Statutory Documents - IMO Publications and Documents - Circulars - Maritime Safety Committee - MSC/Circular.1035 – Guidelines for the use and Installation of Detectors Equivalent to Smoke Detectors – (Adopted on 28 May 2002) - Annex - Guidelines for the use and Installation of Detectors Equivalent to Smoke Detectors - Principal requirements

Principal requirements

  3 The requirements of chapter 9 of the Fire Safety Systems (FSS) Codefootnote, except as modified by these guidelines, should apply.

  4 Where carbon monoxide detectors are used, the alarm threshold should be set at 40 ppm with the ability of the detector to be adjusted to high and low sensitivity settings in order to obtain the optimum performance after considering the fire hazard and the likely source and to minimise false alarms.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.