Section 7 Inert gas systems on Tankers of 8,000 tonnes DWT and above
Clasification Society 2024 - Version 9.40
Clasifications Register Rules and Regulations - Rules and Regulations for the Classification of Ships, July 2022 - Part 5 Main and Auxiliary Machinery - Chapter 15 Piping Systems for Oil Tankers - Section 7 Inert gas systems on Tankers of 8,000 tonnes DWT and above

Section 7 Inert gas systems on Tankers of 8,000 tonnes DWT and above

7.1 General

7.1.1 An inert gas system complying with the applicable requirements of Chapter 15 - Inert Gas Systems of theFSS Code - Fire Safety Systems – Resolution MSC.98(73) as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) , is to be fitted on tankers of 8,000 tonnes DWT and above. For purposes of classification any use of the word ”Administration” in the Regulation is to be taken as meaning LR. See Pt 5, Ch 15, 7.7 Nitrogen generator systems for additional requirements for inert gas systems utilising nitrogen.

7.1.2 Ships complying with these requirements will be eligible for the additional notation IGS in the Register Book, see Pt 1, Ch 2 Classification Regulations.

7.1.3 Throughout this Section the term `cargo tank' includes also `slop tanks'. For definition of Machinery spaces of Category `A', see SOLAS - International Convention for the Safety of Life at Sea Chapter II-2 - Construction - Fire protection, fire detection and fire extinction/ Part A - General.

7.2 Gas supply

7.2.1 The inert gas may be treated flue gas from the main or auxiliary boiler(s) gas turbine(s), or from a separate inert gas generator. In all cases, automatic combustion control, capable of producing suitable inert gas under all service conditions, is to be fitted.

7.3 Venting arrangements

7.3.1 The arrangements for the venting of all vapours displaced from the cargo tanks during loading and ballasting are to comply with Pt 5, Ch 15, 4 Cargo tank venting, purging and gas-freeing and are to consist of either one or more mast risers, or a number of high velocity vents. The inert gas supply mains may be used for such venting.

7.3.2 The arrangements for inerting, purging or gas freeing of empty tanks as required in by 2.2.1.2.1 to .3 of Chapter 15 - Inert Gas Systemsof the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) are to be such that the accumulation of hydrocarbon vapours in pockets formed by the internal structural members in a tank is minimised and that:

  1. on individual cargo tanks the gas outlet pipe, if fitted, is to be positioned as far as practicable from the inert gas/air inlet and in accordance with Pt 5, Ch 15, 4 Cargo tank venting, purging and gas-freeing. The inlet of such outlet pipes may be located either at deck level or at not more than 1 m above the bottom of the tank;

  2. the cross-sectional area of such gas outlet pipes referred to in Pt 5, Ch 15, 7.3 Venting arrangements 7.3.2 is to be such that an exit velocity of at least 20 m/s can be maintained when any three tanks are being simultaneously supplied with inert gas. Their outlets are to extend not less than 2 m above deck level;

  3. each gas outlet referred to in Pt 5, Ch 15, 7.3 Venting arrangements 7.3.2.(b) is to be fitted with suitable blanking arrangements;

7.3.3 One or more pressure-vacuum breaking devices are to be provided to prevent the cargo tanks from being subject to:

  1. a positive pressure in excess of the test pressure of the cargo tank if the cargo were to be loaded at the maximum rated capacity and all other outlets were left shut; and

  2. a negative pressure in excess of 700 mm water gauge if cargo were to be discharged at the maximum rated capacity of the cargo pumps and the inert gas blowers were to fail.

Such devices shall be installed on the inert gas main unless they are installed in the venting system required by Pt 5, Ch 15, 4 Cargo tank venting, purging and gas-freeing or on individual cargo tanks.

7.3.4 The location and design of the devices referred to in Pt 5, Ch 15, 7.3 Venting arrangements 7.3.3 are to be in accordance with Pt 5, Ch 15, 4 Cargo tank venting, purging and gas-freeing.

