Section
3 System design - Protection
3.1 General
3.1.1 Installations
are to be protected against accidental overcurrents including short-circuit.
The protective devices are to provide complete and co-ordinated protection
to ensure:
-
Continuity of service
under fault conditions through discriminative action of the protective
devices.
-
Elimination of the
fault to reduce damage to the system and hazard of fire.
3.2 Protection against overload
3.2.1 Circuit-breakers
and automatic switches provided for overload protection are to have
tripping characteristics appropriate to the system. Fuses above 320
A are not to be used for overload protection, but may be used for
short-circuit protection.
3.3 Protection against short-circuit
3.3.1 Protection
against short-circuit currents is to be provided.
3.3.2 The breaking
capacity of every protective device is to be not less than the maximum
value of the short-circuit current which can flow at the point of
installation at the instant of contact separation.
3.3.3 The making
capacity of every switching device intended to be capable of being
closed, if necessary, on short-circuit, is to be not less than the
maximum value of the short-circuit current at the point of installation.
On alternating current, this maximum value corresponds to the peak
value allowing for maximum asymmetry.
3.3.4 Every protective
device or contactor not intended for short-circuit interruption is
to be adequate for the maximum short-circuit current which can occur
at the point of installation having regard to the time required for
the short-circuit to be removed.
3.3.5 In the
absence of precise data, the following short-circuit currents at the
machine terminals are to be assumed:
-
Direct current systems
10 times full load current for generators normally connected
(including spare). Six times full load current for motors simultaneously
in service.
-
Alternating current
systems
10 times full load current for generators normally connected
(including spare) – symmetrical r.m.s. Three times full load
current for motors simultaneously in service.
3.4 Combined circuit-breakers and fuses
3.4.1 The use
of a circuit-breaker of breaking capacity less than the prospective
short-circuit current at the point of installation is permitted, provided
that it is preceded on the generator side by fuses, or by a circuit-breaker
having at least the necessary breaking capacity. The generator breakers
are not to be used for this purpose.
3.4.2 Fused circuit-breakers
with fuses connected to the load side may be used where operation
of the circuit-breaker and fuses is co-ordinated.
3.4.3 The characteristics
of the arrangement shall be such that:
-
When the short-circuit
current is broken, the circuit-breaker on the load side shall not
be damaged and is to be capable of further service.
-
When the circuit-breaker
is closed on the short-circuit current, the remainder of the installation
shall not be damaged. However, it is admissible that the circuit-breaker
on the load side may require servicing after the fault has been cleared.
3.5 Protection of circuits
3.5.1 Short-circuit
protection is to be provided in each live pole of a direct current
system and in each phase of an alternating current system.
3.5.2 Overload
protection is to be provided in:
-
Two-wire direct current
or single-phase alternating current system – at least one line
or phase.
-
Three-wire direct
current system – both outer lines.
-
Insulated three-phase
alternating current system – at least two phases.
-
Earthed three-phase
alternating current system – all three phases.
3.5.3 No fuse,
non-linked switch or non-linked circuit-breaker is to be inserted
in an earthed conductor. Any switch or circuit-breaker fitted is to
operate simultaneously in the earthed conductor and the insulated
conductors.
3.5.4 These requirements
do not preclude the provision (for test purposes) of an isolating
link to be used only when the other conductors are isolated.
3.6 Protection of generators
3.6.2 For generators
not arranged to run in parallel: A circuit-breaker or contactor arranged
to open simultaneously all insulated poles or in the case of generators
rated at less than 50 kW a multi-pole linked switch with a fuse in
each insulated pole.
3.6.3 For generators
arranged to operate in parallel: A circuit-breaker or contactor arranged
to open simultaneously all insulated poles and provided with:
-
For direct current
generators, instantaneous reverse-current protection operating at
not more than 15 per cent rated current.
-
For alternating current
generators, a reverse-power protection, with time delay, selected
and set within the limits of two per cent to 15 per cent of full load
to a value fixed in accordance with the characteristics of the prime
mover.
3.6.4 The reverse-current
protection is to be adequate to deal with the reverse-current conditions
emanating from the ship’s network, e.g. winches.
3.7 Feeder circuits
3.7.2 Circuits
which supply motors fitted with overload protection may be provided
with short-circuit protection only.
3.7.3 Motors
of rating exceeding 0,5 kW are to be protected individually against
overload and short-circuit. The short-circuit protection can be provided
by the same protective device for the motor and its supply cable.
The overload protection may be replaced by an overload alarm if desired
by the Owner.
3.8 Power transformers
3.8.1 The primary
circuits of power transformers are to be protected against short-circuit
by circuit-breakers or fuses.
3.8.2 When transformers
are arranged to operate in parallel, means of isolation are to be
provided on the secondary windings. Switches and circuit-breakers
are to be capable of withstanding surge currents.
3.9 Lighting circuits
3.9.1 Lighting
circuits are to be provided with overload and short-circuit protection.
3.9.2 Where more
than one light is installed in a space, the lighting is to be supplied
from at least two final sub-circuits in such a way that failure of
one of the circuits does not leave the space in darkness.
3.10 Meters, pilot lamps, capacitors
3.10.1 Protection
is to be provided for voltmeters, voltage coils of measuring instruments,
earth indicating devices and pilot lamps, together with their connecting
leads.
3.10.2 A pilot
lamp installed as an integral part of another item of equipment need
not be individually protected, provided it is fitted in the same enclosure.
3.11 Batteries
3.11.1 Batteries,
except starter batteries, are to be protected against short-circuit
by a fuse in each insulated conductor or a multi-pole circuit-breaker
at a position adjacent to the battery compartment.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
 |
|