4.21 Water shield [6.22 and 6.23]
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - Resolutions - Assembly - IMO Resolution A.800(19) – Revised Guidelines for Approval of Sprinkler Systems Equivalent to that Referred to in SOLAS Regulation II-2/12 – (Adopted on 23 November 1995) - Appendix 1 - Component Manufacturing Standards for Water Mist Nozzles - 4 Water Mist Nozzle Requirements - 4.21 Water shield [6.22 and 6.23]

4.21 Water shield [6.22 and 6.23]

4.21.1 General

 An automatic nozzle intended for use at intermediate levels or beneath open grating should be provided with a water shield which complies with 4.21.2 and 4.21.3.

4.21.2 Angle of protection (see 5.21.1 )

 Water shields should provide an "angle of protection" of 45° or less for the heat responsive element against direct impingement of run-off water from the shield caused by discharge from nozzles at higher elevations. Compliance with this requirement should be determined in accordance with 5.24.1.

4.21.3 Rotation (see 5.21.2 )

 Rotation of the water shield should not alter the nozzle service load when evaluated in accordance with 5.24.2.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.