7.4 Unattended machinery

7.4.1 Where inert gas generators are fitted with automatic or remote controls so that under normal operating conditions they do not require any manual intervention by the operators, they are to be provided with the alarms and safety arrangements required by Pt 5, Ch 15, 7.4 Unattended machinery 7.4.2, Pt 5, Ch 15, 7.4 Unattended machinery 7.4.3, Pt 5, Ch 15, 7.5 Instrumentation and alarms and Pt 5, Ch 15, 7.7 Nitrogen generator systems, as appropriate. Alternative arrangements which provide equivalent safeguards will be considered.

7.4.2 Where machinery is arranged to start automatically or from a remote control station, interlocks are to be provided to prevent start-up under conditions which could hazard the machinery.

7.4.3 Where machinery specified in Pt 5, Ch 15, 7.4 Unattended machinery 7.4.1 and Pt 5, Ch 15, 7.4 Unattended machinery 7.4.2 is required to be provided with a standby pump, the standby pump is to start automatically if the discharge pressure from the working pumps falls below a predetermined value.

7.5 Instrumentation and alarms

7.5.1 Alarms and safeguards are to be provided in accordance with 2.2.4 Indicators and alarms and 2.3.2 Indicators and alarms of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) as amended by Resolution MSC.365(93) – Amendments to the International Convention For the Safety of Life at Sea, 1974, as amended – (Adopted on 22 May 2014) and Table 15.7.1 Inert gas systems – Alarms and safeguards.

Table 15.7.1 Inert gas systems – Alarms and safeguards

Item Alarm Note
Combustion air pressure to oil burner Low 1
Fuel oil pressure Low -
Fuel oil temperature or viscosity High and Low 3
Burner flame and ignition Failure 1, 2
Cooling water temperature High -
Automatic control system power supply Failure -

Note 1 Combustion spaces are to be purged automatically before re-ignition takes place in the event of a flame out on all burners.

Note 2 Fuel oil to burner to be shut off automatically.

Note 3 Heavy oil only.

Note 4 Additional alerts and shutdowns may be necessary as determined through risk-mitigating activities in response to the completed Risk-Based Analysis (e.g. FMECA) for the inert gas generator.

7.5.2 Inert gas generators are to be fitted with an automatic combustion control system so as to maintain steady state conditions throughout the operating range of the generator.

7.5.3 See also Pt 6, Ch 1 Control Engineering Systems for requirements for control, alarm and safety systems.

7.6 Installation and tests

7.6.1 The inert gas system, including alarms and safety devices, is to be installed on board and tested under working conditions to the satisfaction of the Surveyors.

7.7 Nitrogen generator systems

7.7.1 The following requirements apply where a nitrogen generator system is fitted on board Tankers of 8,000 tonnes DWT and above. For the purpose, the inert gas is to be produced by separating air into its component gases by passing compressed air through a bundle of hollow fibres, semi-permeable membranes or adsorber materials.

7.7.2 Alarms and safeguards are to be provided in accordance with 2.2.4 Indicators and alarms and 2.3.2 Indicators and alarms of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) as amended by Resolution MSC.365(93) – Amendments to the International Convention For the Safety of Life at Sea, 1974, as amended – (Adopted on 22 May 2014) and Table 15.7.2 Nitrogen generator systems – Alarms and safeguards.

Table 15.7.2 Nitrogen generator systems – Alarms and safeguards

Item Alarm Note
Oxygen content High 1, 2, 3
Power supply to oxygen content monitoring instrumentation downstream of Nitrogen generator Failure 1

Note 1 To be fitted in the machinery space and cargo control room, where provided.

Note 2 Oxygen content not to exceed 5% with automatic discharge to atmosphere where this is exceeded, see Pt 5, Ch 15, 7.7 Nitrogen generator systems 7.7.5.

Note 3 Automatic shutdown of inert gas generating system.

