Section
3 Safety equipment
3.1 Fire safety for tugs of less than 500 GT
The guidance in this Chapter has the following fire safety objectives:
- Prevent the occurrence of fire and explosion;
- Reduce the risk to life caused by fire;
- Reduce the risk of damage caused by fire to the tug and the environment;
- Contain, control and suppress fire and explosion in the compartment of origin;
and
- Provide adequate and readily accessible means of escape for crew.
For easy reference, a summary of the guideline requirements for tug fire
safety is included as Table 3.3.4 Fire safety Guidance.
3.1.1 Fire pumps and fire main systems
This guidance aims to ensure that any fire is effectively suppressed and swiftly
extinguished in the space of origin. For this purpose, the following functional
requirements should be met:
- Fixed fire-extinguishing systems should be installed, as applicable, having
due regard to the fire growth potential of the protected spaces; and
- Fire-extinguishing appliances should be readily available.
-
Capacity
The total capacity of the main fire pump(s) should not be less
than:
Q = (0.145(L(B +
D))1/2 + 2.170)2
, but need not exceed 25 m3/hour,
- where
B |
= |
Greatest moulded breadth of tug, in m |
D |
= |
Moulded depth to bulkhead deck, in m |
L |
= |
Freeboard Length, in m |
Q |
= |
Total capacity, in m3/hour |
-
Fire pumps
Generally one main power pump and one portable fire pump should
be provided as specified below.
- Sanitary, ballast, bilge or general service pumps may
be accepted as fire pumps, provided that they are not normally used
for pumping oil, and that, if they are subject to occasional duty
for the transfer or pumping of fuel oil, suitable changeover
arrangements are fitted.
- A power pump is a fixed pump driven by a power source
other than by hand. An independently driven power pump is
independent from the main engine(s).
- Provisions should be made for clearing sea inlet
gratings of fire pump sea inlet valves. Special attention should be
paid to ice clearing arrangements for tugs intended for navigation
in ice (e.g. air blowing, heating).
- Relief valves should be provided in conjunction with
any fire pump if the pump is capable of developing a pressure
exceeding the design pressure of the water service pipes, hydrants
and hoses. These valves should be so placed and adjusted as to
prevent excessive pressure in any part of the fire main system.
- Where a centrifugal pump is provided in order to comply
with this sub-Section, a non-return valve should be fitted in the
pipe connecting the pump to the fire main.
-
Portable fire pumps
- Portable fire pumps should comply with the
following:
- The pump should be self-priming.
- The total suction head and the net positive
suction head of the pump should be determined taking account
of actual operation, i.e. pump location when used. The net
positive suction head of the pump should be realised at the
deck where the pump is fitted (in practical cases on tugs
this is typically the main deck).
- The portable fire pump, when fitted with its
length of discharge hose and nozzle, should be capable of
maintaining a pressure sufficient to produce a jet throw of
at least 12 m, or that required to enable a jet of water to
be directed on any part of the engine room or the exterior
boundary of the engine room and casing, whichever is the
greater.
- Except for electric pumps, the pump set should
have its own fuel tank of sufficient capacity to operate the
pump for three hours. For electric pumps, their batteries
should have sufficient capacity for three hours.
- Except for electric pumps, details of the fuel
type and storage location should be carefully considered. If
the fuel type has a flashpoint below 60°C, further
consideration to the fire safety aspects should be given.
- The pump set should be stored in a secure, safe
and enclosed space, accessible from open deck and clear of
the Category ‘A’ machinery space.
- The pump set should be easily moved and operated
by two persons and be readily available for immediate use.
- Arrangements should be provided to secure the
pump at its anticipated operating position(s).
- The overboard suction hose should be
non-collapsible and of sufficient length, to ensure suction
under all operating conditions. A suitable strainer should
be fitted at the inlet end of the hose.
- Any diesel-driven power source for the
pump should be capable of being readily started in its cold
condition by hand (manual) cranking. If this is
impracticable, consideration should be given to the
provision and maintenance of heating arrangements, so that
readily starting can be ensured.
•
Alternatively to the guidance in Ch 3, 3.1 Fire
safety 3.1.1 (c) (i) .to Ch 3, 3.1 Fire safety 3.1.1
(c) (x), a fixed fire pump may be fitted, which
should comply with the following:
- The pump, its source of power and sea
connection should be located in accessible positions,
outside the compartment housing the main fire pump.
- The sea valve should be
capable of being operated from a position near the pump.
- The room where the fire pump
prime mover is located should be illuminated from the
emergency source of electrical power, and should be well
ventilated.
