8.2.1 Where
settlement of vapour is required on Type G or Type C tankers, or cooling
is required to retain the cargo temperature within the limits of safe
carriage on Type N or Type C tankers, a water spray system with a
capacity of not less than 50 litres/m2 deck area cargo
zone per hour is to be provided on deck.
8.2.2 This water
spray system is to be capable of being connected to a shore supply.
8.2.3 The water
spray system is to be controlled from the wheelhouse as well as on
deck.
8.2.4 The water
spray nozzles are to be arranged such that the deck area will be covered
totally and for Type G and C tankers the releasing gases can be settled
in a safe manner.
8.2.5 For cargoes
for which a water spray system is mandatory, see list
of chemicals in ADN, Table C, Column 9, (see
Pt 5, Ch 13, 1.3 Materials 1.3.9 for reference).