Test piping should be provided in each zone to periodically
allow a full flow test. The piping should discharge the zone's flow
overboard. Test piping may also serve as system drain piping. for
wet pipe systems, the discharge piping need not exceed 50 mm in diameter.
All systems should also have a test arrangement at the farthest point
in each zone to allow a test flow equal to that from a single sprinkler.