9.10 Portable fire extinguishers in accommodation, service and working spaces
Clasification Society 2024 - Version 9.40
Statutory Documents - IMO Publications and Documents - International Codes - 2009 MODU Code - Code for the Construction and Equipment of Mobile Offshore Drilling Units, 2009 – Resolution A.1023(26) - Chapter 9 - Fire Safety - 9.10 Portable fire extinguishers in accommodation, service and working spaces

9.10 Portable fire extinguishers in accommodation, service and working spaces

  9.10.1 Except for the supplemental arrangements provided in paragraph 9.10.2, portable fire extinguishers in accommodation spaces, service spaces, control stations, machinery spaces of category A, other machinery spaces, cargo spaces, weather deck and other spaces should be provided in number and arrangement in accordance with the guidance provided by the Organizationfootnote to the satisfaction of the Administration.

  9.10.2 Table 9-3 contains supplemental recommendations for number and distribution of additional portable fire extinguishers on mobile offshore drilling units. Where the recommendations in table 9-3 differ from the guidance provided by the Organizationfootnote, the provisions of table 9-3 should be followed. In all cases, the selection of the fire extinguishing medium should be based on the fire hazard for the space protected.footnote The classes of portable fire extinguishers in the table are only for reference.

Table 9-3 Recommended number and distribution of additional portable extinguishers

Type of Space Minimum number of extinguishers1 Class(es) of extinguisher(s)
Space containing the controls for the main source of electrical power 1; and 1 additional extinguisher suitable for electrical fires when main switchboards are arranged in the space A and/or C
Cranes:
With electric motors/hydraulics
0  
Cranes:
With internal combustion engine
2
B
(1 in cab and 1 at exterior of engine compartment)
Drill floor 2 C
(1 at each exit)
Helidecks In accordance with section 9.17 B
Machinery spaces of category A In accordance with section 9.9 B
Machinery spaces of category A which are periodically unattended At each entrance in accordance with section 9.92 B
Main switchboards 2 in the vicinity C
Mud pits, Mud processing areas 1 for each enclosed space
(Travel distance to an extinguisher not to exceed 10 m for open space)
B

Note 1 Minimum size should be in accordance with paragraph 3.1.1 of chapter 4 of the FSS Code.

Note 2 A portable extinguisher provided for that space may be located outside near the entrance to that space.

A portable fire extinguisher placed outside near the entrance to that space may also be considered as satisfying the provisions for the space in which it is located.


Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.