In assessing the damage stability of column stabilized units,
the following extent of damage should be assumed:
-
.1 Only those columns on the periphery of the
unit should be assumed to be damaged and the damage should be assumed
in the exposed portions of the column.
-
.2 Columns which are subdivided into watertight
compartments by watertight flats should in general be assumed to be
damaged within anyone compartment enclosed by watertight flats. Columns
should be assumed to be flooded by damage having a vertical extent
of 3.0 metres occurring at any level between 5.0 metres above and
3.0 metres below the draughts specified in the Operating Manual. Lesser
distances above or below the draughts may be applied to the satisfaction
of the Administration, taking into account the actual operating conditions.
However, the extent of required damage region should be at least 1.5
metres above and below the draughts specified in the Operating Manual
and where a watertight flat is located within this region, the damage
should be assumed to have occurred in both compartments above and
below the watertight flat in question.
-
.3 No vertical bulkhead should be assumed to be
damaged, except where bulkheads are spaced closer than a distance
of one eighth of the column perimeter at the draught under consideration,
measured at the periphery, in which case one or more of the bulkheads
should be disregarded.
-
.4 Horizontal penetration of damage should be
assumed to be 1.5 metres.
-
.5 Footings should be assumed to be damaged when
operating in a light or transit condition in the same manner as indicated
in 3.5.3.1 to 3.5.3.4 or in 3.5.2, having regard to their shape.
-
.6 All piping, ventilation systems, trunks, etc.,
within the extent of damage should be assumed to be damaged. Positive
means of closure should be provided at watertight boundaries to preclude
the progressive flooding of other spaces which are intended to be
intact.