4.1.1 The foam concentrates of low-expansion foam
fire-extinguishing systems shall be approved by the Administration
based on the guidelines adopted by the Organizationfootnote. Different foam concentrate types shall
not be mixed in a low-expansion foam system. Foam concentrates of
the same type from different manufacturers shall not be mixed unless
they are approved for compatibility.
4.1.2 The system shall be capable of discharging
through fixed discharge outlets, in no more than 5 min, a quantity
of foam sufficient to produce an effective foam blanket over the largest