11.3.1 In all craft, the station or stations in
the operating compartment from which control of craft manoeuvring
and/or of its main machinery is exercised should be provided, within
easy reach of the crew member at that station, with controls for use
in an emergency to:
-
.1 activate fixed fire-extinguishing systems:
-
.2 close ventilation openings and stop ventilating
machinery supplying spaces covered by fixed fire-extinguishing systems,
if not incorporated in .1:
-
.3 shut off fuel supplied to machinery in main
and auxiliary machinery spaces:
-
.4 disconnect all electrical power sources from
the normal power distribution system (the operating control should
be guarded to reduce the risk of inadvertent or careless operation);
and
-
.5 stop main engine(s) and auxiliary machinery.
11.3.2 Where control of propulsion and manoeuvring
is provided at stations outside the operating compartment, such stations
should have direct communication with the operating compartment which
should be a continuously manned control station.