FSS Code
|
Interpretation or reference
|
Chapter
|
Paragraph
|
Application
|
3
|
2.1.1.4
|
Personal Equipment
Reference is made to IEC Publication 60079- Electrical
Apparatus for Explosive Gas Atmospheres.
|
4
|
-
|
Fire Extinguishers
Reference is made to resolution A.951(23) - improved Guidelines for marine
portable fire extinguishers, as amended by resolution A.951(23).
|
4
|
2.1.1.2
|
Equivalents of fire extinguishers
Reference is made to the international standard on fire
protection equipment - portable fire extinguisher - performance and
construction, to be developed by ISO (ISO/DIS 7156E).
|
4
|
3.1.2
|
Recharging of spare charges
Partially emptied extinguishers should also be recharged.
|
5
|
2.1.1.1
|
Separation of spaces
Two spaces can be considered as separated spaces where fire
divisions as required by regulations 9.2.2, 9.2.3 and 9.2.4, as appropriate,
or divisions of steel are provided between them.
|
5
|
2.1.1.3
|
Means for checking the quantity of medium in containers
Means for checking the quantity of medium in containers
should be so arranged that it is not necessary to move the containers
completely from their fixing position. This is achieved, for instance, by
providing hanging bars above each bottle row for a weighing device or by
using suitable surface indicators.
|
5
|
2.1.3.2
|
Certain spaces for which the automatic warning of release of the
extinguishing medium is required
Ordinary cargo holds need not comply with regulation
2.1.3.2. However, ro-ro cargo spaces, holds in container ships equipped for
integrated reefer containers and other spaces where personnel can be
expected to enter and where the access is therefore facilitated by doors or
manway hatches should comply with the above regulation.
|
5
|
2.2
|
Low pressure CO2 systems
Where a low pressure CO2 system is fitted to
comply with this regulation, the following applies:
1 The system
control devices and the refrigerating plants should be located within the
same room where the pressure vessels are stored.
2
The rated amount of liquid carbon dioxide should be stored in
vessel(s) under the working pressure in the range of 1.8 to 2.2
N/mm2. The normal liquid charge in the container should be
limited to provide sufficient vapour space to allow for expansion of the
liquid under the maximum storage temperatures than can be obtained
corresponding to the setting of the pressure relief valves but should not
exceed 95% of the volumetric capacity of the container.
3 Provision should be made for:
- pressure gauge;
- high pressure alarm: not more than setting of the relief
valve;
- low pressure alarm: not less than 1.8 N/mm2;
- branch pipes with stop valves for filling the
vessel;
- discharge pipes;
- liquid CO2 level indicator, fitted on the
vessel(s);
- two safety valves.
4 The two safety relief valves should be
arranged so that either valve can be shut off while the other is
connected to the vessel. The setting of the relief valves should not be
less than 1.1 times working pressure. The capacity of each valve should
be such that the vapours generated under fire condition can be discharged
with a pressure rise not more than 20% above the setting pressure. The
discharge from the safety valves should be led to the open.
5 The vessel(s) and outgoing pipes permanently
filled with carbon dioxide should have thermal insulation preventing the
operation of the safety valve in 24 hours after de-energizing the plant,
at ambient temperature of 45°C and an initial pressure equal to the
starting pressure of the refrigeration unit.
6
The vessel(s) should be serviced by two automated completely
independent refrigerating units solely intended for this purpose, each
comprising a compressor and the relevant prime mover, evaporator and
condenser.
7 The refrigerating capacity and
the automatic control of each unit should be so as to maintain the
required temperature under conditions of continuous operation during 24
hours at sea temperatures up to 32°C and ambient air temperatures up to
45°C.
8 Each electric refrigerating unit
should be supplied from the main switchboard busbars by a separate
feeder.
9 Cooling water supply to the
refrigerating plant (where required) should be provided from at least two
circulating pumps one of which being used as a stand-by. The stand-by
pump may be a pump used for other services so long as its use for cooling
would not interfere with any other essential service of the ship. Cooling
water should be taken from not less than two sea connections, preferably
one port and one starboard.
10 Safety relief
devices should be provided in each section of pipe that may be isolated
by block valves and in which there could be a build-up of pressure in
excess of the design pressure of any of the components.
11 The piping system should be designed in such a way that
the CO2 pressure at the nozzles should not be less than 1
N/mm2.
