4.3 Emission limits
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Resolutions - Marine Environment Protection Committee - Resolution MEPC.184(59) – 2009 Guidelines for Exhaust Gas Cleaning Systems – (adopted on 17 July 2009) - Annex – 2009 Guidelines for Exhaust Gas Cleaning Systems - 4 Scheme A - EGC System Approval, Survey and Certification Using Parameter and Emission Checks - 4.3 Emission limits

4.3 Emission limits

  4.3.1 Each EGC unit should be capable of reducing emissions to equal to or less than the Certified Value at any load point when operated in accordance with the criteria as given within 4.2.2.1(b), as specified in paragraphs 4.3.2 to 4.3.5 of these Guidelines, and as excepted in paragraph 4.3.7.

  4.3.2 EGC units fitted to main propulsion diesel engines should meet the requirements of 4.3.1 at all loads between 25-100% of the load range of the engines to which they are fitted.

  4.3.3 EGC units fitted to auxiliary diesel engines should meet the requirements of 4.3.1 at all loads between 10-100% of the load range of the engines to which they are fitted.

  4.3.4 EGC units fitted to diesel engines which supply power for both main propulsion and auxiliary purposes should meet the requirements of 4.3.3.

  4.3.5 EGC units fitted to boilers should meet the requirements of 4.3.1 at all loads between 10-100% of the load range (steaming rates) or, if the turn down ratio is smaller, over the actual load range of the boilers to which they are fitted.

  4.3.6 In order to demonstrate performance, emission measurements should be undertaken, with the agreement of the Administration, at a minimum of four load points. One load point should be at 95-100% of the maximum exhaust gas mass flow rate for which the unit is to be certified. One load point should be within ± 5% of the minimum exhaust gas mass flow rate for which the unit is to be certified. The other two load points should be equally spaced between the maximum and minimum exhaust gas mass flow rates. Where there are discontinuities in the operation of the system the number of load points should be increased, with the agreement of the Administration, so that it is demonstrated that the required performance over the stated exhaust gas mass flow rate range is retained. Additional intermediate load points should be tested if there is evidence of an emission peak below the maximum exhaust gas mass flow rate and above, if applicable, the minimum exhaust gas flow rate. These additional tests should be sufficient number as to establish the emission peak value.

  4.3.7 For loads below those specified in 4.3.2 to 4.3.5, the EGC unit should continue in operation. In those cases where the fuel oil combustion equipment may be required to operate under idling conditions, the SO2 emission concentration (ppm) at standardized O2 concentration (15.0% diesel engines, 3.0% boilers) should not exceed 50 ppm.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.