Note 4 The Table contains the minimum list of alerts and shutdowns for an inert gas generator and is in addition to 2.2.4 Indicators and alarms and 2.4.2 Indicators and alarms of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) as amended by Resolution MSC.365(93) – Amendments to the International Convention For the Safety of Life at Sea, 1974, as amended – (Adopted on 22 May 2014); additional alerts and shutdowns may be necessary as determined through risk-mitigating activities in response to the completed Risk-Based Analysis (e.g. FMECA) for the inert gas generator.

7.7.4 A nitrogen generator consisting of a feed air treatment system and any number of membrane or adsorber modules in parallel is to be capable of delivering nitrogen to the cargo tanks at the rate required by paragraph 2.2.1.2.4 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) .

7.7.5 The nitrogen generator is to be capable of delivering high purity nitrogen with an oxygen content in accordance with paragraph 2.2.1.2.5 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) . In addition to meeting the venting requirements of paragraph 2.2.2.4 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) , the system is to be fitted with automatic means to discharge “off-spec” gas to the atmosphere during start-up and abnormal operation.

7.7.6 The system is to be provided with one or more compressors to generate enough positive pressure to be capable of delivering the total volume of gas required by 2.2.1.2 of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) . Where two compressors are provided, the total required capacity of the system is preferably to be divided equally between the two compressors, and in no case is one compressor to have a capacity less than 1/3 of the total capacity required.

7.7.7 Where the nitrogen system includes a nitrogen storage tank which has sufficient capacity to deliver the total volume of gas required by 2.2.1.2 of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) , in the event of failure of a compressor a single compressor may be accepted provided that sufficient spares are carried on board to enable the failure to be rectified by the ship’s crew. The list of spare parts required is to be supplied by the manufacturer and supported by a reliability analysis of the specific system submitted to and verified by LR. The size of the nitrogen storage tank is to be specified.

7.7.8 The feed air treatment system fitted to remove free water, particles and traces of oil from the compressed air as required by 2.4.1.2 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) , as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) , is also to maintain the specification temperature.

7.7.9 The oxygen-enriched air from the nitrogen generator and the nitrogen-product enriched gas from the protective devices of the nitrogen receiver are to be arranged to discharge to a safe location on the open deck. This safe location needs to address the two types of discharges separately.

For oxygen-enriched air from the nitrogen generator, safe locations on the open deck are:

  • outside of hazardous areas as defined by Pt 6, Ch 2, 13.5 Discharge lighting;
  • not within 3 m of areas traversed by personnel;
  • not within 6 m of air intakes for machinery and all ventilation inlets.

For nitrogen-product enriched gas from the protective devices of the nitrogen receiver, safe locations on the open deck are:

  • not within 3 m of areas traversed by personnel;
  • not within 6 m of air intakes for machinery and all ventilation inlets/outlets.

7.7.10 In order to permit maintenance, means of isolation are to be fitted between the generator and the receiver.

7.8 Nitrogen/inert gas systems fitted for purposes other than inerting required by SOLAS Reg. II-2/4.5.5.1

7.8.1 This section applies to systems fitted on oil tankers to which SOLAS - International Convention for the Safety of Life at Sea Chapter II-2 - Construction - Fire protection, fire detection and fire extinction/4.5.5.1 does not apply.

7.8.4 Materials used in inert gas systems are to be suitable for their intended purpose in accordance with the LR Rules for the Manufacture, Testing and Certification of Materials, July 2022.

7.8.5 All the equipment is to be installed on board and tested under working conditions to the satisfaction of the Surveyor.

7.8.6 The two non-return devices as required by paragraph 2.2.3.1.1 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73) , as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) are to be fitted in the inert gas main. The non-return devices are to comply with 2.2.3.1.2 and 2.2.3.1.3 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) ; however, where the connections to the cargo tanks, to the hold spaces or to cargo piping are not permanent, the non-return devices required by paragraph 2.2.3.1.1 of Chapter 15 - Inert Gas Systems of the FSS Code - Fire Safety Systems – Resolution MSC.98(73), as amended by Resolution MSC.367(93) – Amendments to the International Code for Fire Safety Systems (FSS Code) – (Adopted on 22 May 2014) , may be substituted by two non-return valves.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.