7.8 Protection of special category
                     spaces and ro-ro spaces
                  
                  
                  
                  
                  
                  
                  
                  
                  
                  
                     
                        
                         
                        
                           7.8.1 Structural protection
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.1.1 Subject to 7.8.1.2 boundaries of special
                                 category spaces shall be insulated in accordance with tables 7.4-1 and 7.4-2.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.1.2 The vehicle deck of a special category
                                 space or a ro-ro space, including an open ro-ro space, need only be
                                 insulated on the underside if required. Vehicle decks located totally
                                 within ro-ro spaces may be accepted without structural fire protection,
                                 provided these decks are not part of, or do not provide support to,
                                 the craft's main load-carrying structure and provided satisfactory
                                 measures are taken to ensure that the safety of the craft, including
                                 fire-fighting abilities, integrity of fire resisting divisions and
                                 means of evacuation, is not affected by a partial or total collapse
                                 of these internal decks.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.1.3 Indicators shall be provided on the navigation
                                 bridge which shall indicate when any door leading to or from the special
                                 category space or ro-ro space is closed.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.1.4 Fire doors in boundaries of special category
                                 spaces leading to spaces below the vehicle deck shall be arranged
                                 with coamings of a height of at least 100 mm.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.2 Fixed fire-extinguishing
                           system
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.2.1 Each special category space and ro-ro
                                 space shall be fitted with an approved fixed pressure water-spraying
                                 systemfootnote for manual operation which
                                 shall protect all parts of any deck and vehicle platform in such space,
                                 provided that the Administration may permit the use of any other fixed
                                 fire-extinguishing system that has been shown by full-scale test in
                                 conditions simulating a flowing petrol fire in the space to be not
                                 less effective in controlling fires likely to occur in such a space.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.2.2 The pumps of the system shall be capable
                                 of maintaining:
                               
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 half the total required application rate with
                                       any one pump unit out of function, for category A craft; and
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .2 the total required application rate with any
                                       one pump unit out of function, for category B craft.
                                     
                                    
                                    
                                  
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.2.3 Fixed fire-extinguishing systems shall
                                 fulfil the following requirements:
                               
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 the valve manifold shall be provided with a
                                       pressure gauge, and each of the valves shall be marked to identify
                                       the protected areas;
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .2 instructions for maintenance and operation
                                       of the installation shall be set up in the room where the valves are
                                       located; and
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .3 the piping system shall be provided with a
                                       sufficient number of drainage valves.
                                     
                                    
                                    
                                  
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.3 Patrols and detection
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.3.1 A continuous fire patrol shall be maintained
                                 in special category spaces and ro-ro spaces unless a fixed fire-detection
                                 and fire alarm system, complying with the requirements of 7.7.1, and a television surveillance
                                 system are provided. The fixed fire-detection system shall be capable
                                 of rapidly detecting the onset of fire. The spacing and location of
                                 detectors shall be tested taking into account the effects of ventilation
                                 and other relevant factors.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.3.2 Manually operated call points shall be
                                 provided as necessary throughout the special category spaces and ro-ro
                                 spaces and one shall be placed close to each exit from such spaces.
                                 Manually operated call points shall be spaced so that no part of the
                                 space shall be more than 20 m from a manually operated call point.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.4 Fire-extinguishing equipment
                        
                        
                        
                        
                           
                           
                              
                              
                               There shall be provided in each special category space and
                                 ro-ro space:
                               
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 at least three water fog applicators, which
                                       shall consist of a metal L-shaped pipe, the long limb being approximately
                                       2 m in length and capable of being fitted to a fire hose, and the
                                       short limb being approximately 250 mm in length and fitted with a
                                       fixed water fog nozzle or capable of being fitted with a water spray
                                       nozzle;
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .2 one portable foam applicator unit consisting
                                       of an air foam nozzle of an inductor type capable of being connected
                                       to the fire main by a fire hose, together with a portable tank containing
                                       20 l  of foam-making liquid and one spare tank. The nozzle shall
                                       be capable of producing effective foam suitable for extinguishing
                                       an oil fire of at least 1.5 m3/min. At least two portable
                                       foam applicator units shall be available in the craft for use in such
                                       space; and
                                       
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .3 portable fire extinguishers of approved type
                                       and design, located so that no point in the space is more than approximately
                                       15 m walking distance from an extinguisher, provided that at least
                                       one portable extinguisher is located at each access to such space.
                                       In addition to complying with 7.7.4,
                                       fire extinguishers shall be suitable for A and B class fires and have
                                       a capacity of 12 kg dry powder or equivalent.
                                       
                                     
                                    
                                    
                                  
