8.6.1 An alarm system should be provided which
should indicate any fault requiring attention.
8.6.2
-
.1 The alarm system should have a connexion to
the public rooms and to all engineers' cabins. The Administration
may permit other arrangements.
-
.2 The alarm system should have a connexion to
the engineers' public rooms and to each of the engineers' cabins through
a selector switch, to ensure connexion to at least one of those cabins.
Administrations may permit equivalent arrangements.
-
.3 Audible and visual alarm should be activated
on the navigating bridge for any situation which requires action by
the officer on watch or which should be brought to his attention.
-
.4 The alarm system should as far as is practicable
be designed on the fail-to-safety principle.
-
.5 The alarm system should activate the engineers'
alarm required by 7.8 if an alarm
function has not received attention locally within a limited time.
8.6.3
-
.1 The alarm system should be continuously powered
with automatic change-over to a stand-by power supply in case of loss
of normal power supply.
-
.2 Failure of the normal power supply of the alarm
system should be alarmed.
8.6.4
-
.1 The alarm system should be able to indicate
at the same time more than one fault and the acceptance of any alarm
should not inhibit another alarm.
-
.2 Acceptance at the position mentioned in 8.6.2.1
of any alarm condition should be indicated at the positions where
it was shown. Alarms should be maintained until they are accepted
and the visual indications should remain until the fault has been
corrected, when the alarm system should automatically reset to the
normal operating condition.