2.5.1 For determining the size of devices to avoid
inadmissible pressure or vacuum in cargo tanks during loading or discharging,
calculations of pressure losses should be carried out. The following
parameters should be taken into account:
-
.1 loading/discharge rates;
-
.2 gas evolution;
-
.3 pressure loss across devices, taking into account
the resistance coefficient;
-
.4 pressure loss in the vent piping system;
-
.5 pressure at which the vent opens if a high
velocity valve is used;
-
.6 density of the saturated vapour/air mixture;
and
-
.7 to compensate for possible fouling of a flame
arrester, 70% of its rated performance is to be used in the pressure
drop calculation of the installation.
2.5.2 Devices should be located at the outlets
to atmosphere unless tested and approved for in-line installation.
Devices for in-line installation may not be fitted at the outlets
to atmosphere unless they have also been tested and approved for that
position.
2.5.3 End of line devices which are intended for
exclusive use at openings of inerted cargo tanks need not be tested
against endurance burning as specified in 3.2.3.
2.5.4 Where end-of-line devices are fitted with
cowls, weather hoods and deflectors, etc., these attachments should
be fitted for the tests described in 3.2.
2.5.5 Where detonation flame arresters are installed,
as in-line devices venting to atmosphere, they should be located at
a sufficient distance from the open end of the pipeline so as to preclude
the possibility of a stationary flame resting on the arrester.
2.5.6 When venting to atmosphere is not performed
through an end-of-line device according to 2.5.4, or a detonation
flame arrester according to 2.5.5, the in-line device has to be specifically
tested with the inclusion of all pipes, tees, bends, cowls, weather
hoods, etc., which may be fitted between the device and atmosphere.
The testing should consist of the flashback test of 3.2.2 and, if for the given installation
it is possible for a stationary flame to rest on the device, the testing
should also include the endurance burning test of 3.2.3.
2.5.7 Means should be provided to enable personnel
to reach devices situated more than 2 m above deck to facilitate maintenance,
repair and inspection.