The water droplet size distribution and droplet velocity
distribution should be determined in accordance with 4.11.2 for each design nozzle at
the minimum and maximum operating pressures, and minimum and maximum
air flow rates, when used, as part of the identification of the discharge
characteristics of the nozzles which have demonstrated compliance
with the fire test. The measurements should be made at two representative
locations:
-
.1 perpendicular to the central axis of the nozzle,
exactly 1 m below the discharge orifice or discharge deflector; and
-
.2 radially outward from the first location at
either 0.5 m or 1 m distance, depending on the distribution pattern.