Water should be discharged from a spray nozzle at the minimum
operating and rated working pressure. A second automatic nozzle located
at the minimum distance specified by the manufacturer should be mounted
on a pipe parallel to the pipe discharging water.
The nozzle orifices or distribution plates (if used), should
be placed 550 mm, 356 mm and 152 mm below a flat smooth ceiling for
three separate tests, respectively at each test pressure. The top
of a square pan measuring 305 mm square and 102 mm deep should be
positioned 152 mm below the heat responsive element for each test.
The pan should be filled with 0.47l of heptane. After ignition, the
automatic nozzle should operate before the heptane is consumed.