5.1 The peak radiant flux (Ew) should
be measured for the first 15 min of the test, for the first 30 min
of the test, and for the entire duration of the test (i.e., 60 min
for class "A" and 30 min for class "B" boundaries).
5.2 The peak radiant fluxes (Ew) measured
in accordance with paragraph 5.1 should be compared against the reference
value (Ec) from the table.
5.3 If (Ew) is less than (Ec),
the window is acceptable for installation in a boundary of the corresponding
fire resistant classification.
Table 1. Criteria For Heat Flux
|
Fire
Resistant Division Classification
|
Time
Period From Beginning of Test To
|
Emissive Power
Ec (kW/m2)
|
A-0
|
60
minutes
|
56.5
|
A-15
|
15
minutes
|
2.34
|
|
60
minutes
|
8.0
|
A-30
|
30
minutes
|
2.34
|
|
60
minutes
|
6.4
|
A-60
|
60
minutes
|
2.34
|
B-0
|
30
minutes
|
36.9
|
B-15
|
15
minutes
|
2.34
|
|
30
minutes
|
4.3
|