Before starting the test, condition at least 24 nozzles
at room temperature of 20°C to 25°C for at least 30 min.
The nozzles should be immersed in a bath of liquid, the
temperature of which should be 10 ± 2°C below the nominal
release temperature of the nozzles. After 5 min, the nozzles should
be removed from the bath and immersed immediately in another bath
of liquid, with the bulb seal downwards, at a temperature of 10 ±
1°C. Then test the nozzles in accordance with 5.5.1.