequate to permit the release of the required pump
output while maintaining the pressure in the system specified in Pt 17, Ch 4, 1.2 Wet pipe type 1.2.9.
1.2.14 The
sea inlet to the pump is to be, wherever possible, in the space containing
the pump and is to be so arranged that when the vessel is afloat it
will not be necessary to shut off the supply of sea water to the pump
for any purpose other than the inspection or repair of the pump.
1.2.15 The
sprinkler pump and tank are to be situated in a position reasonably
remote from any machinery space of Category `A' and not in any space
required to be protected by the sprinkler system.
1.2.17 For
yachts of not greater than 50 m Rule length and all service craft,
the sources of electrical power supply for the sea-water pump may
be fed from the main source of electrical power.
1.2.19 The
sprinkler system is to have a connection from the vessel's fire main
by way of a lockable screw-down non-return valve at the connection
which will prevent a backflow from the sprinkler system to the fire
main.
1.2.20 A test
valve is to be provided for testing the automatic alarm for each section
of sprinklers by a discharge of water equivalent to the operation
of one sprinkler. The test valve for each section is to be situated
near the stop valve for that section.
1.2.21 Means
are to be provided for testing the automatic operation of the pump,
on reduction of pressure in the system.
1.2.22 Each
section of sprinklers is to include means for giving a visual and
audible alarm signal automatically at one or more indicating units
whenever any sprinkler comes into operation. Such alarm systems are
to be such as to indicate if any fault occurs in the system. Such
units are to indicate in which section, served by the system, fire
has occurred and are to be centralised on the navigation bridge. In
addition, visible and audible alarms from the unit are to be located
in a position other than on the navigation bridge, so as to ensure
that the indication of fire is immediately received by the crew. Switches
are to be provided at one of these indicating positions, which will
enable the alarm and the indicators for each section of sprinklers
to be tested.
1.2.23 Spare
sprinkler heads are to be provided as specified in Table 4.1.1 Spares requirements. The spare sprinkler heads
are to be stowed in boxes or holders provided for that purpose, together
with a tool suitable for removing and installing sprinkler heads.
The boxes or holders are to be situated near the control valve for
the section, and are to be clearly and permanently marked to indicate
their contents.
Table 4.1.1 Spares requirements
Number of sprinkler
heads provided
|
Number of spare
sprinkler heads required
|
300
|
One spare sprinkler
head is to be provided for each 50 sprinkler heads fitted, with a minimum of
one spare being provided for each type fitted
|
301 to 1000
|
12
|
>1000
|
24
|