5.16.1 Five nozzles should be fixed vertically
to a vibration table. They should be subjected at room temperature
to sinusoidal vibrations. The direction of vibration should be along
the axis of the connecting thread.
5.16.2 The nozzles should be vibrated continuously
from 5 Hz to 40 Hz at a maximum rate of 5 min/octave and an amplitude
of 1 mm (1/2 peak-to-peak value). If one or more resonant points are
detected, the nozzles after coming to 40 Hz, should be vibrated at
each of these resonant frequencies for 120 h/number of resonances.
If no resonances are detected, the vibration from 5 Hz to 40 Hz should
be continued for 120 h.
5.16.3 The nozzle should then be subjected to
the leakage test in accordance with 4.8.1 and the functional test in accordance with 4.5.1 at the minimum operating
pressure.