9.5.1 In spaces where main or auxiliary oil-fired
boilers and other fired processes of equivalent thermal rating are
situated, or in spaces containing oil fuel units or settling tanks,
the unit should be provided with the following:
Where the machinery space and spaces containing fired processes
are not entirely separate, or if fuel oil can drain from the latter
spaces into the machinery space, the combined machinery space and
fired process space should be considered as one compartment.
-
.2 At least two approved portable foam extinguishers
or equivalent in each space containing a fired process and each space
in which a part of the oil fuel installation is situated. In addition,
at least one extinguisher of the same description with a capacity
of 9l for each burner, provided that the total capacity
of the additional extinguisher or extinguishers need not exceed 45l for any one space.
-
.3 A receptacle containing sand, sawdust impregnated
with soda, or other approved dry material in such quantity as may
be required by the Administration. An approved portable extinguisher
may be provided as an alternative.
9.5.2 Spaces containing internal combustion machinery
used either for main propulsion or for other purposes, when such machinery
has a total power output of not less than 750 kW, should be provided
with the following arrangements:
-
.1 One of the fixed arrangements required by 9.5.1.1;
and
-
.2 One approved foam-type extinguisher of not
less than 45l capacity or equivalent in every engine
space and one approved portable foam extinguisher for each 750 kW
of engine power output or part thereof. The total number of portable
extinguishers so supplied should be not less than two and need not
exceed six.
9.5.3 The Administration should give special consideration
to the fire-extinguishing arrangements to be provided in spaces not
fitted with fixed fire-extinguishing installations containing steam
turbines which are separated from boiler rooms by watertight bulkheads.
9.5.4 Where, in the opinion of the Administration,
a fire hazard exists in any machinery space for which no specific
provisions for fire-extinguishing appliances are prescribed in 9.5.1
to 9.5.3, there should be provided in, or adjacent to, that space
a number of approved portable fire extinguishers or other means of
fire extinction to the satisfaction of the Administration.