6.5.1 In view of exceptional conditions in which
the explosion hazard may extend outside the above-mentioned zones,
special arrangements should be provided to facilitate the selective
disconnection or shutdown of:
-
.1 ventilation systems, except fans necessary
for supplying combustion air to prime movers for the production of
electrical power;
-
.2 main generator prime movers, including the
ventilation systems for these;
-
.3 emergency generator prime movers.
6.5.2 Disconnection or shutdown should be possible
from at least two strategic locations, one of which should be outside
hazardous areas.
6.5.3 Shutdown systems that are provided to comply
with 6.5.1 should be so designed that the risk of unintentional stoppages
caused by malfunction in a shutdown system and the risk of inadvertent
operation of a shutdown are minimized.
6.5.4 Equipment which is located in spaces other
than enclosed spaces and which is capable of operation after shutdown
as given in 6.5.1 should be suitable for installation in zone 2 locations.
Such equipment which is located in enclosed spaces should be suitable
for its intended application to the satisfaction of the Administration.
At least the following facilities should be operable after an emergency
shutdown:
|
–
|
emergency lighting required by 5.3.6.1.1
to 5.3.6.1.4 for half an hour;
|
|
–
|
blow-out preventer control
system;
|
|
–
|
general alarm system;
|
|
–
|
public address system; and
|
|
–
|
battery supplied radiocommunication
installations.
|