13.2.1 Each cargo tank should
                           be fitted with at least one liquid level gauging device, designed
                           to operate at pressures not less than the MARVS of the cargo tank
                           and at temperatures within the cargo operating temperature range.
                           Where only one liquid level gauge is fitted it should be so arranged
                           that any necessary maintenance can be carried out while the cargo
                           tank is in service.
                        
                        
                        
                      
                     
                     
                     
                        
                        
                         
                           13.2.2 Cargo tank liquid
                           level gauges may be of the following types subject to any special
                           requirement for particular cargoes shown in column g in the table
                           of chapter 19:
                           
                        
                        
                        
                        
                           - 
                              
                              
                              
                                 .1 indirect devices, which determine the amount of
                                 cargo by means such as weighing or pipe flow meters;
                              
                              
                              
                            
                           - 
                              
                              
                              
                                 .2 closed devices, which do not penetrate the cargo
                                 tank, such as devices using radioisotopes or ultrasonic devices;
                              
                              
                              
                            
                           - 
                              
                              
                              
                                 .3 closed devices, which penetrate the cargo tank,
                                 but which form part of a closed system and keep the cargo from being released,
                                 such as float type systems, electronic probes, magnetic probes and bubble tube
                                 indicators. If a closed gauging device is not mounted directly on the tank it
                                 should be provided with a shutoff valve located as close as possible to the tank;
                                 and
                              
                              
                              
                            
                           - 
                              
                              
                              
                                 .4 restricted devices, which penetrate the tank and
                                 when in use permit a small quantity of cargo vapour or liquid to escape to the
                                 atmosphere, such as fixed tube and slip tube gauges. When not in use, the devices
                                 should be kept completely closed. The design and installation should ensure that
                                 no dangerous escape of cargo can take place when opening the device. Such gauging
                                 devices should be so designed that the maximum opening does not exceed 1.5 mm
                                 diameter or equivalent area unless the device is provided with an excess flow
                                 valve.
                              
                              
                              
                            
                        
                        
                        
                      
                     
                     
                     
                        
                        
                         
                           13.2.3 Sighting ports with
                           a suitable protective cover and situated above the liquid level with
                           an internal scale may be allowed by the Administration as a secondary
                           means of gauging for cargo tanks having a design vapour pressure not
                           higher than 0.7 bar.
                        
                        
                        
                      
                     
                     
                     
                        
                        
                         
                           13.2.4 Tubular gauge glasses
                           should not be fitted. Gauge glasses of the robust type as fitted on
                           high-pressure boilers and fitted with excess flow valves may be allowed
                           by the Administration for deck tanks, subject to any provisions of chapter 17.