9.1 Dry pipe systems should be arranged such that
water will discharge from the farthest sprinkler within 60 s of actuation
of the sprinkler.
9.2 Compressed air may be taken from a dedicated
compressor or other reliable source.
9.2.1 A means should be provided to prevent water
from entering the air supply system.
9.3 Air pressure should be automatically maintained
to account for normal pressure fluctuations and air supply should
be arranged to prevent significant qualities entering the system when
the sprinklers activate.
9.4 An alarm should be provided on the bridge
to indicate low pressure in a dry pipe system.