Section
5 Site-specific support structure design evaluation
5.1 Module requirements
5.1.1 The purpose of this evaluation is to confirm that the site-specific support structure
design complies with the design basis. The support structure includes the tower,
sub-structure, foundations and mooring systems (floating structures only).
5.2 Guidance on input requirements
5.2.1 The applicant is expected to provide documentation fully detailing the
design of all parts of the site-specific support structure including drawings,
calculations and manufacturing specifications. The documentation submission for the
below site-specific support structure items should include amongst others:
Tower:
- tower design evaluation in relation to ILA results, including
design calculation reports (these are to include secondary structures
critical to personnel safety, e.g. tower ladders);
- tower stiffness and damping comparison with ILA;
- impact of tower internals on structural integrity of the tower
primary structure;
- manufacturing, transportation and installation, and maintenance
plans in relation to tower in-place structural integrity;
- material selection and corrosion protection system, based on
design basis (see
Ch 2, 2 Design basis evaluation); and
- design drawings.
Sub-structure:
- sub-structure design evaluation in relation to ILA results,
including design calculation reports (these are to include secondary
structures critical to personnel safety, e.g. boat landings);
- sub-structure stiffness and damping comparison with ILA;
- impact of secondary structures (e.g. boat landings) on
structural integrity of the primary structure;
- manufacturing, transportation and installation, and maintenance
plans in relation to sub-structure in-place structural integrity; and
- material selection and corrosion protection system, based on
design basis (see
Ch 2, 2 Design basis evaluation); and
- design drawings.
Foundation:
- foundation design evaluation in relation to ILA results (for
floating WT, this should include mooring lines and other project-specific
components as applicable);
- foundation stiffness and damping comparison with ILA;
- manufacturing, transportation and installation, and maintenance plans in
relation to foundation in-place structural integrity; and
- material selection and corrosion protection system, based on
design basis (see
Ch 2, 2 Design basis evaluation); and
- design drawings.
The above documentation should incorporate the guidance provided in the
following paragraphs as applicable to the type of support structure.
5.2.2 Fatigue is likely to be the dominant degradation mechanism for the support structure
of an offshore WT. Fatigue damage should be minimised by:
- ensuring that the structural natural frequencies do not
coincide with blade-passing or WT rotational frequencies or with frequencies
containing significant wave energy except where a system exists to
sufficiently damp or otherwise mitigate the oscillations;
- avoidance of dynamic response to wind, including vortex-induced vibration
(VIV) except where a system exists to sufficiently damp or otherwise
mitigate the oscillations;
- designing structural details to minimise stress concentration factors;
- controlling manufacturing precision and quality to achieve the tolerances
specified in the selected code of practice for construction; and
- prohibiting temporary or permanent unauthorised attachments, modifications
or repairs.
The process of fatigue is aggravated by corrosion and therefore appropriate corrosion
protection should be applied. Corrosion protection in the splash zone is of
particular importance because cathodic protection will be less effective and
in-service replacement of coatings will be difficult.
5.2.3 The air gap should be calculated based on deck elevation requirements
within IEC 61400-3-1 Wind energy generation systems – Part 3-1: Design
requirements for fixed offshore wind turbines. The air gap is defined as the
vertical gap between a highest wave crest elevation including the effects of highest
astronomical tide, positive storm surge, motion of the support structure and the
lower of either the tip of the WT blade or lowest point (beam, equipment or fixing)
of the lowest deck of the support structure. The air gap should be greater than or
equal to 0,2Hs50, where Hs50 is the 50-year
return value of significant wave height, with a minimum air gap value of 1 m for
fixed structures. In addition, for floating platforms, the strength with respect to
loads resulting from wave impacts, including slamming, sloshing and green water
should be confirmed in accordance with ISO 19904-1: Petroleum and natural gas
industries – Floating offshore structures – Part 1: Monohulls, semi-submersibles
and spars.
5.2.4 If the air gap for the abnormal condition is assessed based on a favourable parked
blade position, then the air gap must also be assessed for the operating wave crest
elevation. The possibility of contact between a wind-turbine blade and a vessel
should be considered; there should either be a means of remotely stopping the
turbine blades or the air gap should be set such that there can be no clash in the
limiting sea-state for service vessels. For other vessels, a risk assessment should
be undertaken to determine policy.
5.2.5 The design of a fixed steel WT support structure should generally meet
the requirements of IEC 61400-3-1 Wind energy generation systems – Part 3-1:
Design requirements for fixed offshore wind turbines, supplemented by the
applicable parts of other recognised industry standards:
- ISO 19902 Petroleum and natural gas industries – Fixed steel
offshore structures should be followed for partial factor design and
API RP 2A-WSD Recommended Practice for Planning, Designing and
Constructing Fixed Offshore Platforms – Working Stress Design for
allowable stress design;
- the post-impact condition can be regarded as an abnormal load-case.
Environmental conditions with a one-year return period should be
considered.
5.2.6 Design of foundations for fixed structures should consider the effects of
accumulated deformation in the soil. This may be especially significant for monopile
and gravity-base type structures that are subject to dynamic cyclic loading. Special
attention should be given to the effect of foundation stiffness upon the behaviour
of the support structure and WT/RNA.
5.2.7 To allow for corrosion, design of fixed structures should generally meet
the requirements of Annex G, IEC 61400-3-1 Wind energy generation systems – Part
3-1: Design requirements for fixed offshore wind turbines, and take into
account the following:
- for design strength calculations, the design thickness should
be reduced by the full corrosion margin;
- for accidental vessel impact and post-impact conditions, the
design thickness should be reduced by up to the full corrosion margin; and
- for design fatigue calculations, the design thickness should be
reduced by 50 per cent of the corrosion margin.