- Pumps required to supply
water for a fixed fire-extinguishing system in the space
where the main fire pump is situated, should be capable of
simultaneously supplying water to this system and the fire
main at the required rates.
- The pump may also be used
for other suitable purposes, subject to the approval in each
case.
- Pressure and quantity of water delivered
by the pump should be sufficient to produce a jet of water,
at any nozzle, of not less than 12 m in length. For tugs of
less than 150 GT, the jet of water may be specially
considered.
- For tugs of less than 150 GT fitted with an approved
fixed fire-fighting system in the engine room, portable pumps may be
omitted.
- Means to illuminate the stowage area of the portable
pump and its necessary areas of operation should be provided from
the emergency source of electrical power.
-
Fire main
- The diameter of the fire main should be based on the
required capacity of the fixed main fire pump(s) and the diameter of
the water service pipes should be sufficient to ensure an adequate
supply of water for the operation of at least one fire hose.
- The wash deck line may be used as a fire main provided
that the requirements of this sub-Section are satisfied.
- All exposed water pipes for fire-extinguishing should be
provided with drain valves for use in frosty weather. The valves
should be located where they will not be damaged by tug
operations.
-
Pressure in the fire main
-
Fire hydrants
- For tugs of less than 150 GT the number and position of
the hydrants should be such that at least one jet of water may reach
any part normally accessible to the crew, while the tug is being
navigated and any part of any deck space when empty. Furthermore,
such hydrants should be positioned near the accesses to the
protected spaces. At least one hydrant should be provided in each
Category ‘A’ machinery space.
- For tug equal to or greater than 150 GT the number and
position of hydrants should be such that at least two jets of water
not emanating from the same hydrant, one of which should be from a
single length of hose, may reach any part of the tug normally
accessible to the crew while the tug is being navigated and any part
of any cargo spaces when empty. Furthermore, such hydrants should be
positioned near the accesses to the protected spaces. Other
Requirements specified by the Administration will additionally be
considered.
-
Pipes and hydrants
- Materials readily rendered ineffective by heat should
not be used for fire mains. Where steel pipes are used, they should
be galvanised internally and externally. Cast iron pipes are
generally not acceptable. The pipes and hydrants should be so placed
that the fire-hoses may be easily coupled to them. The arrangement
of pipes and hydrants should be such as to avoid the possibility of
freezing. In tugs where deck cargo may be carried, the positions of
the hydrants should be such that they are always readily accessible
and the pipes should be arranged, as far as practicable, to avoid
risk of damage by such cargo. There should be complete interchange
ability of hose couplings and nozzles.
- A valve should be fitted at each fire hydrant so that
any fire-hose may be removed while the fire pump is at work.
- Where a fixed fire pump is fitted outside the engine
room, in accordance with Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.1.(c).(xi) to Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.1.(c).(xvi); an isolating valve should be fitted in the fire
main so that all the hydrants in the tug, except those in the
Category ‘A’ machinery space, can be supplied with water. The
isolating valve should be located in an easily accessible and
tenable position outside the Category ‘A’ machinery space. And the
fire main should not re-enter the machinery space downstream of the
isolating valve.
-
Fire-hoses
- Fire-hoses should be of approved non-perishable
material. The hoses should be sufficient in length to project a jet
of water to any of the spaces in which they may be required to be
used. Their length, in general, should not exceed 18 m. Each hose
should be provided with a nozzle and the necessary couplings.
Fire-hoses, together with any necessary fittings and tools, should
be kept ready for use in conspicuous positions near the water
service hydrants or connections.
- One hose should be provided for each hydrant. In
addition one spare hose should be provided on board.
-
Nozzles
- For the purpose of this Chapter, standard nozzle sizes
are 12 mm, 16 mm or 19 mm, or as near thereto as possible, so as to
make full use of the maximum discharge capacity of the fire pump(s).
- For accommodation and service spaces, the nozzle size
need not exceed 12 mm.
- The size of nozzles used in conjunction with a portable
fire pump need not exceed 12 mm.
- All nozzles should be of an approved dual purpose type
(i.e. spray/jet type) incorporating a shut-off.
3.1.2 Fire safety measures
The purpose of this guidance is to ensure that a fire is contained in
the space of origin. For this purpose, the following functional requirements should
be met:
- The tug should be subdivided by thermal and structural
boundaries;
- Thermal insulation of boundaries should have due regard to the
fire risk of the space and adjacent spaces;
- The fire integrity of the divisions should be maintained at
openings and penetrations.
