.1 Systems (such as purifiers) for preparing flammable
liquid for use in boilers and machinery are subject to the following
additional requirements.
.2 The main components in such systems shall be
placed in a separate room, enclosed by steel bulkheads extending from
deck to deck and provided with self-closing steel doors.
.3 Rooms in which flammable liquids are handled
as specified in 5.2.1 shall be provided with:
-
.1 independent mechanical ventilation or a ventilation
arrangement which can be isolated from the machinery space ventilation
-
.2 fire detecting system
-
.3 fixed fire extinguishing installation.
The extinguishing installation shall be capable of being activated
from outside the room.
Closing of ventilation openings shall be effected from a position
close to where the extinguishing system is activated.
The
extinguishing system shall be separate from the room, but may be a
part of the main fire extinguishing system for the machinery space.
.4 If it is impracticable to locate the main components
of such systems in a separate space, special consideration shall be
given with regard to location, containment of possible leakages, and
shielding of the components.