12 Audible and visual
alarms should be given in a central control station when:
- the pressure in the vessel(s) reaches the low and high
values according to 2;
- any one of the refrigerating units fails to
operate;
- the lowest permissible level of the liquid in the vessels
is reached.
13 If the system serves more than one space,
means for control of discharge quantities of CO2 should be
provided, e.g. automatic timer or accurate level indicators located at
the control position(s).
14 If a device is
provided which automatically regulates the discharge of the rated
quantity of carbon dioxide into the protected spaces, it should be also
possible to regulate the discharge manually.
|
7
|
2.1.1.2
|
Areas for increased application rates
An indication of areas for which increased application rates
may be required is given below:
|
|
|
Protected Area
|
Application rate
|
|
|
Boiler
fronts or roof, firing areas, oil fuel units, centrifugal separators (not
oily water separators), oil purifiers, and clarifiers.
|
20
l /min/m2
|
|
|
Hot oil fuel
pipes near exhausts or similar heated surfaces on main or auxiliary diesel
engines
|
10
l /min/m2
|
8
|
2.1.1
|
Dry pipe systems in saunas
For the definition of "dry pipe system" see resolution A.800(19), Annex, paragraph 2.3.
|
8
|
2.5.2.3
|
Definition of nominal area
Nominal area is defined as being the gross, horizontal
projection of the area to be covered.
|
9
|
2.4.1.1
|
Acceptable activating arrangements
The following arrangement may be acceptable to:
.1 activate a paging system;
.2 activate the fan stops;
.3
activate the closure of fire doors;
.4
activate the closure of fire dampers;
.5
activate the sprinkler system;
.6
activate the smoke extraction system; and
.7
activate the low-location lighting system.
|
9
|
2.1.4
|
Relevant definitions
Loop means electrical circuit linking detectors of various sections
in a sequence and connected (input and output) to the indicating
unit(s). Zone address identification capability
means a system with individually identifiable fire detectors.
|
9
|
2.1.3
|
Testing of detectors within cold spaces
Detectors installed within cold spaces such as refrigerated
compartments should be tested according to IEC Publication 60068-2-1 -
Section one - Test Aa.
|
10
|
2.1.2
|
Calculation of intervals
The interval (I) should depend on the number of scanning
points (N) and the response time of the fans (T). (See
interpretation of paragraph 2.2.2 chapter 10 below.) With a
20 % allowance:
However, the maximum allowable interval should not exceed
120 s (x max = 120 s).
|
10
|
2.2.2
|
Response time for fans
Depending on the capacity of the fans and the length of
system piping the maximum response time of the fans in combination with the
system piping should be around 15 s.
|
12
|
2.2.2.1
|
Heating of diesel driven power sources and other means of starting
1 If the room for the diesel driven power source is
not heated, the diesel driven power source for the pump should be fitted
with electric heating of cooling water or lubricating oil.
2 The other means of starting include those by
compressed air, electricity, or other sources of stored energy, hydraulic
power or starting cartridges.
|
13
|
2.2.4
|
Size of landings and intermediate landings
If landings can be entered directly via entrance doors,
situated in stairway enclosures, the area of such landings should comply
with the requirements of paragraph 2.2.4 of chapter 13. However, if landings cannot be entered by entrance
doors, such landings should be considered as intermediate landings which
should comply with the capacity requirements as given in paragraph 2.3.1 of
chapter 13.
|
14
|
2.1.3
|
Capacity, use and handling of deck foam systems
A common line for fire main and deck foam line can only be
accepted provided it can be demonstrated that the hose nozzles can be
effectively controlled by one person when supplied from the common line at a
pressure needed for operation of the monitors. Additional foam concentrate
should be provided for operation of 2 nozzles for the same period of time
required for the foam system. The simultaneous use of the minimum required
jets of water should be possible on deck over the full length of the ship,
in the accommodation, service spaces, control stations and machinery spaces.
|
14
|
2.3.2.3
|
Foam systems positions of aft monitors
The port and starboard monitors required by this paragraph
may also be located in the cargo area above oil bunker tanks adjacent to
cargo tanks if capable of protecting the deck below and aft of each other.
|
14
|
2.3.3
|
Application to tankers
This paragraph applies to all tankers regardless of their
size.
|
15
|
2.3.2.7
|
Arrangements for isolation of inert gas supply mains and cargo piping
systems
As a guide, the effective isolation required by this
paragraph may be achieved by the two arrangements shown in figures 1 and 2
of chapter 15 and paragraph
2.3.2.7 in the Appendix of this circular.
|