- Structural fire protection
Table 3.3.1 Minimum fire
integrity of bulkheads and decks
[Item]
|
Space
|
Separation
by
|
From space
|
[(1)]
|
Machinery space
Class ‘A’
|
A-60
|
Accommodation /
control stations / corridors / staircases / service
spaces of high fire risk
|
[(2)]
|
Machinery space
Class ‘A’
|
A-0
|
Other than above
[item (1)]
|
[(3)]
|
Galley
|
A-0
|
Unless specified
otherwise
|
[(4)]
|
Service space of
high fire risk other than galley
|
B-15
|
Unless specified
above [item (1)]
|
[(5)]
|
Corridor /
staircase / escape route
|
B-0
|
Unless specified
above [item (1)]
|
The divisions used to separate spaces not mentioned above should
be of non-combustible material.
- The hull, superstructure, structural
bulkheads, decks and deckhouses should be constructed of steel
or other equivalent material. For the purpose of applying the
definition of steel or other equivalent material, as given in
SOLAS, the ‘applicable fire exposure’ should be one hour. Tugs
built of materials other than steel should be specially
considered.
- Stairways should be enclosed, at least at
one level, by divisions and doors or hatches, in order to
restrict the free flow of smoke to other decks in the tug and
the supply of air to the fire. Doors forming such enclosures
should be self-closing.
- Openings in ‘A’ Class divisions should be
provided with permanently attached means of closing which should
be at least as effective for resisting fires as the divisions in
which they are fitted.
- Interior stairways serving machinery spaces,
accommodation spaces, service spaces or control stations should
be of steel or other equivalent material.
- Doors should be self-closing in way of
Category ‘A’ machinery spaces and galleys, except where they are
normally kept closed.
- Where ‘A’ Class divisions are penetrated for
the passage of electric cables, pipes, trunks, ducts, etc., or
for girders, beams or other structural members, arrangements
should be made to ensure that the fire resistance is not
impaired. Arrangements should also prevent the transmission of
heat to un-insulated boundaries at the intersections and
terminal points of the divisions and penetrations by insulating
the horizontal and vertical boundaries or penetrations for a
distance of 450 mm.
- Materials
- Paints, varnishes and other finishes used on
exposed interior surfaces should not be capable of producing
excessive quantities of smoke, toxic gases or vapours and should be
of the low flame spread type in accordance with the IMO 2010 FTP
Code, Annex 1, Parts 2 and 5.
- Except in cargo spaces or refrigerated
compartments of service spaces, insulating materials should be
noncombustible.
- Where pipes penetrate ‘A’ or ‘B’ Class
divisions, the pipes or their penetration pieces should be of steel
or other approved materials having regard to the temperature and
integrity Recommendations such divisions are required to withstand.
- Pipes conveying oil or combustible liquids
through accommodation and service spaces should be of steel or other
approved materials having regard to the fire risk.
- Materials readily rendered ineffective by heat
should not be used for overboard scuppers, sanitary discharges and
other outlets which are close to the waterline, and where the
failure of the material in the event of fire would give rise to the
danger of flooding.
- Primary deck coverings within accommodation
spaces, service spaces and control stations should be of a type
which will not readily ignite, or give rise to toxic or explosive
hazards at elevated temperatures in accordance with the IMO FTP
Code, Annex 1, Parts 2 and 6.
- Materials used for insulating pipes, etc., in
machinery spaces and other compartments containing high fire risks
should be non-combustible. Vapour barriers and adhesives used in
conjunction with insulation, as well as the insulation of pipe
fittings, for cold service systems need not be of non-combustible
materials, but they should be kept to the minimum quantity
practicable and their exposed surfaces should have low flame spread
characteristics.
- Surface of insulation
- In spaces where penetration of oil products is
possible, the surface of the insulation should be impervious to oil
or oil vapours. Insulation boundaries should be arranged to avoid
immersion in oil spillage.
- Ventilation systems
- Ventilation fans should be capable of being
stopped and main inlets and outlets of ventilation systems closed
from outside the spaces being served.
- Ventilation ducts for Category ‘A’ machinery
spaces should not pass through accommodation spaces, galleys,
service spaces or control stations, unless the ducts are constructed
of steel and arranged to preserve the integrity of the
division.
- Ventilation ducts for accommodation spaces,
service spaces or control stations should not pass through Category
‘A’ machinery spaces or galleys unless the ducts are constructed of
steel and arranged to preserve the integrity of the division.
- Ventilation arrangement for store rooms
containing highly flammable products should be specially
considered.
