The nozzle and a pressure gauge should be mounted on a supply
pipe. The water flow should be measured at pressures ranging from
the minimum operating pressure to the rated working pressure at intervals
of approximately 10% of the service pressure range on two sample nozzles.
In one series of tests, the pressure should be increased from zero
to each value and, in the next series, the pressure should be decreased
fro the rated pressure to each value. The flow constant K should be
averaged from each series of readings, i.e., increasing pressure and
decreasing pressure. During the test, pressures should be corrected
for differences in height between the gauge and the outlet orifice
of the nozzle.