Type of Space
|
Minimum number of extinguishers1
|
Class(es) of extinguisher(s)
|
Space containing the controls for the
main source of electrical power
|
1; and 1 additional extinguisher
suitable for electrical fires when main switchboards are arranged in the
space
|
A and/or C
|
Cranes: With electric
motors/hydraulics
|
0
|
|
Cranes:
With internal combustion engine
|
2
|
B
|
(1 in cab
and 1 at exterior of engine compartment)
|
Drill floor
|
2
|
C
|
(1 at each
exit)
|
Helidecks
|
In accordance with section
9.17
|
B
|
Machinery spaces of category A
|
In accordance with section 9.9
|
B
|
Machinery spaces of category A which
are periodically unattended
|
At each entrance in accordance with
section 9.92
|
B
|
Main switchboards
|
2 in the vicinity
|
C
|
Mud pits, Mud processing
areas
|
1 for each enclosed space
(Travel distance to an extinguisher not to exceed 10 m for
open space)
|
B
|
Note
1 Minimum size should be in accordance
with paragraph 3.1.1 of chapter 4 of the FSS Code.
Note
2 A portable extinguisher provided for
that space may be located outside near the entrance to that space.
A portable fire extinguisher placed outside near the
entrance to that space may also be considered as satisfying the
provisions for the space in which it is located.
|