- Ventilation systems serving Category ‘A’
machinery spaces and galley exhaust ducts should be independent of
systems serving other spaces.
- Ventilation should be provided to prevent the
accumulation of gases that may be emitted from batteries.
- Ventilation openings may be fitted in and under
the lower parts of cabin, mess and dayroom doors in corridor
bulkheads. The total net area of any such openings should not exceed
0,05 m2. Balancing ducts should not be permitted in fire
divisions.
- Oil fuel arrangements
- In a tug in which oil fuel is used, the
arrangements for the storage, distribution and utilisation of the
oil fuel should be such as to ensure the safety of the tug and
persons on board.
- Oil fuel tanks situated within the boundaries of
Category ‘A’ machinery spaces should not contain oil fuel having a
flashpoint of less than 60°C.
- Oil fuel, lubricating oil and other flammable
oils should not be carried in a forepeak tank or a tank forward of
the collision bulkhead.
- As far as practicable:
- oil fuel lines shall be arranged far
apart from hot surfaces, electrical installations or other
sources of ignition and shall be screened or otherwise
suitably protected to avoid oil spray or oil leakage onto
the sources of ignition. The number of joints in such piping
systems shall be kept to a minimum.
- surfaces with temperatures above 220°C
which may be impinged as a result of a fuel and/or hydraulic
oil system failure shall be properly insulated. Precautions
shall be taken to prevent any oil that may escape under
pressure from any pump, filter or heater from coming into
contact with heated surfaces.
- external high-pressure fuel delivery
lines between the high pressure fuel pumps and fuel
injectors shall be protected with a jacketed piping system
capable of containing fuel from a high-pressure line
failure. A suitable enclosure on engines having an output of
375 kW or less having fuel injection pumps serving more than
one injector may be used as an alternative to the jacketed
piping system.
- Special arrangements in Category ‘A’ machinery spaces
and where necessary other machinery spaces
- The number of skylights, doors, ventilators,
openings in funnels to permit exhaust ventilation and other openings
to machinery spaces should be reduced to a minimum consistent with
the needs of ventilation and the proper and safe working of the tug.
- Skylights should be constructed with steel
frames and not to contain glass panels, unless fire-retardant glass
equivalent to steel is applied. Suitable arrangements should be made
to permit the release of smoke, in the event of fire, from the space
to be protected.
- Windows should not be fitted in machinery space
boundaries. This does not preclude the use of glass in control rooms
within the machinery spaces.
- Means of control should be provided for:
- opening and closure of skylights,
closure of openings in funnels which normally allow exhaust
ventilation, and closure of ventilator dampers;
- permitting the release of smoke;
- closing power-operated doors or
actuating release mechanism on doors other than
power-operated watertight doors;
- stopping ventilating fans; and
- stopping forced and induced draught
fans, oil fuel transfer pumps, oil fuel unit pumps and other
similar fuel pumps.
- The controls detailed in Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.2.(f)
should be located outside the space concerned, where they will not
be cut off in the event of fire in the space they serve. Such
controls and the controls for any required fire-extinguishing system
should be situated at one control position or grouped in as few
positions as possible. Such positions should have a safe access from
the open deck.
- Arrangements for gaseous fuel for domestic
purposes
Where gaseous fuel is used for domestic purposes, the
arrangements for the storage, distribution and utilisation of the fuel
should be specially considered.
- Space heating
Space heaters, if used, should be fixed
in position and so constructed as to reduce fire risks to a minimum. The
design and location of these units should be such that clothing,
curtains or other similar materials cannot be scorched or set on fire by
heat from the unit.
- Means of escape
- The purpose of this requirement is to provide
means of escape so that persons on board can safely and swiftly
escape to the lifeboat and life raft embarkation deck. For this
purpose, the following functional requirements should be met:
- Safe escape routes should be provided;
- Escape routes should be maintained in a
safe condition, clear of obstacles; and
- Additional aids for escape should be
provided as necessary to ensure accessibility, clear
marking, and adequate design for emergency situations.
- Stairways, ladders and corridors serving crew
spaces and other spaces to which the crew normally have access
should be arranged so as to provide ready means of escape to a deck
from which embarkation into survival craft may be effected.
- There should be at least two means of escape, as
widely separated as possible, from each section of accommodation and
service spaces and control stations,
- The normal means of access to the
accommodation and service spaces below the open deck should
be arranged so that it is possible to reach the open deck
without passing through spaces containing a possible source
of fire (e.g. machinery spaces, storage spaces of flammable
liquids).
- The second means of escape may be
through portholes or hatches of adequate size and preferably
leading directly to the open deck.