5.2.8 The design of floating steel WT support structures should generally meet
the requirements of IEC TS 61400-3-2 Wind energy generation systems – Part 3-2:
Design requirements for floating offshore wind turbines, and take into
account the following:
- using a WSD approach, Pt 4, Ch 3, 4 Structural design
loads of LR’s Rules and Regulations for the Classification of
Ships,July 2019 or equivalent should be applied; and
- for IEC 61400-3-1 Wind energy generation systems – Part 3-1:
Design requirements for fixed offshore wind turbines, the safety
factors in Pt 4, Ch 5, 2.1 General 2.1.1 of LR’s Rules and
Regulations for the Classification of Ships, July 2019 or equivalent
should be applied.
5.2.9 To allow for corrosion, design of floating steel structures should
generally meet the requirements of Annex G, IEC TS 61400-3-2 Wind energy
generation systems – Part 3-2: Design requirements for floating offshore wind
turbines, and take into account the following:
- for design strength calculations, the design thickness should be
reduced by the full corrosion margin for local strength assessment (e.g.
panel buckling) and by 50 per cent of the corrosion margin for global
strength assessment;
- for design fatigue calculations, the design thickness should be
reduced by 50 per cent of the corrosion margin for local stress assessment
and 25 per cent of the corrosion margin for global stress assessment; and
- the corrosion rates in Table 2.5.1 Recommended corrosion
rates for one side of structural members, are provided as
guidance. For a full range of corrosion rates refer to Pt 4, Ch 3, 7.4
Scantling compliance 7.4.6 of LR’s Rules and Regulationsfor the
Classification of Ships, July 2019.
Table 2.5.1 Recommended corrosion
rates for one side of structural members
| Environment
|
Position
|
Corrosion rate on each exposed surface
(mm/year)
|
| ballast water
|
within 3 m below the top of the tank
|
0,15
|
| elsewhere
|
0,1 (see Note 1)
|
| exposed to atmosphere
|
weather deck plating
|
0,1
|
| elsewhere
|
0,075
|
| exposed to seawater
|
all
|
0,075
|
| other tanks and spaces
|
all
|
0,05
|
|
Note 1 - 50 per
cent of the corrosion rate may be used for permanently
filled ballast tanks.
|
5.2.11 Mooring system loading conditions for floating WTs should generally meet
the requirements of IEC TS 61400-3-2 Wind energy generation systems – Part 3-2:
Design requirements for floating offshore wind turbines, and take into
account the following:
Table 2.5.2 Applicable factors of
safety for mooring
| IEC 61400-3
Design situation
|
Load
combination per LR Rules
|
Factor of
safety (break strength)
|
| Normal
(N)
|
Extreme
storm or maximum environment with floating unit attached
(intact)
|
1,67
|
| Abnormal
(A)
|
Extreme
storm or maximum environment with floating unit attached (one
line damaged)
|
1,25
|
5.2.12 Standards for subdivision, stability and freeboard prescribed by the
National Administration for the planned location of a floating WT should be
followed; if no such standards exist, the relevant parts of the IMO Code for the
Construction and Equipment of Mobile Offshore Drilling Units (MODU Code),
LR’s Rules and Regulations for the Classification of Ships, July 2022 or
other suitable international conventions should be applied as applicable for the
type of WT unit under consideration. It may be necessary to conduct a practical test
to support the buoyancy and stability of a complex floating structure or one of
irregular shape.
5.3 Evaluation methodology
5.3.1 LR’s evaluation of the support structure design will include:
- confirmation that the support structure design has been carried out in
accordance with the design basis;
- review of primary structure design reports, including the ULS,
SLS, FLS and ALS conditions;
- review of the impact of secondary structures (e.g. boat landings, tower
ladders) on the primary structure integrity;
- review of secondary structure critical to personnel safety (e.g. boat
landings, tower ladders) design reports, including the ULS, SLS, FLS and ALS
conditions;
- confirmation that the structural design reports incorporate the results of
the ILA, including the assumptions made in the analysis (e.g. support
structure stiffness and damping calculations);
- assessment of the stability of a floating unit based on the design basis;
- assessment of the geotechnical design documentation based on the design
basis;
- review of the plans for construction, transportation, installation and
maintenance; and
- review of the structural corrosion protection system based on the design
basis.
5.3.2 Independent analysis is not required as part of LR’s evaluation.
However, simplified parallel calculations (spot checks) may be undertaken for
critical areas identified in the review of the design reports, and depending on the
experience of the designer and the complexity of the design.
5.3.3 Special attention will be paid to the transition piece and the grouted
and/or bolted connections at the interfaces between the WT tower and the
substructure, or between the substructure and foundations (as applicable to the
site-specific design). LR may undertake finite element analysis of critical areas
identified in the review of the design reports, and depending on the experience of
the designer and the complexity of the design and the quality of the submitted
calculations.
5.3.4 The evaluation of the support structure will consider all project phases
including loadout, sea-fastening, transportation and installation, as applicable.
Where the client or applicant has appointed a Marine Warranty Surveyor (MWS) to
assess the transportation and installation phases of the assets, LR may review the
MWS’s reports and take credit for their reviews as part of the evaluation, provided
the MWS reviews are considered to directly contribute to the certification to IEC
61400-22 Wind turbines – Part 22: Conformity testing and certification and
IECRE OD-502 Project Certification Scheme.
5.3.5 LR’s review will be consider the impact of the load transfer from the
secondary structures to the primary structure.
|