                        The objective of these Guidelines is to establish an agreed method for sampling to
                           enable effective control and enforcement of liquid fuel oil being used on board ships
                           under the provisions of MARPOL Annex VI. 
                        
                        
                        
                      
                     
                     
                     
                        2 Sampling location
                        
                        
                        
                         The in-use
footnote representative sample or samples should be
                           obtained from a designated sampling point or points. The number and location of
                           designated fuel oil sampling points should be confirmed by the Administration following
                           consideration of possible fuel oil cross-contamination and service tank arrangements.
                           Fuel oil sampling points to be used should fulfil all of the following conditions: 
                           
                              - 
                                 
                                 
                                 .1 be easily and safely accessible;  
- 
                                 
                                 
                                 .2 take into account different fuel oil grades being used for the
                                    fuel oil combustion machinery item; 
                                  
- 
                                 
                                 
                                 .3 be downstream of the in-use fuel oil service tank;  
- 
                                 
                                 
                                 .4 be as close to the fuel oil combustion machinery as safely
                                    feasible taking into account the type of fuel oil, flow-rate, temperature, and
                                    pressure behind the selected sampling point; 
                                  
- 
                                 
                                 
                                 .5 be clearly marked for easy identification and described in
                                    either the piping diagram or other relevant documents; 
                                  
- 
                                 
                                 
                                 .6 each sampling point should be located in a position shielded
                                    from any heated surface or electrical equipment and the shielding device or
                                    construction should be sturdy enough to endure leaks, splashes or spray under
                                    design pressure of the fuel oil supply line so as to preclude impingement of
                                    fuel oil onto such surface or equipment; and 
                                  
- 
                                 
                                 
                                 .7 the sampling arrangement should be provided with suitable
                                    drainage to the drain tank or other safe location.
                                  
 
                     
                     
                     
                        3 Sample handling 
                        
                        
                        
                        The fuel oil sample should be taken when a steady flow is established in the
                           fuel oil circulating system. The sampling connection
footnote should be thoroughly flushed through with the
                           fuel oil in use prior to drawing the sample. The sample or samples should be collected
                           in a sampling container or containers and should be representative of the fuel oil being
                           used. The sample bottles should be sealed by the inspector with a unique means of
                           identification installed in the presence of the ship's representative. The ship should
                           be given the option of retaining a sample. The label should include the following
                           information: 
                           
                              - 
                                 
                                 
                                 .1 sampling point location where the sample was drawn;  
- 
                                 
                                 
                                 .2 date and port of sampling;  
- 
                                 
                                 
                                 .3 name and IMO number of the ship;  
- 
                                 
                                 
                                 .4 details of seal identification; and  
- 
                                 
                                 
                                 .5 signatures and names of the inspector and the ship's
                                    representative.