- Dead-end corridors having a length of
more than 7 m are generally unacceptable.
- The escapes should be positioned either
both at centreline, at centreline and at port side, at
centreline and at starboard side or at starboard side and at
port side. Having both escapes on one side of the tug should
be avoided.
- At least two means of escape should be provided
from machinery spaces, except where the small size of a machinery
space makes it impracticable. Escape should be by steel ladders that
should be as widely separated as possible.
3.1.3 Fixed fire detection and fire-alarm systems
An approved and fixed fire detection system should be installed in all Category ‘A’
machinery spaces. Manual activating units should be positioned near each emergency
exit. The use of approved fire detectors connected to a group alarm system will be
specially considered taking into account the size and arrangement (general layout
and number of deckhouse tiers) of the tug.
3.1.4 Fire-extinguishing arrangements
The purpose of this guidance is to ensure that any fire is effectively
suppressed and swiftly extinguished in the space of origin. For this purpose, the
following functional requirements should be met:
- (i) Fixed fire-extinguishing systems should be installed, as applicable,
having due regard to the fire growth potential of the protected spaces;
and
- (ii) Fire-extinguishing appliances should be readily available.
- Fixed fire-extinguishing arrangements in Category ‘A’
machinery spaces
- Machinery spaces of Category ‘A’ on tugs with GT
greater than or equal to 150 except for vessels with a service
restriction notation denoting that it is restricted to operations
within protected/extended protected waters, should be provided with
an approved fixed fire- extinguishing system, as specified in Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.4.(b)
- Fixed fire-extinguishing systems
- Fixed fire-fighting systems where required,
should be in accordance with the requirements of the IMO FSS
Code.
- Protection of paint lockers and flammable liquid
lockers
- The Recommendations for the protection of paint
lockers and flammable liquids lockers should be specially
considered.
- Other fixed fire-extinguishing systems (not covered by
this Chapter)
- If such a system is installed, it should be of
an approved type.
- Portable fire-extinguishers
- The number of portable fire-extinguishers that
should be carried on board are detailed in Table 3.3.2 Portable
fire-extinguishers
Table 3.3.2 Portable
fire-extinguishers
Accommodation and service spaces
|
|
- Tugs greater than or equal
to 150 GT
|
≥ 3
|
|
≥ 1
|
Boiler
rooms etc.
|
≥
2
|
Machinery
spaces
|
|
(one extinguisher per
every 375 kW of internal combustion engine
power)
|
≥ 2, ≤ 6
|
- All fire-extinguishers should be of approved
types and designs.
- The extinguishing media employed should be
suitable for extinguishing fires in the compartments in which they
are intended to be used.
- The extinguishers required for use in the
machinery spaces of tugs using oil as fuel should be of a type
discharging foam, carbon dioxide gas, dry powder or other approved
media suitable for extinguishing oil fires.
- The capacity of required portable fluid
extinguishers should not exceed more than 13,5 litres but not less
than 9 litres. Other extinguishers should be at least as portable as
the 13,5 litre fluid extinguishers, and should have a
fire-extinguishing capability at least equivalent to a 9 litre fluid
extinguisher.
- The following capacities may be taken as
equivalents:
- 9 litre fluid extinguisher (water or
foam);
- 5 kg dry powder;
- 5 kg carbon dioxide.
- A spare charge should be provided for each
required portable fire-extinguisher that can be readily recharged on
board. If this cannot be done, duplicate extinguishers should be
provided.
- The extinguishers should be stowed in readily
accessible positions and should be spread as widely as possible and
not be grouped.
- One of the portable fire-extinguishers intended
for use in any space should be stowed near the entrance to that
space.
- Accommodation spaces, service spaces and control
stations should be provided with a sufficient number of portable
fire-extinguishers to ensure that at least one extinguisher will be
readily available for use in every compartment of the crew spaces.
In any case, their number should be not less than three, except
where this is impractical for very small tugs, in which case one
extinguisher should be available at each deck having accommodation
or service spaces, or control stations.
- Portable fire-extinguishers using C02 are not to
be used in accommodation spaces.
3.1.5 Fire-fighting equipment
Fire-fighting equipment should be available as detailed below:
- Fire-fighter’s outfit (which includes an axe)
- For all vessels of 150 GT or greater at least
two fire-fighter’s outfits complying with the Requirements of the
IMO FSS Code, should be provided on board.
