Statutory Documents - IMO Publications and Documents - Resolutions - Assembly - IMO Resolution A.800(19) – Revised Guidelines for Approval of Sprinkler Systems Equivalent to that Referred to in SOLAS Regulation II-2/12 – (Adopted on 23 November 1995) - Appendix 1 - Component Manufacturing Standards for Water Mist Nozzles - 5 Methods Of Test [7] - 5.19 30-day leakage test (see 4.19) [7.20]

5.19 30-day leakage test (see 4.19 ) [7.20]

 Five nozzles should be installed on a water filled test line maintained under a constant pressure of twice the rated working pressure for 30 days at an ambient temperature of 20 ± 5°C.

 The nozzles should be inspected visually at least weekly for leakage. Following completion of this 30-day test, all samples should meet the leak resistance requirements specified in 4.8 and should exhibit no evidence of distortion or other mechanical damage.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.