7.6.1 The main inlets and outlets of all ventilation
systems shall be capable of being closed from outside the spaces being
ventilated. The controls shall be easily accessible as well as prominently
and permanently marked and shall indicate whether the shut-off is
open or closed. In addition, such openings to areas of major fire
hazard shall be capable of being closed from a continuously manned
control station.
7.6.2 All ventilation fans shall be capable of
being stopped from outside the spaces which they serve, and from outside
the spaces in which they are installed. Ventilation fans serving areas
of major fire hazard shall be capable of being operated from a continuously
manned control station. The means provided for stopping the power
ventilation to the machinery space shall be separated from the means
provided for stopping ventilation of other spaces.
7.6.3 Areas of major fire hazard and spaces serving
as assembly stations shall have independent ventilation systems and
ventilation ducts. Ventilation ducts for areas of major fire hazard
shall not pass through other spaces, unless they are contained within
a trunk or in an extended machinery space or casing insulated in accordance
with tables 7.4-1 and 7.4-2; ventilation ducts of other
spaces shall not pass through areas of major fire hazard. Ventilation
outlets from areas of major fire hazard shall not terminate within
a distance of 1 m from any control station, evacuation station or
external escape route. In addition, exhaust ducts from galley ranges
shall be fitted with:
-
.1 a grease trap, readily removable for cleaning,
unless an alternative approved grease removal system is fitted;
-
.2 a fire damper located in the lower end of the
duct (the junction between the duct and the galley range hood) which
is automatically and remotely operated, and in addition a remotely
operated fire damper located in the upper end of the duct;
-
.3 a fixed means for extinguishing a fire within
the duct;
-
.4 remote control arrangements for shutting off
the exhaust fans and supply fans, for operating the fire dampers mentioned
in .2 and for operating the fire-extinguishing system, which shall
be placed in a position close to the entrance to the galley. Where
a multi-branch system is installed, a remote means, located with the
above controls, shall be provided to close all branches exhausting
through the same main duct before an extinguishing medium is released
into the system; and
-
.5 suitably located hatches for inspection and
cleaning. At minimum, one hatch shall be provided close to the exhaust
fan and others located in areas of high grease accumulation such as
the lower end of the duct as referred to in 7.6.3.2.
7.6.4 Where a ventilation duct passes through
a fire-resisting division, a fail safe automatic closing fire damper
shall be fitted adjacent to the division. The duct between the division
and the damper shall be of steel or other equivalent material and
insulated to the same standard as required for the fire resisting
division. The fire damper may be omitted where ducts pass through
spaces surrounded by fire-resisting divisions without serving those
spaces providing that the duct has the same structural fire protection
time as the divisions it penetrates. Where a ventilation duct passes
through a smoke-tight division, a smoke damper shall be fitted at
the penetration unless the duct which passes through the space does
not serve that space. Fire and smoke dampers shall be arranged so
as to be readily accessible. Where placed behind ceilings or linings,
they shall be provided with an inspection door marked to identify
the damper. Such identification shall also be placed on any required
remote controls.
7.6.5 Where ventilation systems penetrate decks,
the arrangements shall be such that the effectiveness of the deck
in resisting fire is not thereby impaired and precautions shall be
taken to reduce the likelihood of smoke and hot gases passing from
one between-deck space to another through the system.
7.6.6 All dampers fitted on fire-resisting or
smoke-tight divisions shall also be capable of being manually closed
from each side of the division in which they are fitted, except for
those dampers fitted on ducts serving spaces not normally manned such
as stores and toilets that may be manually operated only from outside
the served spaces. Manual closing may be achieved by mechanical means
of release or by remote operation of the fire or smoke damper by means
of a fail-safe electrical switch or pneumatic release (i.e. spring-loaded,
etc.). All dampers shall also be capable of being remotely closed
from the continuously manned control station.
7.6.7 Ducts shall be made of non-combustible or
fire restricting material. Short ducts, however, may be of combustible
materials subject to the following conditions:
-
.1 their cross-section does not exceed 0.02 m2;
-
.2 their length does not exceed 2 m;
-
.3 they may only be used at the terminal end of
the ventilation system;
-
.4 they shall not be situated less than 600 mm
from an opening in a fire-resisting or fire-restricting division;
and
-
.5 their surfaces have low flame spread characteristics.