- For vessels of less than 150 GT at least one
fire-fighter’s outfit complying with the Requirements of the IMO FSS
Code, should be provided on board. Except for vessels of less than
150 GT with a service restriction notation denoting that it is
restricted to operations within protected/ extended protected
waters, where no fire-fighter’s outfit is required, however a
Firefighters axe should still be carried.
- Fire control plans
- In all tugs, general arrangement plans should be
permanently exhibited for the guidance of the tug's officers, using
graphical symbols that are in accordance with IMO Resolution
A.952(23), which show clearly for each deck the control stations,
the various fire sections enclosed by steel or ‘A’ Class divisions,
together with particulars of:
- The fire detection and fire-alarm
systems;
- Fixed fire-fighting system;
- The fire-extinguishing appliances;
- The means of access to different
compartments, decks, etc.;
- The position of the fireman's outfits;
- The ventilating system, including
particulars of the fan control positions, the position of
dampers and identification numbers of the ventilating fans
serving each section; and
- The location and arrangement of the
emergency stop for the oil fuel unit pumps and for closing
the valves on the pipes from oil fuel tanks.
- Alternatively, the details may be set out in a
booklet, a copy of which should be supplied to each officer, with
one copy at all times available on board in an accessible position.
- The plans and booklets should be kept up to
date, any alterations being recorded thereon as soon as practicable.
Description in such plans and booklets should be in the official
language of the Flag State and in the language as shown inTable 3.3.3 Language
in fire control plan. In addition, instructions concerning the
maintenance and operation of all the equipment and installations on
board for the fighting and containment of fire should be kept under
one cover, readily available in an accessible position.
Table 3.3.3 Language
in fire control plan
Notations
|
Language
|
tug,
escort tug
|
English
|
tug,
escort tug with a service restriction
notation
|
Official
language(s) of the Administration(s) concerned
with the tug’s service, or language(s) recognised
by such Administration(s).
However,
description in such plans and booklets for tugs
engaged in domestic service only may be in the
official language of the Flag State
only.
|
- In general, on all vessels greater than or equal
to 150 GT, a duplicate set of fire-control plans or a booklet
containing such plans should be permanently stored in a prominently
marked weather tight enclosure outside the deckhouse for the
assistance of shore-side fire-fighting personnel.
- For vessels with a service restriction notation
denoting that it is restricted to operations within
protected/extended protected waters the duplicate set of the
fire-control plan may be stored at a shore side facility.
3.1.6 Alternative design and arrangements for fire safety
The purpose of this guidance is to provide a methodology for alternative design and
arrangements for fire safety.
- General
- Fire safety design and arrangements that deviate
from Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.1 to Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.6, should meet
the following fire safety objectives and the functional
Recommendations.
- When fire safety design or arrangements deviate
from the requirements of this Chapter, engineering analysis,
evaluation and approval of the alternative design and arrangements
should be carried out in accordance with this part of the guidance.
Reference can be made to MSC/Circ.1002 ‘Guidelines on alternative
design and arrangements for fire safety’.
- Engineering analysis
- The engineering analysis should be prepared and
submitted, based on the guidelines developed by the International
Maritime Organization (IMO) and should include, as a minimum, the
following elements:
- determination of the tug type and
space(s) concerned;
- identification of recommendation(s) with
which the tug or the space(s) will not comply;
- identification of the fire and explosion
hazards of the tug or the space(s) concerned:
- identification of the possible
ignition sources;
- identification of the fire
growth potential of each space concerned;
- identification of the smoke and
toxic effluent generation potential for each space
concerned;
- identification of the potential
for the spread of fire, smoke or of toxic effluents
from the space(s) concerned to other spaces;
- determination of the required fire
safety performance criteria for the tug or the space(s)
concerned:
- detailed description of the alternative
design and arrangements, including a list of the assumptions
used in the design and any proposed operational restrictions
or conditions; and
- technical justification demonstrating
that the alternative design and arrangements meet the
required fire safety performance criteria.
- Evaluation of the alternative design and arrangements
- The engineering analysis required in Ch 3, 3.1 Fire safety for tugs of less than 500 GT 3.1.6.(b) should be
appraised by the relevant body (e.g. Class) taking into account the
guidelines developed by the IMO.
- A copy of the documentation, as appraised,
indicating that the alternative design and arrangements comply with
this regulation should be carried on board the tug.
- Re-evaluation due to change of conditions
- If the assumptions or operational restrictions
that were stipulated in the alternative design and arrangements are
changed, the engineering analysis should be carried out considering
the updated condition and should be submitted for evaluation.