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.5 Ventilation system
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.5.1 There shall be provided an effective power
                                 ventilation systemfootnote for the special
                                 category spaces and ro-ro spaces sufficient to give at least 10 air
                                 changes per hour while navigating and 20 air changes per hour at the
                                 quayside during vehicle loading and unloading operations. The system
                                 for such spaces shall be entirely separated from other ventilation
                                 systems and shall be operating at all times when vehicles are in such
                                 spaces. Ventilation ducts serving special category spaces and ro-ro
                                 spaces capable of being effectively sealed shall be separated for
                                 each such space. The system shall be capable of being controlled from
                                 a position outside such spaces.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.5.2 The ventilation shall be such as to prevent
                                 air stratification and the formation of air pockets.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.5.3 Means shall be provided to indicate in
                                 the operating compartment any loss or reduction of the required ventilating
                                 capacity.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.5.4 Arrangements shall be provided to permit
                                 a rapid shutdown and effective closure of the ventilation system in
                                 case of fire, taking into account the weather and sea conditions.
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.5.5 Ventilation ducts, including dampers,
                                 shall be made of steel or other equivalent material. Ducts lying inside
                                 the served space may be made of non-combustible or fire-restricting
                                 material.
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.6 Scuppers, bilge pumping
                           and drainage
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.6.1 In view of the serious loss of stability
                                 which could arise due to large quantities of water accumulating on
                                 the deck or decks consequent to the operation of the fixed pressure
                                 water-spraying system, pumping and drainage arrangements shall be
                                 such as to prevent such accumulation. Scuppers fitted for this purpose
                                 shall be so arranged as to ensure that such water is rapidly discharged
                                 directly overboard. Alternatively, pumping and drainage facility shall
                                 be provided additional to the requirements of chapter
                                    10. When it is required to maintain watertight or weathertight
                                 integrity, as appropriate, the scuppers shall be arranged so that
                                 they can be operated from outside the space protected.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.6.2 In respect of scuppers and drainage pumps
                                 fitted in accordance with 7.8.6.1:
                               
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 the amount of water for which drainage is provided
                                       shall take into account the capacity of both the water spraying system
                                       pumps and required number of fire hose nozzles;
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .2 the drainage system shall have a capacity of
                                       not less than 125% of the capacity specified in .1 above; and
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .3 bilge wells shall be of sufficient holding
                                       capacity and shall be arranged at the side shell of the ship at a
                                       distance from each other of not more than 40 m in each watertight
                                       compartment.
                                     
                                    
                                    
                                  
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.7 Precautions against
                           ignition of flammable vapours or liquids
                        
                        
                        
                        
                           
                           
                              
                              
                               
                                 7.8.7.1 On any deck or platform, if fitted, on
                                 which vehicles are carried and on which explosive vapours might be
                                 expected to accumulate, except platforms with openings of sufficient
                                 size permitting penetration of petrol gases downwards, equipment which
                                 may constitute a source of ignition of flammable vapours and, in particular,
                                 electrical equipment and wiring, shall be installed at least 450 mm
                                 above the deck or platform. Electrical equipment installed more than
                                 450 mm above the deck or platform shall be of a type enclosed and
                                 protected by an enclosure having an ingress protection based on an
                                 international standard acceptable to the Organization.footnoteHowever, if the installation electrical equipment
                                 and wiring less than 450 mm above the deck or platform is necessary
                                 for the safe operation of the craft, such electrical equipment and
                                 wiring may be installed provided that the equipment is certified "safe
                                 type" based on an international standard acceptable to the Organization.footnote
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.7.2 If installed in an exhaust ventilation
                                 duct, electrical equipment shall be certified "safe type".footnote The equipment and wiring, if fitted, shall
                                 be suitable for use based on standards acceptable to the Organizationfootnote and the outlet from any exhaust duct shall
                                 be sited in a safe position, having regard to other possible sources
                                 of ignition.
                                 
                               
                              
                              
                            
                           
                           
                           
                              
                              
                               
                                 7.8.7.3 If pumping and drainage arrangements are
                                 provided, it shall be ensured that:
                               
                              
                              
                              
                                 - 
                                    
                                    
                                    
                                       .1 water contaminated with petrol or other flammable
                                       substances is not drained to machinery spaces or other spaces where
                                       sources of ignition may be present; and
                                     
                                    
                                    
                                  
                                 - 
                                    
                                    
                                    
                                       .2 electrical equipment fitted in tanks or other
                                       components of the drainage system shall be of a type suitable for
                                       use in explosive petrol/air mixtures.
                                     
                                    
                                    
                                  
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                  
                     
                        
                         
                        
                           7.8.8 Open ro-ro spaces
                        
                        
                        
                        
                           
                           
                           
                           
                           
                              
                              
                               
                                 7.8.8.2 For those parts of a ro-ro space which
                                 are completely open from above, the requirements set out in 7.8.2, 
                                 7.8.3.1 and 7.8.6 need not be complied with. However,
                                 a continuous fire patrol or a television surveillance system shall
                                 be maintained.
                                 
                               
                              
                              
                            
                           
                           
                         
                        
                        
                      
                     
                   
                  
                
             | 
         
         
            
               
                  
                  
                  
                  
                     
                        | Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
                           and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
                           officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
                           Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
                           on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
                           Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
                           exclusively on the terms and conditions set out in that contract.
                           
                         | 
                          | 
                      
                   
                  
                
               
             |