(1) Fire hydrant shall be positioned so as to
allow easy and quick connection of fire hoses and so that at least
one jet can be directed into any part of the vessel which is normally
accessible during navigation.
(2) The jet required in paragraph (1) shall be
from a single length of fire hose.
(3) In addition to the requirements of paragraph
(1), machinery spaces of category A shall be provided with at least
one hydrant complete with fire hose and dual purpose nozzle. The fire
hydrant shall be located outside the spaces and near the entrance.
(4) For every required fire hydrant there shall
be one fire hose. At least one spare fire hose shall be provided in
addition to this requirement.
(5) Single lengths of fire hose shall not exceed
20 m.
(6) Fire hoses shall be of an approved material.
Each fire hose shall be provided with couplings and a dual purpose
nozzle.
(7) Except where fire hoses are permanently attached
to the fire main, the couplings of fire hoses and nozzles shall be
completely interchangeable.
(8) The nozzles as required by paragraph (6) shall
be appropriate to the delivery capacity of the fire pumps fitted,
but in any case shall have a diameter of not less than 12 mm.