Table 3.3.4 Fire safety Guidance
Type
notation
|
Tug, escort tug
|
Service
restrictions
|
(unrestricted)
|
Specified coastal service, or Specified operating or service
areas
|
Protected or Extended Protected waters service
|
fire pumps
|
|
|
|
≥ 150 gt
|
|
|
|
independently driven power pumps
|
1
|
1
|
1
|
power pumps
|
1
|
1
|
-
|
hand pumps
|
-
|
-
|
1
|
< 150 gt
|
|
|
|
independently driven power pumps
|
-
|
-
|
-
|
power pumps
|
1
|
1
|
1
|
hand pumps
|
1
|
1
|
-
|
portable or fixed emergency fire
pump
|
11,2
|
11,2
|
-
|
fire hydrants
|
|
|
|
≥ 150 gt
|
|
|
|
Sufficient number and so located that at
least the number of powerful water jets can reach any normally
accessible part of tug
|
2
|
2
|
2
|
< 150 gt
|
|
|
|
Sufficient number and so located that at
least the number of powerful water jets can reach any normally
accessible part of tug
|
1
|
1
|
1
|
fire hoses
(length3)
|
number of
hydrants + 1 spare hose
|
number of
hydrants + 1 spare hose
|
number of
hydrants + 1 spare hose
|
with coupling and nozzles
|
X
|
X
|
X
|
fire nozzles
|
|
|
|
dual purpose (spray/jet) with 12 mm jet and
integral shut-off; jet may be reduced to 10 mm and shut-off omitted
for hand pump hoses
|
X
|
X
|
X
|
portable fire-extinguishers
|
|
|
|
Accommodation and service spaces
|
|
|
|
≥ 150 gt
|
≥ 3
|
≥ 3
|
≥ 3
|
< 150 gt
|
≥ 1
|
≥ 1
|
≥ 1
|
Boiler rooms, etc.
|
≥ 2
|
≥ 2
|
≥ 2
|
machinery spaces (one extinguisher per 375
kW of internal combustion engine power4 (capacity 45 l fluid or
equivalent)
|
≥ 2 , ≤
6
|
≥ 2 , ≤
6
|
≥ 2 , ≤
6
|
fixed fire-extinguishing
systems
|
|
|
|
≥ 150 gt
|
|
|
|
Category ‘A’ machinery spaces
|
X
|
X
|
-
|
fixed fire detection system (Category
‘A’ spaces)
|
X
|
X
|
X
|
complete fireman’s outfit
|
|
|
|
≥ 150 gt
|
≥ 2
|
≥ 2
|
≥ 2
|
< 150 gt
|
≥ 1
|
≥ 1
|
-
|
fireman’s axe
|
1
|
1
|
1
|
fire control plan
|
1 on display
+ 1 in WT locker
|
1 on display
+ 1 in WT locker
|
1 on display
+ 1 in WT locker
|
means of escape
|
|
|
|
accommodation and service spaces
|
2
|
2
|
2
|
machinery spaces5
|
2
|
2
|
2
|
Notes:
- For tugs of less than 150 GT fitted with
an approved fixed fire-fighting system in the engine room,
portable pumps may be omitted.
- When a portable / emergency fire pump is
fitted, (independent) power pump may be omitted.
- Sufficient in length to project a jet of
water to any of the spaces in which they may be required to
be used.
- Alternatives may be proposed taking
into consideration the size of the tug and the installed
power.
- Unless the small size of the machinery
space makes it impractical.
|
3.2 Life-saving appliances for tugs of less than 500 GT
3.2.1 Life-saving appliance requirements.
The guideline requirements for life-saving appliances for tugs and
escort tugs are detailed in Table 3.3.5 Guidance for life-saving
appliances (LSA).
Table 3.3.5 Guidance for life-saving
appliances (LSA)
Type notation
|
Tug, escort tug
|
Service
restrictions
|
(unrestricted)
|
Specified coastal service, or Specified operating
or service areas
|
Protected or Extended Protected waters
service
|
life rafts
|
|
|
|
100% capacity on each side
/ easy side to side transfer
or
150% capacity on each side
|
X
|
X
|
1
|
hydrostatic
releases
|
X
|
X
|
1
|
illumination and operating
instructions
|
X
|
X
|
1
|
MOB
arrangement
|
|
|
|
rescue boat
|
X2
|
X2
|
-
|
Jason’s cradle
|
X
|
X
|
X
|
search light
|
X
|
X
|
X
|
lifebuoys
|
|
|
|
with smoke/light
|
2
|
1
|
1
|
with light
|
1
|
1
|
1
|
with lifeline
|
1
|
1
|
1
|
lifejackets with
lights
|
|
|
|
each person on
board
|
X
|
X
|
X
|
immersion
suit
|
|
|
|
each person on
board
|
X3
|
X3
|
-
|
other
equipment
|
|
|
|
rocket parachute
flares
|
12
|
6
|
-
|
red hand flares
|
6
|
2
|
2
|
smoke signals
|
2 buoyant
|
2
|
2
|
line throwing
apparatus
|
1
|
1
|
-
|
general alarm
|
X
|
X
|
X
|
communication
system
|
|
|
|
to engine room /
accommodation / deck
|
X
|
X
|
X
|
documentation on
board
|
|
|
|
fire and safety
plan
|
X
|
X
|
X
|
training and instruction
manual
|
X
|
X
|
X
|
SOLAS life-saving
table4
|
X
|
X
|
X
|
muster list and emergency
instructions
|
X
|
X
|
X
|
Notes:
- A float free buoyant apparatus
should be provided.
- The tug’s operational working area,
manoeuvrability, size, freeboard and propulsion
arrangement may be taken into consideration for the
evaluation of the applicability of the requirement for a
rescue boat.
- If the tug is constantly engaged in
warm climates (refer to MSC Circ.1046) where, in the
opinion of the Administration thermal protection is
unnecessary, immersion suits may need not to be carried
on board.
- An illustrated table describing the
life-saving signals should be readily available to the
officer of the watch of every tug to all tugs on all
voyages. The signals should be used by tugs or persons
in distress when communicating with life-saving
stations, maritime rescue units and aircraft engaged in
search and rescue operations.
|
3.3 Radio installation for tugs of less than 300 GT
3.3.1 Radio installation Guidelines.
The guidelines for Radio installations for tugs and escort tugs are detailed in Table 3.3.6 Guidance for radio installation.
Table 3.3.6 Guidance for radio installation
Type notation
|
Tug, escort tug
|
Service
restrictions
|
(unrestricted)
|
Specified coastal service, or Specified operating or service
areas
|
Protected or Extended Protected waters service
|
general guidance
|
|
|
|
≥ 300 gt
|
|
|
|
SOLAS (A1+A2+A3+A4, as
applicable)
|
X
|
X
|
X
|
< 300 gt
|
|
|
|
no duplication of equipment
required
|
X
|
X
|
X
|
specific guidance
|
|
|
|
VHF / DSC
|
1
|
1
|
1
|
SART1
|
1
|
1
|
1
|
EPIRB / satellite
|
1
|
1
(A2+A3)
|
-
|
EPIRB / VHF
|
-
|
1
(A1)
|
-
|
NAVTEX
|
1
|
1
|
-
|
MF / DSC
|
1
|
-2
|
-
|
INMARSAT C
|
1
|
-2
|
-
|
GMDSS porto
|
1
|
1
|
1
|
electrical power supply
|
dedicated radio battery
|
emergency battery
|
emergency battery
|
Notes:
- SART may not be required if the 406
MHZ EPIRB provided has a 121.5 MHz frequency
transmitting capability and is of the non-float free
type for placing in a life raft.
- MF / DSC or INMARSAT C depending on
region.
|
3.4 Navigation equipment for tugs of less than 500 GT
3.4.1 Navigation equipment requirements
Table 3.3.7 Guidance for navigation
equipment
Type notation
|
Tug, escort tug
|
Service
restrictions
|
(unrestricted)
|
Specified coastal service, or Specified operating or service
areas
|
Protected or Extended Protected waters service
|
general
requirements
|
|
|
|
SOLAS Ch V should to be taken
into account for all tugs on all voyages the administration should
determine to what extent the provisions of SOLAS Ch V do not apply
to the following tugs:
- tugs below 150 GT on any voyage
- tugs below 150 GT not engaged on
international voyages1
|
X
|
X
|
X
|
specific
requirements
|
|
|
|
radar
|
1
|
1
|
-
|
magnetic compass
|
12
|
12
|
1
|
gyro compass
|
12
|
12
|
-
|
GPS compass
|
12
|
12
|
-
|
GPS
|
2
|
1
|
1
|
AIS
|
1
|
1
|
1
|
nautical charts /
ECDIS
|
1
|
1
|
1
|
daylight signalling
lamp
|
1
|
1
|
1
|
echo sounding
|
1
|
1
|
1
|
IAMSAR
|
1
|
1
|
1
|
code of signals
|
1
|
1
|
1
|
Notes:
- International voyage: voyage from a
country to which the SOLAS Convention applies to a port
outside such country, or conversely.
- Optional 2 out of 3
|
|